# Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:RFFB") { field(DESC, "RFFB Monitor") field(PINI, "YES") field(VAL, "Slow RF Freq") } # Status message set by the monitoring application. record(stringout, "SPEARMON:RFFBStatusMsg") { field(DESC, "RFFB Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:RFFBCount") { field(DESC, "RFFB Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:RFFBCountDelay") { field(DESC, "RFFB Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:RFFBLatchDelay") { field(DESC, "RFFB Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:RFFBAck") { field(DESC, "RFFB Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:RFFBAckType") { field(DESC, "RFFB Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:RFFBModeFilter") { field(DESC, "RFFB Monitor Mode Filter") field(PINI, "YES") field(DOL, "3") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:RFFBAudio") { field(DESC, "RFFB Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:RFFBAudioState") { field(DESC, "RFFB Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:RFFBAudioRepeat") { field(DESC, "RFFB Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:RFFBAudioDelay") { field(DESC, "RFFB Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:RFFBDisable") { field(DESC, "RFFB Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:SOFB") { field(DESC, "SOFB Monitor") field(PINI, "YES") field(VAL, "Slow Orbit Fdbk") } # Status message set by the monitoring application. record(stringout, "SPEARMON:SOFBStatusMsg") { field(DESC, "SOFB Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:SOFBCount") { field(DESC, "SOFB Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:SOFBCountDelay") { field(DESC, "SOFB Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:SOFBLatchDelay") { field(DESC, "SOFB Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:SOFBAck") { field(DESC, "SOFB Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:SOFBAckType") { field(DESC, "SOFB Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:SOFBModeFilter") { field(DESC, "SOFB Monitor Mode Filter") field(PINI, "YES") field(DOL, "3") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:SOFBAudio") { field(DESC, "SOFB Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:SOFBAudioState") { field(DESC, "SOFB Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:SOFBAudioRepeat") { field(DESC, "SOFB Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:SOFBAudioDelay") { field(DESC, "SOFB Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:SOFBDisable") { field(DESC, "SOFB Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:FDBK") { field(DESC, "FDBK Monitor") field(PINI, "YES") field(VAL, "Orbit/RF Freq") } # Status message set by the monitoring application. record(stringout, "SPEARMON:FDBKStatusMsg") { field(DESC, "FDBK Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:FDBKCount") { field(DESC, "FDBK Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:FDBKCountDelay") { field(DESC, "FDBK Monitor Count Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:FDBKLatchDelay") { field(DESC, "FDBK Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:FDBKAck") { field(DESC, "FDBK Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:FDBKAckType") { field(DESC, "FDBK Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:FDBKModeFilter") { field(DESC, "FDBK Monitor Mode Filter") field(PINI, "YES") field(DOL, "3") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:FDBKAudio") { field(DESC, "FDBK Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:FDBKAudioState") { field(DESC, "FDBK Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:FDBKAudioRepeat") { field(DESC, "FDBK Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:FDBKAudioDelay") { field(DESC, "FDBK Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:FDBKDisable") { field(DESC, "FDBK Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:BLDS") { field(DESC, "BLDS Monitor") field(PINI, "YES") field(VAL, "BL Dyn Steering") } # Status message set by the monitoring application. record(stringout, "SPEARMON:BLDSStatusMsg") { field(DESC, "BLDS Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:BLDSCount") { field(DESC, "BLDS Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:BLDSCountDelay") { field(DESC, "BLDS Monitor Count Delay") field(PINI, "YES") field(DOL, "15") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:BLDSLatchDelay") { field(DESC, "BLDS Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:BLDSAck") { field(DESC, "BLDS Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:BLDSAckType") { field(DESC, "BLDS Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:BLDSModeFilter") { field(DESC, "BLDS Monitor Mode Filter") field(PINI, "YES") field(DOL, "3") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:BLDSAudio") { field(DESC, "BLDS Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:BLDSAudioState") { field(DESC, "BLDS Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:BLDSAudioRepeat") { field(DESC, "BLDS Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:BLDSAudioDelay") { field(DESC, "BLDS Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:BLDSDisable") { field(DESC, "BLDS Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:BL02PH1") { field(DESC, "BL02PH1 Monitor") field(PINI, "YES") field(VAL, "BL02 Pinhole Cam") } # Status message set by the monitoring application. record(stringout, "SPEARMON:BL02PH1StatusMsg") { field(DESC, "BL02PH1 Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:BL02PH1Count") { field(DESC, "BL02PH1 Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:BL02PH1CountDelay") { field(DESC, "BL02PH1 Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:BL02PH1LatchDelay") { field(DESC, "BL02PH1 Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:BