# checks an incrementor PV to see if it's incrementing. # the incrementors are updated by matlab processes. # Joe's matlab code # this will be 0 if old = current (i.e. not incrementing #function running = check_running(new_string, old_string) # running = abs(sign(str2double(new_string)-str2double(old_string))); #end # ======================================================= # A has current, B has previous record(calcout, "ALRM:SYS1:BPMRPTR:SCAN") { field(CALC, "A=B?0:A+1") field(SCAN, "1 second") field(INPA, "ALRM:SYS1:BPMRPTR:SCAN.VAL") field(INPB, "30") field(OUT, "ALRM:SYS1:BPMRPTR:ALHBCURR.VAL PP") field(DOPT, "Use CALC") field(OOPT, "Transition To Zero") } record(ai, "ALRM:SYS1:BPMRPTR:ALHBCURR") { field(INP, "PHYS:SYS1:1:BPMRPTR NPP MS") field(SCAN, "Passive") field(FLNK, "ALRM:SYS1:BPMRPTR:ALHBCHK") } record(calc, "ALRM:SYS1:BPMRPTR:ALHBCHK") { field(CALC, "C>2?2:(A=B?1:0)") field(INPA, "ALRM:SYS1:BPMRPTR:ALHBCURR NPP MS") field(INPB, "ALRM:SYS1:BPMRPTR:ALHBPREV.VAL NPP MS") field(INPC, "ALRM:SYS1:BPMRPTR:ALHBCURR.SEVR") field(FLNK, "ALRM:SYS1:BPMRPTR:ALHBERR") } # MS will cause this to be invalid if the HBCHK is record(mbbi, "ALRM:SYS1:BPMRPTR:ALHBERR") { field(DESC, "BPMRPTR monitoring") field(INP, "ALRM:SYS1:BPMRPTR:ALHBCHK.VAL NPP MS") field(ZRSV, "NO_ALARM") field(ONSV, "MAJOR") field(TWSV, "INVALID") field(ZRST, "RUNNING") field(ONST, "NOT_RUNNING") field(TWST, "INVALID") field(FLNK, "ALRM:SYS1:BPMRPTR:ALHBPREV") } record(ai, "ALRM:SYS1:BPMRPTR:ALHBPREV") { field(INP, "ALRM:SYS1:BPMRPTR:ALHBCURR NPP NMS") } # checks an incrementor PV to see if it's incrementing. # the incrementors are updated by matlab processes. # Joe's matlab code # this will be 0 if old = current (i.e. not incrementing #function running = check_running(new_string, old_string) # running = abs(sign(str2double(new_string)-str2double(old_string))); #end # ======================================================= # A has current, B has previous record(calcout, "ALRM:SYS1:FACETEGR:SCAN") { field(CALC, "A=B?0:A+1") field(SCAN, "1 second") field(INPA, "ALRM:SYS1:FACETEGR:SCAN.VAL") field(INPB, "30") field(OUT, "ALRM:SYS1:FACETEGR:ALHBCURR.VAL PP") field(DOPT, "Use CALC") field(OOPT, "Transition To Zero") } record(ai, "ALRM:SYS1:FACETEGR:ALHBCURR") { field(INP, "PHYS:SYS1:1:FEEDBACK NPP MS") field(SCAN, "Passive") field(FLNK, "ALRM:SYS1:FACETEGR:ALHBCHK") } record(calc, "ALRM:SYS1:FACETEGR:ALHBCHK") { field(CALC, "C>2?2:(A=B?1:0)") field(INPA, "ALRM:SYS1:FACETEGR:ALHBCURR NPP MS") field(INPB, "ALRM:SYS1:FACETEGR:ALHBPREV.VAL NPP MS") field(INPC, "ALRM:SYS1:FACETEGR:ALHBCURR.SEVR") field(FLNK, "ALRM:SYS1:FACETEGR:ALHBERR") } # MS will cause this to be invalid if the HBCHK is record(mbbi, "ALRM:SYS1:FACETEGR:ALHBERR") { field(DESC, "FACETEGR monitoring") field(INP, "ALRM:SYS1:FACETEGR:ALHBCHK.VAL NPP MS") field(ZRSV, "NO_ALARM") field(ONSV, "MAJOR") field(TWSV, "INVALID") field(ZRST, "RUNNING") field(ONST, "NOT_RUNNING") field(TWST, "INVALID") field(FLNK, "ALRM:SYS1:FACETEGR:ALHBPREV") } record(ai, "ALRM:SYS1:FACETEGR:ALHBPREV") { field(INP, "ALRM:SYS1:FACETEGR:ALHBCURR NPP NMS") } # checks an incrementor PV to see if it's incrementing. # the incrementors are updated by matlab processes. # Joe's matlab code # this will be 0 if old = current (i.e. not incrementing #function running = check_running(new_string, old_string) # running = abs(sign(str2double(new_string)-str2double(old_string))); #end # ======================================================= # A has current, B has previous record(calcout, "ALRM:SYS1:LI20FBCK:SCAN") { field(CALC, "A=B?0:A+1") field(SCAN, "1 second") field(INPA, "ALRM:SYS1:LI20FBCK:SCAN.VAL") field(INPB, "30") field(OUT, "ALRM:SYS1:LI20FBCK:ALHBCURR.VAL PP") field(DOPT, "Use CALC") field(OOPT, "Transition To Zero") } record(ai, "ALRM:SYS1:LI20FBCK:ALHBCURR") { field(INP, "PHYS:LI20:1:TCAVFBCK NPP MS") field(SCAN, "Passive") field(FLNK, "ALRM:SYS1:LI20FBCK:ALHBCHK") } record(calc, "ALRM:SYS1:LI20FBCK:ALHBCHK") { field(CALC, "C>2?2:(A=B?1:0)") field(INPA, "ALRM:SYS1:LI20FBCK:ALHBCURR NPP MS") field(INPB, "ALRM:SYS1:LI20FBCK:ALHBPREV.VAL NPP MS") field(INPC, "ALRM:SYS1:LI20FBCK:ALHBCURR.SEVR") field(FLNK, "ALRM:SYS1:LI20FBCK:ALHBERR") } # MS will cause this to be invalid if the HBCHK is record(mbbi, "ALRM:SYS1:LI20FBCK:ALHBERR") { field(DESC, "LI20FBCK monitoring") field(INP, "ALRM:SYS1:LI20FBCK:ALHBCHK.VAL NPP MS") field(ZRSV, "NO_ALARM") field(ONSV, "MAJOR") field(TWSV, "INVALID") field(ZRST, "RUNNING") field(ONST, "NOT_RUNNING") field(TWST, "INVALID") field(FLNK, "ALRM:SYS1:LI20FBCK:ALHBPREV") } record(ai, "ALRM:SYS1:LI20FBCK:ALHBPREV") { field(INP, "ALRM:SYS1:LI20FBCK:ALHBCURR NPP NMS") } # checks an incrementor PV to see if it's incrementing. # the incrementors are updated by matlab processes. # Joe's matlab code # this will be 0 if old = current (i.e. not incrementing #function running = check_running(new_string, old_string) # running = abs(sign(str2double(new_string)-str2double(old_string))); #end # ======================================================= # A has current, B has previous record(calcout, "ALRM:SYS1:KLYSCUD:SCAN") { field(CALC, "A=B?0:A+1") field(SCAN, "1 second") field(INPA, "ALRM:SYS1:KLYSCUD:SCAN.VAL") field(INPB, "15") field(OUT, "ALRM:SYS1:KLYSCUD:ALHBCURR.VAL PP") field(DOPT, "Use CALC") field(OOPT, "Transition To Zero") } record(ai, "ALRM:SYS1:KLYSCUD:ALHBCURR") { field(INP, "PHYS:SYS1:1:KLYSCUD NPP MS") field(SCAN, "Passive") field(FLNK, "ALRM:SYS1:KLYSCUD:ALHBCHK") } record(calc, "ALRM:SYS1:KLYSCUD:ALHBCHK") { field(CALC, "C>2?2:(A=B?1:0)") field(INPA, "ALRM:SYS1:KLYSCUD:ALHBCURR NPP MS") field(INPB, "ALRM:SYS1:KLYSCUD:ALHBPREV.VAL NPP MS") field(INPC, "ALRM:SYS1:KLYSCUD:ALHBCURR.SEVR") field(FLNK, "ALRM:SYS1:KLYSCUD:ALHBERR") } # MS will cause this to be invalid if the HBCHK is record(mbbi, "ALRM:SYS1:KLYSCUD:ALHBERR") { field(DESC, "KLYSCUD monitoring") field(INP, "ALRM:SYS1:KLYSCUD:ALHBCHK.VAL NPP MS") field(ZRSV, "NO_ALARM") field(ONSV, "MAJOR") field(TWSV, "INVALID") field(ZRST, "RUNNING") field(ONST, "NOT_RUNNING") field(TWST, "INVALID") field(FLNK, "ALRM:SYS1:KLYSCUD:ALHBPREV") } record(ai, "ALRM:SYS1:KLYSCUD:ALHBPREV") { field(INP, "ALRM:SYS1:KLYSCUD:ALHBCURR NPP NMS") } # checks an incrementor PV to see if it's incrementing. # the incrementors are updated by matlab processes. # Joe's matlab code # this will be 0 if old = current (i.e. not incrementing #function running = check_running(new_string, old_string) # running = abs(sign(str2double(new_string)-str2double(old_string))); #end # ======================================================= # A has current, B has previous record(calcout, "ALRM:SYS1:OPREP:SCAN") { field(CALC, "A=B?0:A+1") field(SCAN, "1 second") field(INPA, "ALRM:SYS1:OPREP:SCAN.VAL") field(INPB, "15") field(OUT, "ALRM:SYS1:OPREP:ALHBCURR.VAL PP") field(DOPT, "Use CALC") field(OOPT, "Transition To Zero") } record(ai, "ALRM:SYS1:OPREP:ALHBCURR") { field(INP, "SIOC:SYS1:ML00:AO002 NPP MS") field(SCAN, "Passive") field(FLNK, "ALRM:SYS1:OPREP:ALHBCHK") } record(calc, "ALRM:SYS1:OPREP:ALHBCHK") { field(CALC, "C>2?2:(A=B?1:0)") field(INPA, "ALRM:SYS1:OPREP:ALHBCURR NPP MS") field(INPB, "ALRM:SYS1:OPREP:ALHBPREV.VAL NPP MS") field(INPC, "ALRM:SYS1:OPREP:ALHBCURR.SEVR") field(FLNK, "ALRM:SYS1:OPREP:ALHBERR") } # MS will cause this to be invalid if the HBCHK is record(mbbi, "ALRM:SYS1:OPREP:ALHBERR") { field(DESC, "OPREP monitoring") field(INP, "ALRM:SYS1:OPREP:ALHBCHK.VAL NPP MS") field(ZRSV, "NO_ALARM") field(ONSV, "MAJOR") field(TWSV, "INVALID") field(ZRST, "RUNNING") field(ONST, "NOT_RUNNING") field(TWST, "INVALID") field(FLNK, "ALRM:SYS1:OPREP:ALHBPREV") } record(ai, "ALRM:SYS1:OPREP:ALHBPREV") { field(INP, "ALRM:SYS1:OPREP:ALHBCURR NPP NMS") } # checks an incrementor PV to see if it's incrementing. # the incrementors are updated by matlab processes. # Joe's matlab code # this will be 0 if old = current (i.e. not incrementing #function running = check_running(new_string, old_string) # running = abs(sign(str2double(new_string)-str2double(old_string))); #end # ======================================================= # A has current, B has previous record(calcout, "ALRM:SYS1:WSTLOC:SCAN") { field(CALC, "A=B?0:A+1") field(SCAN, "1 second") field(INPA, "ALRM:SYS1:WSTLOC:SCAN.VAL") field(INPB, "30") field(OUT, "ALRM:SYS1:WSTLOC:ALHBCURR.VAL PP") field(DOPT, "Use CALC") field(OOPT, "Transition To Zero") } record(ai, "ALRM:SYS1:WSTLOC:ALHBCURR") { field(INP, "PHYS:LI20:1:WAIST NPP MS") field(SCAN, "Passive") field(FLNK, "ALRM:SYS1:WSTLOC:ALHBCHK") } record(calc, "ALRM:SYS1:WSTLOC:ALHBCHK") { field(CALC, "C>2?2:(A=B?1:0)") field(INPA, "ALRM:SYS1:WSTLOC:ALHBCURR NPP MS") field(INPB, "ALRM:SYS1:WSTLOC:ALHBPREV.VAL NPP MS") field(INPC, "ALRM:SYS1:WSTLOC:ALHBCURR.SEVR") field(FLNK, "ALRM:SYS1:WSTLOC:ALHBERR") } # MS will cause this to be invalid if the HBCHK is record(mbbi, "ALRM:SYS1:WSTLOC:ALHBERR") { field(DESC, "WSTLOC monitoring") field(INP, "ALRM:SYS1:WSTLOC:ALHBCHK.VAL NPP MS") field(ZRSV, "NO_ALARM") field(ONSV, "MAJOR") field(TWSV, "INVALID") field(ZRST, "RUNNING") field(ONST, "NOT_RUNNING") field(TWST, "INVALID") field(FLNK, "ALRM:SYS1:WSTLOC:ALHBPREV") } record(ai, "ALRM:SYS1:WSTLOC:ALHBPREV") { field(INP, "ALRM:SYS1:WSTLOC:ALHBCURR NPP NMS") } # checks an incrementor PV to see if it's incrementing. # the incrementors are updated by matlab processes. # Joe's matlab code # this will be 0 if old = current (i.e. not incrementing #function running = check_running(new_string, old_string) # running = abs(sign(str2double(new_string)-str2double(old_string))); #end # ======================================================= # A has current, B has previous record(calcout, "ALRM:SYS1:FACET:SCAN") { field(CALC, "A=B?0:A+1") field(SCAN, "1 second") field(INPA, "ALRM:SYS1:FACET:SCAN.VAL") field(INPB, "10") field(OUT, "ALRM:SYS1:FACET:ALHBCURR.VAL PP") field(DOPT, "Use CALC") field(OOPT, "Transition To Zero") } record(ai, "ALRM:SYS1:FACET:ALHBCURR") { field(INP, "OSC:LT10:20:FS_WATCHDOG NPP MS") field(SCAN, "Passive") field(FLNK, "ALRM:SYS1:FACET:ALHBCHK") } record(calc, "ALRM:SYS1:FACET:ALHBCHK") { field(CALC, "C>2?2:(A=B?1:0)") field(INPA, "ALRM:SYS1:FACET:ALHBCURR NPP MS") field(INPB, "ALRM:SYS1:FACET:ALHBPREV.VAL NPP MS") field(INPC, "ALRM:SYS1:FACET:ALHBCURR.SEVR") field(FLNK, "ALRM:SYS1:FACET:ALHBERR") } # MS will cause this to be invalid if the HBCHK is record(mbbi, "ALRM:SYS1:FACET:ALHBERR") { field(DESC, "FACET monitoring") field(INP, "ALRM:SYS1:FACET:ALHBCHK.VAL NPP MS") field(ZRSV, "NO_ALARM") field(ONSV, "MAJOR") field(TWSV, "INVALID") field(ZRST, "RUNNING") field(ONST, "NOT_RUNNING") field(TWST, "INVALID") field(FLNK, "ALRM:SYS1:FACET:ALHBPREV") } record(ai, "ALRM:SYS1:FACET:ALHBPREV") { field(INP, "ALRM:SYS1:FACET:ALHBCURR NPP NMS") } # checks an incrementor PV to see if it's incrementing. # the incrementors are updated by matlab processes. # Joe's matlab code # this will be 0 if old = current (i.e. not incrementing #function running = check_running(new_string, old_string) # running = abs(sign(str2double(new_string)-str2double(old_string))); #end # ======================================================= # A has current, B has previous record(calcout, "ALRM:SYS1:FACETEXP:SCAN") { field(CALC, "A=B?0:A+1") field(SCAN, "1 second") field(INPA, "ALRM:SYS1:FACETEXP:SCAN.VAL") field(INPB, "10") field(OUT, "ALRM:SYS1:FACETEXP:ALHBCURR.VAL PP") field(DOPT, "Use CALC") field(OOPT, "Transition To Zero") } record(ai, "ALRM:SYS1:FACETEXP:ALHBCURR") { field(INP, "OSC:LA20:10:FS_WATCHDOG NPP MS") field(SCAN, "Passive") field(FLNK, "ALRM:SYS1:FACETEXP:ALHBCHK") } record(calc, "ALRM:SYS1:FACETEXP:ALHBCHK") { field(CALC, "C>2?2:(A=B?1:0)") field(INPA, "ALRM:SYS1:FACETEXP:ALHBCURR NPP MS") field(INPB, "ALRM:SYS1:FACETEXP:ALHBPREV.VAL NPP MS") field(INPC, "ALRM:SYS1:FACETEXP:ALHBCURR.SEVR") field(FLNK, "ALRM:SYS1:FACETEXP:ALHBERR") } # MS will cause this to be invalid if the HBCHK is record(mbbi, "ALRM:SYS1:FACETEXP:ALHBERR") { field(DESC, "FACETEXP monitoring") field(INP, "ALRM:SYS1:FACETEXP:ALHBCHK.VAL NPP MS") field(ZRSV, "NO_ALARM") field(ONSV, "MAJOR") field(TWSV, "INVALID") field(ZRST, "RUNNING") field(ONST, "NOT_RUNNING") field(TWST, "INVALID") field(FLNK, "ALRM:SYS1:FACETEXP:ALHBPREV") } record(ai, "ALRM:SYS1:FACETEXP:ALHBPREV") { field(INP, "ALRM:SYS1:FACETEXP:ALHBCURR NPP NMS") } # checks an incrementor PV to see if it's incrementing. # the incrementors are updated by matlab processes. # Joe's matlab code # this will be 0 if old = current (i.e. not incrementing #function running = check_running(new_string, old_string) # running = abs(sign(str2double(new_string)-str2double(old_string))); #end # ======================================================= # A has current, B has previous record(calcout, "ALRM:SYS1:LI10ENGY:SCAN") { field(CALC, "A=B?0:A+1") field(SCAN, "1 second") field(INPA, "ALRM:SYS1:LI10ENGY:SCAN.VAL") field(INPB, "30") field(OUT, "ALRM:SYS1:LI10ENGY:ALHBCURR.VAL PP") field(DOPT, "Use CALC") field(OOPT, "Transition To Zero") } record(ai, "ALRM:SYS1:LI10ENGY:ALHBCURR") { field(INP, "SIOC:SYS1:ML00:AO050 NPP MS") field(SCAN, "Passive") field(FLNK, "ALRM:SYS1:LI10ENGY:ALHBCHK") } record(calc, "ALRM:SYS1:LI10ENGY:ALHBCHK") { field(CALC, "C>2?2:(A=B?1:0)") field(INPA, "ALRM:SYS1:LI10ENGY:ALHBCURR NPP MS") field(INPB, "ALRM:SYS1:LI10ENGY:ALHBPREV.VAL NPP MS") field(INPC, "ALRM:SYS1:LI10ENGY:ALHBCURR.SEVR") field(FLNK, "ALRM:SYS1:LI10ENGY:ALHBERR") } # MS will cause this to be invalid if the HBCHK is record(mbbi, "ALRM:SYS1:LI10ENGY:ALHBERR") { field(DESC, "LI10ENGY monitoring") field(INP, "ALRM:SYS1:LI10ENGY:ALHBCHK.VAL NPP MS") field(ZRSV, "NO_ALARM") field(ONSV, "MAJOR") field(TWSV, "INVALID") field(ZRST, "RUNNING") field(ONST, "NOT_RUNNING") field(TWST, "INVALID") field(FLNK, "ALRM:SYS1:LI10ENGY:ALHBPREV") } record(ai, "ALRM:SYS1:LI10ENGY:ALHBPREV") { field(INP, "ALRM:SYS1:LI10ENGY:ALHBCURR NPP NMS") } # checks an incrementor PV to see if it's incrementing. # the incrementors are updated by matlab processes. # Joe's matlab code # this will be 0 if old = current (i.e. not incrementing #function running = check_running(new_string, old_string) # running = abs(sign(str2double(new_string)-str2double(old_string))); #end # ======================================================= # A has current, B has previous record(calcout, "ALRM:SYS1:GUNWATCHER:SCAN") { field(CALC, "A=B?0:A+1") field(SCAN, "1 second") field(INPA, "ALRM:SYS1:GUNWATCHER:SCAN.VAL") field(INPB, "30") field(OUT, "ALRM:SYS1:GUNWATCHER:ALHBCURR.VAL PP") field(DOPT, "Use CALC") field(OOPT, "Transition To Zero") } record(ai, "ALRM:SYS1:GUNWATCHER:ALHBCURR") { field(INP, "PHYS:IN10:1:GUN NPP MS") field(SCAN, "Passive") field(FLNK, "ALRM:SYS1:GUNWATCHER:ALHBCHK") } record(calc, "ALRM:SYS1:GUNWATCHER:ALHBCHK") { field(CALC, "C>2?2:(A=B?1:0)") field(INPA, "ALRM:SYS1:GUNWATCHER:ALHBCURR NPP MS") field(INPB, "ALRM:SYS1:GUNWATCHER:ALHBPREV.VAL NPP MS") field(INPC, "ALRM:SYS1:GUNWATCHER:ALHBCURR.SEVR") field(FLNK, "ALRM:SYS1:GUNWATCHER:ALHBERR") } # MS will cause this to be invalid if the HBCHK is record(mbbi, "ALRM:SYS1:GUNWATCHER:ALHBERR") { field(DESC, "GUNWATCHER monitoring") field(INP, "ALRM:SYS1:GUNWATCHER:ALHBCHK.VAL NPP MS") field(ZRSV, "NO_ALARM") field(ONSV, "MAJOR") field(TWSV, "INVALID") field(ZRST, "RUNNING") field(ONST, "NOT_RUNNING") field(TWST, "INVALID") field(FLNK, "ALRM:SYS1:GUNWATCHER:ALHBPREV") } record(ai, "ALRM:SYS1:GUNWATCHER:ALHBPREV") { field(INP, "ALRM:SYS1:GUNWATCHER:ALHBCURR NPP NMS") } # checks an incrementor PV to see if it's incrementing. # the incrementors are updated by matlab processes. # Joe's matlab code # this will be 0 if old = current (i.e. not incrementing #function running = check_running(new_string, old_string) # running = abs(sign(str2double(new_string)-str2double(old_string))); #end # ======================================================= # A has current, B has previous record(calcout, "ALRM:SYS1:CATHSUPP:SCAN") { field(CALC, "A=B?0:A+1") field(SCAN, "1 second") field(INPA, "ALRM:SYS1:CATHSUPP:SCAN.VAL") field(INPB, "30") field(OUT, "ALRM:SYS1:CATHSUPP:ALHBCURR.VAL PP") field(DOPT, "Use CALC") field(OOPT, "Transition To Zero") } record(ai, "ALRM:SYS1:CATHSUPP:ALHBCURR") { field(INP, "PHYS:IN10:1:CATHSUPP NPP MS") field(SCAN, "Passive") field(FLNK, "ALRM:SYS1:CATHSUPP:ALHBCHK") } record(calc, "ALRM:SYS1:CATHSUPP:ALHBCHK") { field(CALC, "C>2?2:(A=B?1:0)") field(INPA, "ALRM:SYS1:CATHSUPP:ALHBCURR NPP MS") field(INPB, "ALRM:SYS1:CATHSUPP:ALHBPREV.VAL NPP MS") field(INPC, "ALRM:SYS1:CATHSUPP:ALHBCURR.SEVR") field(FLNK, "ALRM:SYS1:CATHSUPP:ALHBERR") } # MS will cause this to be invalid if the HBCHK is record(mbbi, "ALRM:SYS1:CATHSUPP:ALHBERR") { field(DESC, "CATHSUPP monitoring") field(INP, "ALRM:SYS1:CATHSUPP:ALHBCHK.VAL NPP MS") field(ZRSV, "NO_ALARM") field(ONSV, "MAJOR") field(TWSV, "INVALID") field(ZRST, "RUNNING") field(ONST, "NOT_RUNNING") field(TWST, "INVALID") field(FLNK, "ALRM:SYS1:CATHSUPP:ALHBPREV") } record(ai, "ALRM:SYS1:CATHSUPP:ALHBPREV") { field(INP, "ALRM:SYS1:CATHSUPP:ALHBCURR NPP NMS") } # checks an incrementor PV to see if it's incrementing. # the incrementors are updated by matlab processes. # Joe's matlab code # this will be 0 if old = current (i.e. not incrementing #function running = check_running(new_string, old_string) # running = abs(sign(str2double(new_string)-str2double(old_string))); #end # ======================================================= # A has current, B has previous record(calcout, "ALRM:SYS1:DEFENDER:SCAN") { field(CALC, "A=B?0:A+1") field(SCAN, "1 second") field(INPA, "ALRM:SYS1:DEFENDER:SCAN.VAL") field(INPB, "30") field(OUT, "ALRM:SYS1:DEFENDER:ALHBCURR.VAL PP") field(DOPT, "Use CALC") field(OOPT, "Transition To Zero") } record(ai, "ALRM:SYS1:DEFENDER:ALHBCURR") { field(INP, "PHYS:LI20:1:DEFENDER NPP MS") field(SCAN, "Passive") field(FLNK, "ALRM:SYS1:DEFENDER:ALHBCHK") } record(calc, "ALRM:SYS1:DEFENDER:ALHBCHK") { field(CALC, "C>2?2:(A=B?1:0)") field(INPA, "ALRM:SYS1:DEFENDER:ALHBCURR NPP MS") field(INPB, "ALRM:SYS1:DEFENDER:ALHBPREV.VAL NPP MS") field(INPC, "ALRM:SYS1:DEFENDER:ALHBCURR.SEVR") field(FLNK, "ALRM:SYS1:DEFENDER:ALHBERR") } # MS will cause this to be invalid if the HBCHK is record(mbbi, "ALRM:SYS1:DEFENDER:ALHBERR") { field(DESC, "DEFENDER monitoring") field(INP, "ALRM:SYS1:DEFENDER:ALHBCHK.VAL NPP MS") field(ZRSV, "NO_ALARM") field(ONSV, "MAJOR") field(TWSV, "INVALID") field(ZRST, "RUNNING") field(ONST, "NOT_RUNNING") field(TWST, "INVALID") field(FLNK, "ALRM:SYS1:DEFENDER:ALHBPREV") } record(ai, "ALRM:SYS1:DEFENDER:ALHBPREV") { field(INP, "ALRM:SYS1:DEFENDER:ALHBCURR NPP NMS") } # checks an incrementor PV to see if it's incrementing. # the incrementors are updated by matlab processes. # Joe's matlab code # this will be 0 if old = current (i.e. not incrementing #function running = check_running(new_string, old_string) # running = abs(sign(str2double(new_string)-str2double(old_string))); #end # ======================================================= # A has current, B has previous record(calcout, "ALRM:SYS1:LA10LASRARCH:SCAN") { field(CALC, "A=B?0:A+1") field(SCAN, "1 second") field(INPA, "ALRM:SYS1:LA10LASRARCH:SCAN.VAL") field(INPB, "30") field(OUT, "ALRM:SYS1:LA10LASRARCH:ALHBCURR.VAL PP") field(DOPT, "Use CALC") field(OOPT, "Transition To Zero") } record(ai, "ALRM:SYS1:LA10LASRARCH:ALHBCURR") { field(INP, "PHYS:LA10:1:LASR_ARCHIV NPP MS") field(SCAN, "Passive") field(FLNK, "ALRM:SYS1:LA10LASRARCH:ALHBCHK") } record(calc, "ALRM:SYS1:LA10LASRARCH:ALHBCHK") { field(CALC, "C>2?2:(A=B?1:0)") field(INPA, "ALRM:SYS1:LA10LASRARCH:ALHBCURR NPP MS") field(INPB, "ALRM:SYS1:LA10LASRARCH:ALHBPREV.VAL NPP MS") field(INPC, "ALRM:SYS1:LA10LASRARCH:ALHBCURR.SEVR") field(FLNK, "ALRM:SYS1:LA10LASRARCH:ALHBERR") } # MS will cause this to be invalid if the HBCHK is record(mbbi, "ALRM:SYS1:LA10LASRARCH:ALHBERR") { field(DESC, "LA10LASRARCH monitoring") field(INP, "ALRM:SYS1:LA10LASRARCH:ALHBCHK.VAL NPP MS") field(ZRSV, "NO_ALARM") field(ONSV, "MAJOR") field(TWSV, "INVALID") field(ZRST, "RUNNING") field(ONST, "NOT_RUNNING") field(TWST, "INVALID") field(FLNK, "ALRM:SYS1:LA10LASRARCH:ALHBPREV") } record(ai, "ALRM:SYS1:LA10LASRARCH:ALHBPREV") { field(INP, "ALRM:SYS1:LA10LASRARCH:ALHBCURR NPP NMS") } # checks an incrementor PV to see if it's incrementing. # the incrementors are updated by matlab processes. # Joe's matlab code # this will be 0 if old = current (i.e. not incrementing #function running = check_running(new_string, old_string) # running = abs(sign(str2double(new_string)-str2double(old_string))); #end # ======================================================= # A has current, B has previous record(calcout, "ALRM:SYS1:LA20LASRARCH:SCAN") { field(CALC, "A=B?0:A+1") field(SCAN, "1 second") field(INPA, "ALRM:SYS1:LA20LASRARCH:SCAN.VAL") field(INPB, "30") field(OUT, "ALRM:SYS1:LA20LASRARCH:ALHBCURR.VAL PP") field(DOPT, "Use CALC") field(OOPT, "Transition To Zero") } record(ai, "ALRM:SYS1:LA20LASRARCH:ALHBCURR") { field(INP, "PHYS:LA20:1:LASR_ARCHIV NPP MS") field(SCAN, "Passive") field(FLNK, "ALRM:SYS1:LA20LASRARCH:ALHBCHK") } record(calc, "ALRM:SYS1:LA20LASRARCH:ALHBCHK") { field(CALC, "C>2?2:(A=B?1:0)") field(INPA, "ALRM:SYS1:LA20LASRARCH:ALHBCURR NPP MS") field(INPB, "ALRM:SYS1:LA20LASRARCH:ALHBPREV.VAL NPP MS") field(INPC, "ALRM:SYS1:LA20LASRARCH:ALHBCURR.SEVR") field(FLNK, "ALRM:SYS1:LA20LASRARCH:ALHBERR") } # MS will cause this to be invalid if the HBCHK is record(mbbi, "ALRM:SYS1:LA20LASRARCH:ALHBERR") { field(DESC, "LA20LASRARCH monitoring") field(INP, "ALRM:SYS1:LA20LASRARCH:ALHBCHK.VAL NPP MS") field(ZRSV, "NO_ALARM") field(ONSV, "MAJOR") field(TWSV, "INVALID") field(ZRST, "RUNNING") field(ONST, "NOT_RUNNING") field(TWST, "INVALID") field(FLNK, "ALRM:SYS1:LA20LASRARCH:ALHBPREV") } record(ai, "ALRM:SYS1:LA20LASRARCH:ALHBPREV") { field(INP, "ALRM:SYS1:LA20LASRARCH:ALHBCURR NPP NMS") } # checks an incrementor PV to see if it's incrementing. # the incrementors are updated by matlab processes. # Joe's matlab code # this will be 0 if old = current (i.e. not incrementing #function running = check_running(new_string, old_string) # running = abs(sign(str2double(new_string)-str2double(old_string))); #end # ======================================================= # A has current, B has previous record(calcout, "ALRM:SYS1:FASTLASRARCH:SCAN") { field(CALC, "A=B?0:A+1") field(SCAN, "1 second") field(INPA, "ALRM:SYS1:FASTLASRARCH:SCAN.VAL") field(INPB, "30") field(OUT, "ALRM:SYS1:FASTLASRARCH:ALHBCURR.VAL PP") field(DOPT, "Use CALC") field(OOPT, "Transition To Zero") } record(ai, "ALRM:SYS1:FASTLASRARCH:ALHBCURR") { field(INP, "PHYS:LA10:1:FASTLASR_ARCHIV NPP MS") field(SCAN, "Passive") field(FLNK, "ALRM:SYS1:FASTLASRARCH:ALHBCHK") } record(calc, "ALRM:SYS1:FASTLASRARCH:ALHBCHK") { field(CALC, "C>2?2:(A=B?1:0)") field(INPA, "ALRM:SYS1:FASTLASRARCH:ALHBCURR NPP MS") field(INPB, "ALRM:SYS1:FASTLASRARCH:ALHBPREV.VAL NPP MS") field(INPC, "ALRM:SYS1:FASTLASRARCH:ALHBCURR.SEVR") field(FLNK, "ALRM:SYS1:FASTLASRARCH:ALHBERR") } # MS will cause this to be invalid if the HBCHK is record(mbbi, "ALRM:SYS1:FASTLASRARCH:ALHBERR") { field(DESC, "FASTLASRARCH monitoring") field(INP, "ALRM:SYS1:FASTLASRARCH:ALHBCHK.VAL NPP MS") field(ZRSV, "NO_ALARM") field(ONSV, "MAJOR") field(TWSV, "INVALID") field(ZRST, "RUNNING") field(ONST, "NOT_RUNNING") field(TWST, "INVALID") field(FLNK, "ALRM:SYS1:FASTLASRARCH:ALHBPREV") } record(ai, "ALRM:SYS1:FASTLASRARCH:ALHBPREV") { field(INP, "ALRM:SYS1:FASTLASRARCH:ALHBCURR NPP NMS") } # checks an incrementor PV to see if it's incrementing. # the incrementors are updated by matlab processes. # Joe's matlab code # this will be 0 if old = current (i.e. not incrementing #function running = check_running(new_string, old_string) # running = abs(sign(str2double(new_string)-str2double(old_string))); #end # ======================================================= # A has current, B has previous record(calcout, "ALRM:SYS1:STEERING:SCAN") { field(CALC, "A=B?0:A+1") field(SCAN, "1 second") field(INPA, "ALRM:SYS1:STEERING:SCAN.VAL") field(INPB, "30") field(OUT, "ALRM:SYS1:STEERING:ALHBCURR.VAL PP") field(DOPT, "Use CALC") field(OOPT, "Transition To Zero") } record(ai, "ALRM:SYS1:STEERING:ALHBCURR") { field(INP, "PHYS:LA20:1:STEERING NPP MS") field(SCAN, "Passive") field(FLNK, "ALRM:SYS1:STEERING:ALHBCHK") } record(calc, "ALRM:SYS1:STEERING:ALHBCHK") { field(CALC, "C>2?2:(A=B?1:0)") field(INPA, "ALRM:SYS1:STEERING:ALHBCURR NPP MS") field(INPB, "ALRM:SYS1:STEERING:ALHBPREV.VAL NPP MS") field(INPC, "ALRM:SYS1:STEERING:ALHBCURR.SEVR") field(FLNK, "ALRM:SYS1:STEERING:ALHBERR") } # MS will cause this to be invalid if the HBCHK is record(mbbi, "ALRM:SYS1:STEERING:ALHBERR") { field(DESC, "STEERING monitoring") field(INP, "ALRM:SYS1:STEERING:ALHBCHK.VAL NPP MS") field(ZRSV, "NO_ALARM") field(ONSV, "MAJOR") field(TWSV, "INVALID") field(ZRST, "RUNNING") field(ONST, "NOT_RUNNING") field(TWST, "INVALID") field(FLNK, "ALRM:SYS1:STEERING:ALHBPREV") } record(ai, "ALRM:SYS1:STEERING:ALHBPREV") { field(INP, "ALRM:SYS1:STEERING:ALHBCURR NPP NMS") } # checks an incrementor PV to see if it's incrementing. # the incrementors are updated by matlab processes. # Joe's matlab code # this will be 0 if old = current (i.e. not incrementing #function running = check_running(new_string, old_string) # running = abs(sign(str2double(new_string)-str2double(old_string))); #end # ======================================================= # A has current, B has previous record(calcout, "ALRM:SYS1:BPMCALMGR:SCAN") { field(CALC, "A=B?0:A+1") field(SCAN, "1 second") field(INPA, "ALRM:SYS1:BPMCALMGR:SCAN.VAL") field(INPB, "5") field(OUT, "ALRM:SYS1:BPMCALMGR:ALHBCURR.VAL PP") field(DOPT, "Use CALC") field(OOPT, "Transition To Zero") } record(ai, "ALRM:SYS1:BPMCALMGR:ALHBCURR") { field(INP, "SIOC:SYS1:ML00:AO048 NPP MS") field(SCAN, "Passive") field(FLNK, "ALRM:SYS1:BPMCALMGR:ALHBCHK") } record(calc, "ALRM:SYS1:BPMCALMGR:ALHBCHK") { field(CALC, "C>2?2:(A=B?1:0)") field(INPA, "ALRM:SYS1:BPMCALMGR:ALHBCURR NPP MS") field(INPB, "ALRM:SYS1:BPMCALMGR:ALHBPREV.VAL NPP MS") field(INPC, "ALRM:SYS1:BPMCALMGR:ALHBCURR.SEVR") field(FLNK, "ALRM:SYS1:BPMCALMGR:ALHBERR") } # MS will cause this to be invalid if the HBCHK is record(mbbi, "ALRM:SYS1:BPMCALMGR:ALHBERR") { field(DESC, "BPMCALMGR monitoring") field(INP, "ALRM:SYS1:BPMCALMGR:ALHBCHK.VAL NPP MS") field(ZRSV, "NO_ALARM") field(ONSV, "MAJOR") field(TWSV, "INVALID") field(ZRST, "RUNNING") field(ONST, "NOT_RUNNING") field(TWST, "INVALID") field(FLNK, "ALRM:SYS1:BPMCALMGR:ALHBPREV") } record(ai, "ALRM:SYS1:BPMCALMGR:ALHBPREV") { field(INP, "ALRM:SYS1:BPMCALMGR:ALHBCURR NPP NMS") } # checks an incrementor PV to see if it's incrementing. # the incrementors are updated by matlab processes. # Joe's matlab code # this will be 0 if old = current (i.e. not incrementing #function running = check_running(new_string, old_string) # running = abs(sign(str2double(new_string)-str2double(old_string))); #end # ======================================================= # A has current, B has previous record(calcout, "ALRM:SYS1:FACETCHRGFB:SCAN") { field(CALC, "A=B?0:A+1") field(SCAN, "1 second") field(INPA, "ALRM:SYS1:FACETCHRGFB:SCAN.VAL") field(INPB, "60") field(OUT, "ALRM:SYS1:FACETCHRGFB:ALHBCURR.VAL PP") field(DOPT, "Use CALC") field(OOPT, "Transition To Zero") } record(ai, "ALRM:SYS1:FACETCHRGFB:ALHBCURR") { field(INP, "PHYS:IN10:1:FACET_CHRGFB NPP MS") field(SCAN, "Passive") field(FLNK, "ALRM:SYS1:FACETCHRGFB:ALHBCHK") } record(calc, "ALRM:SYS1:FACETCHRGFB:ALHBCHK") { field(CALC, "C>2?2:(A=B?1:0)") field(INPA, "ALRM:SYS1:FACETCHRGFB:ALHBCURR NPP MS") field(INPB, "ALRM:SYS1:FACETCHRGFB:ALHBPREV.VAL NPP MS") field(INPC, "ALRM:SYS1:FACETCHRGFB:ALHBCURR.SEVR") field(FLNK, "ALRM:SYS1:FACETCHRGFB:ALHBERR") } # MS will cause this to be invalid if the HBCHK is record(mbbi, "ALRM:SYS1:FACETCHRGFB:ALHBERR") { field(DESC, "FACETCHRGFB monitoring") field(INP, "ALRM:SYS1:FACETCHRGFB:ALHBCHK.VAL NPP MS") field(ZRSV, "NO_ALARM") field(ONSV, "MAJOR") field(TWSV, "INVALID") field(ZRST, "RUNNING") field(ONST, "NOT_RUNNING") field(TWST, "INVALID") field(FLNK, "ALRM:SYS1:FACETCHRGFB:ALHBPREV") } record(ai, "ALRM:SYS1:FACETCHRGFB:ALHBPREV") { field(INP, "ALRM:SYS1:FACETCHRGFB:ALHBCURR NPP NMS") } # checks an incrementor PV to see if it's incrementing. # the incrementors are updated by matlab processes. # Joe's matlab code # this will be 0 if old = current (i.e. not incrementing #function running = check_running(new_string, old_string) # running = abs(sign(str2double(new_string)-str2double(old_string))); #end # ======================================================= # A has current, B has previous record(calcout, "ALRM:SYS1:CAMERA:SCAN") { field(CALC, "A=B?0:A+1") field(SCAN, "1 second") field(INPA, "ALRM:SYS1:CAMERA:SCAN.VAL") field(INPB, "30") field(OUT, "ALRM:SYS1:CAMERA:ALHBCURR.VAL PP") field(DOPT, "Use CALC") field(OOPT, "Transition To Zero") } record(ai, "ALRM:SYS1:CAMERA:ALHBCURR") { field(INP, "PHYS:SYS1:1:CAMERA NPP MS") field(SCAN, "Passive") field(FLNK, "ALRM:SYS1:CAMERA:ALHBCHK") } record(calc, "ALRM:SYS1:CAMERA:ALHBCHK") { field(CALC, "C>2?2:(A=B?1:0)") field(INPA, "ALRM:SYS1:CAMERA:ALHBCURR NPP MS") field(INPB, "ALRM:SYS1:CAMERA:ALHBPREV.VAL NPP MS") field(INPC, "ALRM:SYS1:CAMERA:ALHBCURR.SEVR") field(FLNK, "ALRM:SYS1:CAMERA:ALHBERR") } # MS will cause this to be invalid if the HBCHK is record(mbbi, "ALRM:SYS1:CAMERA:ALHBERR") { field(DESC, "CAMERA monitoring") field(INP, "ALRM:SYS1:CAMERA:ALHBCHK.VAL NPP MS") field(ZRSV, "NO_ALARM") field(ONSV, "MAJOR") field(TWSV, "INVALID") field(ZRST, "RUNNING") field(ONST, "NOT_RUNNING") field(TWST, "INVALID") field(FLNK, "ALRM:SYS1:CAMERA:ALHBPREV") } record(ai, "ALRM:SYS1:CAMERA:ALHBPREV") { field(INP, "ALRM:SYS1:CAMERA:ALHBCURR NPP NMS") } # checks an incrementor PV to see if it's incrementing. # the incrementors are updated by matlab processes. # Joe's matlab code # this will be 0 if old = current (i.e. not incrementing #function running = check_running(new_string, old_string) # running = abs(sign(str2double(new_string)-str2double(old_string))); #end # ======================================================= # A has current, B has previous record(calcout, "ALRM:SYS1:MPS_REC_FLT:SCAN") { field(CALC, "A=B?0:A+1") field(SCAN, "1 second") field(INPA, "ALRM:SYS1:MPS_REC_FLT:SCAN.VAL") field(INPB, "30") field(OUT, "ALRM:SYS1:MPS_REC_FLT:ALHBCURR.VAL PP") field(DOPT, "Use CALC") field(OOPT, "Transition To Zero") } record(ai, "ALRM:SYS1:MPS_REC_FLT:ALHBCURR") { field(INP, "PHYS:SYS1:1:MPS_REC_FLT_WATCH NPP MS") field(SCAN, "Passive") field(FLNK, "ALRM:SYS1:MPS_REC_FLT:ALHBCHK") } record(calc, "ALRM:SYS1:MPS_REC_FLT:ALHBCHK") { field(CALC, "C>2?2:(A=B?1:0)") field(INPA, "ALRM:SYS1:MPS_REC_FLT:ALHBCURR NPP MS") field(INPB, "ALRM:SYS1:MPS_REC_FLT:ALHBPREV.VAL NPP MS") field(INPC, "ALRM:SYS1:MPS_REC_FLT:ALHBCURR.SEVR") field(FLNK, "ALRM:SYS1:MPS_REC_FLT:ALHBERR") } # MS will cause this to be invalid if the HBCHK is record(mbbi, "ALRM:SYS1:MPS_REC_FLT:ALHBERR") { field(DESC, "MPS_REC_FLT monitoring") field(INP, "ALRM:SYS1:MPS_REC_FLT:ALHBCHK.VAL NPP MS") field(ZRSV, "NO_ALARM") field(ONSV, "MAJOR") field(TWSV, "INVALID") field(ZRST, "RUNNING") field(ONST, "NOT_RUNNING") field(TWST, "INVALID") field(FLNK, "ALRM:SYS1:MPS_REC_FLT:ALHBPREV") } record(ai, "ALRM:SYS1:MPS_REC_FLT:ALHBPREV") { field(INP, "ALRM:SYS1:MPS_REC_FLT:ALHBCURR NPP NMS") } # checks an incrementor PV to see if it's incrementing. # the incrementors are updated by matlab processes. # Joe's matlab code # this will be 0 if old = current (i.e. not incrementing #function running = check_running(new_string, old_string) # running = abs(sign(str2double(new_string)-str2double(old_string))); #end # ======================================================= # A has current, B has previous record(calcout, "ALRM:SYS1:MODEL_SERVER:SCAN") { field(CALC, "A=B?0:A+1") field(SCAN, "1 second") field(INPA, "ALRM:SYS1:MODEL_SERVER:SCAN.VAL") field(INPB, "30") field(OUT, "ALRM:SYS1:MODEL_SERVER:ALHBCURR.VAL PP") field(DOPT, "Use CALC") field(OOPT, "Transition To Zero") } record(ai, "ALRM:SYS1:MODEL_SERVER:ALHBCURR") { field(INP, "PHYS:SYS1:1:MODEL_SERVER NPP MS") field(SCAN, "Passive") field(FLNK, "ALRM:SYS1:MODEL_SERVER:ALHBCHK") } record(calc, "ALRM:SYS1:MODEL_SERVER:ALHBCHK") { field(CALC, "C>2?2:(A=B?1:0)") field(INPA, "ALRM:SYS1:MODEL_SERVER:ALHBCURR NPP MS") field(INPB, "ALRM:SYS1:MODEL_SERVER:ALHBPREV.VAL NPP MS") field(INPC, "ALRM:SYS1:MODEL_SERVER:ALHBCURR.SEVR") field(FLNK, "ALRM:SYS1:MODEL_SERVER:ALHBERR") } # MS will cause this to be invalid if the HBCHK is record(mbbi, "ALRM:SYS1:MODEL_SERVER:ALHBERR") { field(DESC, "MODEL_SERVER monitoring") field(INP, "ALRM:SYS1:MODEL_SERVER:ALHBCHK.VAL NPP MS") field(ZRSV, "NO_ALARM") field(ONSV, "MAJOR") field(TWSV, "INVALID") field(ZRST, "RUNNING") field(ONST, "NOT_RUNNING") field(TWST, "INVALID") field(FLNK, "ALRM:SYS1:MODEL_SERVER:ALHBPREV") } record(ai, "ALRM:SYS1:MODEL_SERVER:ALHBPREV") { field(INP, "ALRM:SYS1:MODEL_SERVER:ALHBCURR NPP NMS") } # Joe's matlab code # for m = 1:num_feedbacks # ... # incr_ok = check_running(pv_data{n+1}, pv_data_last{n+1}); % the CNTDISP PV # green_ok = strcmp('ON', pv_data{n}); % the STATE PV # if green_ok && (~incr_ok) % green, not incrementing # error_flag(n) = 1; # end # end # ====================================================== # check to see if feedback is incrementing (running) record(calcout, "FBCK:FMDL0:1:ALSCAN") { field(CALC, "A=B?0:A+1") field(SCAN, "1 second") field(INPA, "FBCK:FMDL0:1:ALSCAN.VAL") field(INPB, "600") field(OUT, "FBCK:FMDL0:1:ALHBCURR.VAL PP") field(DOPT, "Use CALC") field(OOPT, "Transition To Zero") } record(ai, "FBCK:FMDL0:1:ALHBCURR") { field(INP, "FBCK:FMDL0:1:CNTDISP NPP MS") field(SCAN, "Passive") field(FLNK, "FBCK:FMDL0:1:ALHBCHK") } record(calc, "FBCK:FMDL0:1:ALHBCHK") { field(CALC, "C>2?2:(A=B?1:0)") field(INPA, "FBCK:FMDL0:1:ALHBCURR.VAL NPP MS") field(INPB, "FBCK:FMDL0:1:ALHBPREV.VAL NPP MS") field(INPC, "FBCK:FMDL0:1:ALHBCURR.SEVR") field(FLNK, "FBCK:FMDL0:1:ALHBERR") } # never in alarm; this is simply the status, not # the final alarm PV. record(mbbi, "FBCK:FMDL0:1:ALHBERR") { field(DESC, "FBCK:FMDL0:1 monitoring") field(FLNK, "FBCK:FMDL0:1:ALFBERRCALC") field(INP, "FBCK:FMDL0:1:ALHBCHK.VAL NPP MS") field(ZRSV, "NO_ALARM") field(ONSV, "MAJOR") field(TWSV, "INVALID") field(ZRST, "RUNNING") field(ONST, "NOT_RUNNING") field(TWST, "INVALID") field(FLNK, "FBCK:FMDL0:1:ALHBPREV") } record(ai, "FBCK:FMDL0:1:ALHBPREV") { field(INP, "FBCK:FMDL0:1:ALHBCURR NPP MS") field(FLNK, "FBCK:FMDL0:1:ALFBERRCALC") } # then see if the status is OK, but it's not incrementing # (it thinks it's good, but it's not) # feedback is on and not incrementing is an error # if any input is invalid, then the status is invalid # ALHBERR has no value severity, so can propagate its severity # into the calc (to capture invalid) # STATE itself could be major or minor; simply want to capture an # invalid status here. record(calc, "FBCK:FMDL0:1:ALFBERRCALC") { field(CALC, "C>2||D>2?2:((A=1&&B=1)?1:0)") field(INPA, "FBCK:FMDL0:1:STATE NPP NMS") field(INPB, "FBCK:FMDL0:1:ALHBERR NPP NMS") field(INPC, "FBCK:FMDL0:1:STATE.SEVR") field(INPD, "FBCK:FMDL0:1:ALHBERR.SEVR") field(FLNK, "FBCK:FMDL0:1:ALFBERR") } record(mbbi, "FBCK:FMDL0:1:ALFBERR") { field(DESC, "FBCK:FMDL0:1 monitoring") field(INP, "FBCK:FMDL0:1:ALFBERRCALC.VAL NPP MS") field(ZRST, "OK") field(ONST, "ON_NOT_RUNNING") field(TWST, "INVALID") field(ZRSV, "NO_ALARM") field(ONSV, "MAJOR") field(TWSV, "INVALID") } #record(bi, "FBCK:FMDL0:1:ALFBERR") { # field(DESC, "FBCK:FMDL0:1 monitoring") # field(INP, "FBCK:FMDL0:1:ALFBERRCALC.VAL NPP MS") # field(ZSV, "NO_ALARM") # field(OSV, "MAJOR") # field(ZNAM, "OK") # field(ONAM, "ON_NOT_RUNNING") #} #! Generated by VisualDCT v2.7.0 #! DBDSTART #! DBDEND record(bo, F2:WATCHER:FACETSUPPORT_STAT) { field(DESC, "Running Status for Facet Support IOC") field(SCAN, "Passive") field(PINI, "YES") field(DTYP, "Soft Channel") field(VAL, "0") field(OMSL, "supervisory") field(HIGH, "3") field(ZNAM, "OFF") field(ONAM, "RUNNING") field(ZSV, "MAJOR") } record(bo, F2:WATCHER:KEEPALIVE) { field(OUT, "F2:WATCHER:FACETSUPPORT_STAT PP") field(VAL, "1") field(PINI, "YES") field(FLNK, "F2:WATCHER:FACETSUPPORT_STAT") field(SCAN, "1 second") } record(bo, F2:WATCHER:WAISTLOCATOR_STAT) { field(DESC, "Waist Locater Running Status") field(SCAN, "Passive") field(PINI, "YES") field(DTYP, "Soft Channel") field(VAL, "0") field(OMSL, "supervisory") field(HIGH, "3") field(ZNAM, "OFF") field(ONAM, "RUNNING") field(ZSV, "MAJOR") field(COSV, "NO_ALARM") } record(bo, F2:WATCHER:GUNWATCHER_STAT) { field(DESC, "Gun Watcher Running Status") field(SCAN, "Passive") field(PINI, "YES") field(DTYP, "Soft Channel") field(VAL, "0") field(OMSL, "supervisory") field(HIGH, "3") field(ZNAM, "OFF") field(ONAM, "RUNNING") field(ZSV, "MAJOR") } record(bo, F2:WATCHER:CATHODESUPPORT_STAT) { field(DESC, "Cathode Support Running Status") field(SCAN, "Passive") field(PINI, "YES") field(DTYP, "Soft Channel") field(VAL, "0") field(OMSL, "supervisory") field(HIGH, "3") field(ZNAM, "OFF") field(ONAM, "RUNNING") field(ZSV, "MAJOR") } record(bo, F2:WATCHER:FEEDBACKS_STAT) { field(DESC, "Gun Watcher Running Status") field(SCAN, "Passive") field(PINI, "YES") field(DTYP, "Soft Channel") field(VAL, "0") field(OMSL, "supervisory") field(HIGH, "3") field(ZNAM, "OFF") field(ONAM, "RUNNING") field(ZSV, "MAJOR") } record(bo, F2:WATCHER:BPMREPEATER_STAT) { field(DESC, "BPM Repeater Status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "Soft Channel") field(VAL, "0") field(OMSL, "closed_loop") field(ZNAM, "RUNNING") field(ONAM, "OFF") field(DOL, "ALRM:SYS1:BPMRPTR:ALHBCHK CA MS") field(OSV, "MAJOR") } record(bo, F2:WATCHER:TCAVFEEDBACK_STAT) { field(DESC, "TCAV Feedback Status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "Soft Channel") field(VAL, "0") field(OMSL, "closed_loop") field(ZNAM, "RUNNING") field(ONAM, "OFF") field(DOL, "ALRM:SYS1:LI20FBCK:ALHBCHK CA MS") field(OSV, "MAJOR") } record(bo, F2:WATCHER:VITARA_STAT) { field(DESC, "FACET Vitara Status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "Soft Channel") field(VAL, "0") field(OMSL, "closed_loop") field(ZNAM, "RUNNING") field(ONAM, "OFF") field(DOL, "ALRM:SYS1:FACET:ALHBCHK CA MS") field(OSV, "MAJOR") } record(bo, F2:WATCHER:KLYSCUD_STAT) { field(DESC, "Klystron CUD Status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "Soft Channel") field(VAL, "0") field(OMSL, "closed_loop") field(ZNAM, "RUNNING") field(ONAM, "OFF") field(DOL, "ALRM:SYS1:KLYSCUD:ALHBCHK CA MS") field(OSV, "MAJOR") } record(calc, F2:WATCHER:WATCHER_STAT) { field(SCAN, "1 second") field(INPA, "F2:WATCHER:FACETSUPPORT_STAT NPP MS") field(INPB, "F2:WATCHER:WAISTLOCATOR_STAT NPP MS") field(INPC, "F2:WATCHER:GUNWATCHER_STAT NPP MS") field(INPD, "F2:WATCHER:CATHODESUPPORT_STAT NPP MS") field(INPE, "F2:WATCHER:FEEDBACKS_STAT NPP MS") field(INPF, "F2:WATCHER:DIFFPUMP_STAT NPP MS") field(INPL, "F2:WATCHER:WATCHER_STAT1 PP MS") field(INPG, "F2:WATCHER:S10LASERARCHIVER_STAT NPP MS") field(INPH, "F2:WATCHER:S20LASERARCHIVER_STAT NPP MS") field(INPI, "F2:WATCHER:FASTLASERARCHIVER_STAT NPP MS") field(INPJ, "F2:WATCHER:MDLFF_STAT NPP MS") field(INPK, "F2:WATCHER:ORBIT_STAT NPP MS") } record(bo, F2:WATCHER:DEFENDER_STAT) { field(DESC, "Defender Status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "Soft Channel") field(VAL, "0") field(OMSL, "closed_loop") field(ZNAM, "RUNNING") field(ONAM, "OFF") field(DOL, "ALRM:SYS1:DEFENDER:ALHBCHK CA MS") field(OSV, "MAJOR") } record(calc, F2:WATCHER:WATCHER_STAT1) { field(SCAN, "Passive") field(INPA, "F2:WATCHER:BPMREPEATER_STAT NPP MS") field(INPB, "F2:WATCHER:TCAVFEEDBACK_STAT NPP MS") field(INPC, "F2:WATCHER:CHARGEFEEDBACK_STAT.VAL NPP MS") field(INPD, "F2:WATCHER:VITARA_STAT NPP MS") field(INPE, "F2:WATCHER:KLYSCUD_STAT NPP MS") field(INPF, "F2:WATCHER:DEFENDER_STAT NPP MS") field(INPJ, "F2:WATCHER:LASERSTEERING_STAT NPP MS") field(INPG, "F2:WATCHER:CAMERA_STAT NPP MS") field(INPH, "F2:WATCHER:MODEL_SERVER_STAT NPP MS") } record(bo, F2:WATCHER:LASERSTEERING_STAT) { field(DESC, "Laser Steering Status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "Soft Channel") field(VAL, "0") field(OMSL, "closed_loop") field(ZNAM, "RUNNING") field(ONAM, "OFF") field(DOL, "ALRM:SYS1:STEERING:ALHBCHK CA MS") field(OSV, "MAJOR") } record(bo, F2:WATCHER:DIFFPUMP_STAT) { field(DESC, "Differential Pumping Status") field(SCAN, "Passive") field(PINI, "YES") field(DTYP, "Soft Channel") field(VAL, "0") field(OMSL, "supervisory") field(HIGH, "3") field(ZNAM, "OFF") field(ONAM, "RUNNING") field(ZSV, "MAJOR") } record(bo, F2:WATCHER:S10LASERARCHIVER_STAT) { field(DESC, "S10 Laser Archiver Status") field(SCAN, "Passive") field(PINI, "YES") field(DTYP, "Soft Channel") field(VAL, "0") field(OMSL, "supervisory") field(HIGH, "3") field(ZNAM, "OFF") field(ONAM, "RUNNING") field(ZSV, "MAJOR") } record(bo, F2:WATCHER:S20LASERARCHIVER_STAT) { field(DESC, "S20 Laser Archiver Status") field(SCAN, "Passive") field(PINI, "YES") field(DTYP, "Soft Channel") field(VAL, "0") field(OMSL, "supervisory") field(HIGH, "3") field(ZNAM, "OFF") field(ONAM, "RUNNING") field(ZSV, "MAJOR") } record(bo, F2:WATCHER:FASTLASERARCHIVER_STAT) { field(DESC, "S20 Laser Archiver Status") field(SCAN, "Passive") field(PINI, "YES") field(DTYP, "Soft Channel") field(VAL, "0") field(OMSL, "supervisory") field(HIGH, "3") field(ZNAM, "OFF") field(ONAM, "RUNNING") field(ZSV, "MAJOR") } record(bo, F2:WATCHER:CHARGEFEEDBACK_STAT) { field(DESC, "OP Repeater Status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "Soft Channel") field(VAL, "0") field(OMSL, "closed_loop") field(ZNAM, "RUNNING") field(ONAM, "OFF") field(DOL, "ALRM:SYS1:FACETCHRGFB:ALHBCHK CA MS") field(OSV, "MAJOR") } record(bo, F2:WATCHER:MDLFF_STAT) { field(DESC, "MDL Feedforward Status") field(SCAN, "Passive") field(PINI, "YES") field(DTYP, "Soft Channel") field(VAL, "0") field(OMSL, "supervisory") field(HIGH, "3") field(ZNAM, "OFF") field(ONAM, "RUNNING") field(ZSV, "MAJOR") } record(bo, F2:WATCHER:ORBIT_STAT) { field(DESC, "Orbit Watcher Status") field(SCAN, "Passive") field(PINI, "YES") field(DTYP, "Soft Channel") field(VAL, "0") field(OMSL, "supervisory") field(HIGH, "3") field(ZNAM, "OFF") field(ONAM, "RUNNING") field(ZSV, "MAJOR") } record(bo, F2:MATLABSERVER:STAT1:OPI20) { field(VAL, "0") field(HIGH, "90") field(PINI, "YES") field(OMSL, "supervisory") field(ZNAM, "OFF") field(ONAM, "RUNNING") field(ZSV, "MAJOR") } record(bo, F2:MATLABSERVER:STAT1:OPI21) { field(VAL, "0") field(HIGH, "90") field(PINI, "YES") field(OMSL, "supervisory") field(ZNAM, "OFF") field(ONAM, "RUNNING") field(ZSV, "MAJOR") } record(bo, F2:MATLABSERVER:STAT1:OPI22) { field(VAL, "0") field(HIGH, "90") field(PINI, "YES") field(OMSL, "supervisory") field(ZNAM, "OFF") field(ONAM, "RUNNING") field(ZSV, "MAJOR") } record(bo, F2:MATLABSERVER:STAT1:OPI23) { field(VAL, "0") field(HIGH, "90") field(PINI, "YES") field(OMSL, "supervisory") field(ZNAM, "OFF") field(ONAM, "RUNNING") field(ZSV, "MAJOR") } record(bo, F2:MATLABSERVER:STAT2:OPI20) { field(VAL, "0") field(HIGH, "90") field(PINI, "YES") field(OMSL, "supervisory") field(ZNAM, "OFF") field(ONAM, "RUNNING") field(ZSV, "MAJOR") } record(bo, F2:MATLABSERVER:STAT2:OPI21) { field(VAL, "0") field(HIGH, "90") field(PINI, "YES") field(OMSL, "supervisory") field(ZNAM, "OFF") field(ONAM, "RUNNING") field(ZSV, "MAJOR") } record(bo, F2:MATLABSERVER:STAT2:OPI22) { field(VAL, "0") field(HIGH, "90") field(PINI, "YES") field(OMSL, "supervisory") field(ZNAM, "OFF") field(ONAM, "RUNNING") field(ZSV, "MAJOR") } record(bo, F2:MATLABSERVER:STAT2:OPI23) { field(VAL, "0") field(HIGH, "90") field(PINI, "YES") field(OMSL, "supervisory") field(ZNAM, "OFF") field(ONAM, "RUNNING") field(ZSV, "MAJOR") } record(bo, F2:MATLABSERVER:STAT3:OPI20) { field(VAL, "0") field(HIGH, "90") field(PINI, "YES") field(OMSL, "supervisory") field(ZNAM, "OFF") field(ONAM, "RUNNING") field(ZSV, "MAJOR") } record(bo, F2:MATLABSERVER:STAT3:OPI21) { field(VAL, "0") field(HIGH, "90") field(PINI, "YES") field(OMSL, "supervisory") field(ZNAM, "OFF") field(ONAM, "RUNNING") field(ZSV, "MAJOR") } record(bo, F2:MATLABSERVER:STAT3:OPI22) { field(VAL, "0") field(HIGH, "90") field(PINI, "YES") field(OMSL, "supervisory") field(ZNAM, "OFF") field(ONAM, "RUNNING") field(ZSV, "MAJOR") } record(bo, F2:MATLABSERVER:STAT3:OPI23) { field(VAL, "0") field(HIGH, "90") field(PINI, "YES") field(OMSL, "supervisory") field(ZNAM, "OFF") field(ONAM, "RUNNING") field(ZSV, "MAJOR") } record(bo, F2:WATCHER:CAMERA_STAT) { field(DESC, "Klystron CUD Status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "Soft Channel") field(VAL, "0") field(OMSL, "closed_loop") field(ZNAM, "RUNNING") field(ONAM, "OFF") field(DOL, "ALRM:SYS1:CAMERA:ALHBCHK CA MS") field(OSV, "MAJOR") } record(bo, F2:WATCHER:MODEL_SERVER_STAT) { field(DESC, "Model Server Status") field(SCAN, "1 second") field(PINI, "YES") field(DTYP, "Soft Channel") field(VAL, "0") field(OMSL, "closed_loop") field(ZNAM, "RUNNING") field(ONAM, "OFF") field(DOL, "ALRM:SYS1:MODEL_SERVER:ALHBCHK CA MS") field(OSV, "MAJOR") } #! Further lines contain data used by VisualDCT #! View(0,1023,1.7) #! Record(F2:WATCHER:FACETSUPPORT_STAT,20,22,0,1,"F2:WATCHER:FACETSUPPORT_STAT") #! Field("F2:WATCHER:FACETSUPPORT_STAT.VAL",16777215,1,"F2:WATCHER:FACETSUPPORT_STAT.VAL") #! Record(F2:WATCHER:KEEPALIVE,500,13,0,0,"F2:WATCHER:KEEPALIVE") #! Field("F2:WATCHER:KEEPALIVE.OUT",16777215,0,"F2:WATCHER:KEEPALIVE.OUT") #! Link("F2:WATCHER:KEEPALIVE.OUT","F2:WATCHER:FACETSUPPORT_STAT.VAL") #! Field("F2:WATCHER:KEEPALIVE.FLNK",16777215,0,"F2:WATCHER:KEEPALIVE.FLNK") #! Link("F2:WATCHER:KEEPALIVE.FLNK",F2:WATCHER:FACETSUPPORT_STAT) #! Record(F2:WATCHER:WAISTLOCATOR_STAT,720,8,0,0,"F2:WATCHER:WAISTLOCATOR_STAT") #! Field("F2:WATCHER:WAISTLOCATOR_STAT.VAL",16777215,0,"F2:WATCHER:WAISTLOCATOR_STAT.VAL") #! Record(F2:WATCHER:GUNWATCHER_STAT,940,22,0,0,"F2:WATCHER:GUNWATCHER_STAT") #! Field("F2:WATCHER:GUNWATCHER_STAT.VAL",16777215,0,"F2:WATCHER:GUNWATCHER_STAT.VAL") #! Record(F2:WATCHER:CATHODESUPPORT_STAT,1160,22,0,0,"F2:WATCHER:CATHODESUPPORT_STAT") #! Field("F2:WATCHER:CATHODESUPPORT_STAT.VAL",16777215,0,"F2:WATCHER:CATHODESUPPORT_STAT.VAL") #! Record(F2:WATCHER:FEEDBACKS_STAT,1380,22,0,0,"F2:WATCHER:FEEDBACKS_STAT") #! Field("F2:WATCHER:FEEDBACKS_STAT.VAL",16777215,0,"F2:WATCHER:FEEDBACKS_STAT.VAL") #! Record(F2:WATCHER:BPMREPEATER_STAT,420,902,0,1,"F2:WATCHER:BPMREPEATER_STAT") #! Field("F2:WATCHER:BPMREPEATER_STAT.DOL",16777215,1,"F2:WATCHER:BPMREPEATER_STAT.DOL") #! Field("F2:WATCHER:BPMREPEATER_STAT.VAL",16777215,0,"F2:WATCHER:BPMREPEATER_STAT.VAL") #! Record(F2:WATCHER:TCAVFEEDBACK_STAT,640,902,0,1,"F2:WATCHER:TCAVFEEDBACK_STAT") #! Field("F2:WATCHER:TCAVFEEDBACK_STAT.DOL",16777215,1,"F2:WATCHER:TCAVFEEDBACK_STAT.DOL") #! Field("F2:WATCHER:TCAVFEEDBACK_STAT.VAL",16777215,0,"F2:WATCHER:TCAVFEEDBACK_STAT.VAL") #! Record(F2:WATCHER:VITARA_STAT,1080,902,0,1,"F2:WATCHER:VITARA_STAT") #! Field("F2:WATCHER:VITARA_STAT.DOL",16777215,1,"F2:WATCHER:VITARA_STAT.DOL") #! Field("F2:WATCHER:VITARA_STAT.VAL",16777215,0,"F2:WATCHER:VITARA_STAT.VAL") #! Record(F2:WATCHER:KLYSCUD_STAT,1300,902,0,1,"F2:WATCHER:KLYSCUD_STAT") #! Field("F2:WATCHER:KLYSCUD_STAT.DOL",16777215,1,"F2:WATCHER:KLYSCUD_STAT.DOL") #! Field("F2:WATCHER:KLYSCUD_STAT.VAL",16777215,0,"F2:WATCHER:KLYSCUD_STAT.VAL") #! Record(F2:WATCHER:WATCHER_STAT,440,200,0,1,"F2:WATCHER:WATCHER_STAT") #! Field("F2:WATCHER:WATCHER_STAT.INPA",16777215,0,"F2:WATCHER:WATCHER_STAT.INPA") #! Link("F2:WATCHER:WATCHER_STAT.INPA","F2:WATCHER:FACETSUPPORT_STAT.VAL") #! Field("F2:WATCHER:WATCHER_STAT.INPB",16777215,1,"F2:WATCHER:WATCHER_STAT.INPB") #! Link("F2:WATCHER:WATCHER_STAT.INPB","F2:WATCHER:WAISTLOCATOR_STAT.VAL") #! Field("F2:WATCHER:WATCHER_STAT.INPC",16777215,1,"F2:WATCHER:WATCHER_STAT.INPC") #! Link("F2:WATCHER:WATCHER_STAT.INPC","F2:WATCHER:GUNWATCHER_STAT.VAL") #! Field("F2:WATCHER:WATCHER_STAT.INPD",16777215,1,"F2:WATCHER:WATCHER_STAT.INPD") #! Link("F2:WATCHER:WATCHER_STAT.INPD","F2:WATCHER:CATHODESUPPORT_STAT.VAL") #! Field("F2:WATCHER:WATCHER_STAT.INPE",16777215,1,"F2:WATCHER:WATCHER_STAT.INPE") #! Link("F2:WATCHER:WATCHER_STAT.INPE","F2:WATCHER:FEEDBACKS_STAT.VAL") #! Field("F2:WATCHER:WATCHER_STAT.INPF",16777215,1,"F2:WATCHER:WATCHER_STAT.INPF") #! Link("F2:WATCHER:WATCHER_STAT.INPF","F2:WATCHER:DIFFPUMP_STAT.VAL") #! Field("F2:WATCHER:WATCHER_STAT.INPL",16777215,0,"F2:WATCHER:WATCHER_STAT.INPL") #! Link("F2:WATCHER:WATCHER_STAT.INPL","F2:WATCHER:WATCHER_STAT1.VAL") #! Field("F2:WATCHER:WATCHER_STAT.INPG",16777215,1,"F2:WATCHER:WATCHER_STAT.INPG") #! Link("F2:WATCHER:WATCHER_STAT.INPG","F2:WATCHER:S10LASERARCHIVER_STAT.VAL") #! Field("F2:WATCHER:WATCHER_STAT.INPH",16777215,1,"F2:WATCHER:WATCHER_STAT.INPH") #! Link("F2:WATCHER:WATCHER_STAT.INPH","F2:WATCHER:S20LASERARCHIVER_STAT.VAL") #! Field("F2:WATCHER:WATCHER_STAT.INPI",16777215,1,"F2:WATCHER:WATCHER_STAT.INPI") #! Link("F2:WATCHER:WATCHER_STAT.INPI","F2:WATCHER:FASTLASERARCHIVER_STAT.VAL") #! Field("F2:WATCHER:WATCHER_STAT.INPJ",16777215,1,"F2:WATCHER:WATCHER_STAT.INPJ") #! Link("F2:WATCHER:WATCHER_STAT.INPJ","F2:WATCHER:MDLFF_STAT.VAL") #! Field("F2:WATCHER:WATCHER_STAT.INPK",16777215,1,"F2:WATCHER:WATCHER_STAT.INPK") #! Link("F2:WATCHER:WATCHER_STAT.INPK","F2:WATCHER:ORBIT_STAT.VAL") #! Record(F2:WATCHER:DEFENDER_STAT,1520,902,0,1,"F2:WATCHER:DEFENDER_STAT") #! Field("F2:WATCHER:DEFENDER_STAT.DOL",16777215,1,"F2:WATCHER:DEFENDER_STAT.DOL") #! Field("F2:WATCHER:DEFENDER_STAT.VAL",16777215,0,"F2:WATCHER:DEFENDER_STAT.VAL") #! Record(F2:WATCHER:WATCHER_STAT1,140,496,0,1,"F2:WATCHER:WATCHER_STAT1") #! Field("F2:WATCHER:WATCHER_STAT1.VAL",16777215,1,"F2:WATCHER:WATCHER_STAT1.VAL") #! Field("F2:WATCHER:WATCHER_STAT1.INPA",16777215,1,"F2:WATCHER:WATCHER_STAT1.INPA") #! Link("F2:WATCHER:WATCHER_STAT1.INPA","F2:WATCHER:BPMREPEATER_STAT.VAL") #! Field("F2:WATCHER:WATCHER_STAT1.INPB",16777215,1,"F2:WATCHER:WATCHER_STAT1.INPB") #! Link("F2:WATCHER:WATCHER_STAT1.INPB","F2:WATCHER:TCAVFEEDBACK_STAT.VAL") #! Field("F2:WATCHER:WATCHER_STAT1.INPC",16777215,1,"F2:WATCHER:WATCHER_STAT1.INPC") #! Link("F2:WATCHER:WATCHER_STAT1.INPC","F2:WATCHER:CHARGEFEEDBACK_STAT.VAL") #! Field("F2:WATCHER:WATCHER_STAT1.INPD",16777215,1,"F2:WATCHER:WATCHER_STAT1.INPD") #! Link("F2:WATCHER:WATCHER_STAT1.INPD","F2:WATCHER:VITARA_STAT.VAL") #! Field("F2:WATCHER:WATCHER_STAT1.INPE",16777215,1,"F2:WATCHER:WATCHER_STAT1.INPE") #! Link("F2:WATCHER:WATCHER_STAT1.INPE","F2:WATCHER:KLYSCUD_STAT.VAL") #! Field("F2:WATCHER:WATCHER_STAT1.INPF",16777215,1,"F2:WATCHER:WATCHER_STAT1.INPF") #! Link("F2:WATCHER:WATCHER_STAT1.INPF","F2:WATCHER:DEFENDER_STAT.VAL") #! Field("F2:WATCHER:WATCHER_STAT1.INPJ",16777215,1,"F2:WATCHER:WATCHER_STAT1.INPJ") #! Link("F2:WATCHER:WATCHER_STAT1.INPJ","F2:WATCHER:LASERSTEERING_STAT.VAL") #! Field("F2:WATCHER:WATCHER_STAT1.INPG",16777215,1,"F2:WATCHER:WATCHER_STAT1.INPG") #! Link("F2:WATCHER:WATCHER_STAT1.INPG","F2:WATCHER:CAMERA_STAT.VAL") #! Record(F2:WATCHER:LASERSTEERING_STAT,1740,902,0,1,"F2:WATCHER:LASERSTEERING_STAT") #! Field("F2:WATCHER:LASERSTEERING_STAT.DOL",16777215,1,"F2:WATCHER:LASERSTEERING_STAT.DOL") #! Field("F2:WATCHER:LASERSTEERING_STAT.VAL",16777215,0,"F2:WATCHER:LASERSTEERING_STAT.VAL") #! Record(F2:WATCHER:DIFFPUMP_STAT,1600,22,0,1,"F2:WATCHER:DIFFPUMP_STAT") #! Field("F2:WATCHER:DIFFPUMP_STAT.VAL",16777215,0,"F2:WATCHER:DIFFPUMP_STAT.VAL") #! Record(F2:WATCHER:S10LASERARCHIVER_STAT,1820,22,0,1,"F2:WATCHER:S10LASERARCHIVER_STAT") #! Field("F2:WATCHER:S10LASERARCHIVER_STAT.VAL",16777215,0,"F2:WATCHER:S10LASERARCHIVER_STAT.VAL") #! Record(F2:WATCHER:S20LASERARCHIVER_STAT,2040,22,0,1,"F2:WATCHER:S20LASERARCHIVER_STAT") #! Field("F2:WATCHER:S20LASERARCHIVER_STAT.VAL",16777215,0,"F2:WATCHER:S20LASERARCHIVER_STAT.VAL") #! Record(F2:WATCHER:FASTLASERARCHIVER_STAT,2080,262,0,1,"F2:WATCHER:FASTLASERARCHIVER_STAT") #! Field("F2:WATCHER:FASTLASERARCHIVER_STAT.VAL",16777215,0,"F2:WATCHER:FASTLASERARCHIVER_STAT.VAL") #! Record(F2:WATCHER:CHARGEFEEDBACK_STAT,860,902,0,1,"F2:WATCHER:CHARGEFEEDBACK_STAT") #! Field("F2:WATCHER:CHARGEFEEDBACK_STAT.DOL",16777215,1,"F2:WATCHER:CHARGEFEEDBACK_STAT.DOL") #! Field("F2:WATCHER:CHARGEFEEDBACK_STAT.VAL",16777215,0,"F2:WATCHER:CHARGEFEEDBACK_STAT.VAL") #! Record(F2:WATCHER:MDLFF_STAT,2120,522,0,1,"F2:WATCHER:MDLFF_STAT") #! Field("F2:WATCHER:MDLFF_STAT.VAL",16777215,0,"F2:WATCHER:MDLFF_STAT.VAL") #! Record(F2:WATCHER:ORBIT_STAT,2100,802,0,1,"F2:WATCHER:ORBIT_STAT") #! Field("F2:WATCHER:ORBIT_STAT.VAL",16777215,0,"F2:WATCHER:ORBIT_STAT.VAL") #! Record(F2:MATLABSERVER:STAT1:OPI20,80,1185,0,1,"F2:MATLABSERVER:STAT1:OPI20") #! Record(F2:MATLABSERVER:STAT1:OPI21,260,1185,0,1,"F2:MATLABSERVER:STAT1:OPI21") #! Record(F2:MATLABSERVER:STAT1:OPI22,440,1185,0,1,"F2:MATLABSERVER:STAT1:OPI22") #! Record(F2:MATLABSERVER:STAT1:OPI23,620,1185,0,1,"F2:MATLABSERVER:STAT1:OPI23") #! Record(F2:MATLABSERVER:STAT2:OPI20,80,1285,0,1,"F2:MATLABSERVER:STAT2:OPI20") #! Record(F2:MATLABSERVER:STAT2:OPI21,260,1285,0,1,"F2:MATLABSERVER:STAT2:OPI21") #! Record(F2:MATLABSERVER:STAT2:OPI22,440,1285,0,1,"F2:MATLABSERVER:STAT2:OPI22") #! Record(F2:MATLABSERVER:STAT2:OPI23,620,1285,0,1,"F2:MATLABSERVER:STAT2:OPI23") #! Record(F2:MATLABSERVER:STAT3:OPI20,80,1385,0,1,"F2:MATLABSERVER:STAT3:OPI20") #! Record(F2:MATLABSERVER:STAT3:OPI21,260,1385,0,1,"F2:MATLABSERVER:STAT3:OPI21") #! Record(F2:MATLABSERVER:STAT3:OPI22,440,1385,0,1,"F2:MATLABSERVER:STAT3:OPI22") #! Record(F2:MATLABSERVER:STAT3:OPI23,620,1385,0,1,"F2:MATLABSERVER:STAT3:OPI23") #! Record(F2:WATCHER:CAMERA_STAT,180,922,0,1,"F2:WATCHER:CAMERA_STAT") #! Field("F2:WATCHER:CAMERA_STAT.DOL",16777215,1,"F2:WATCHER:CAMERA_STAT.DOL") #! Field("F2:WATCHER:CAMERA_STAT.VAL",16777215,1,"F2:WATCHER:CAMERA_STAT.VAL")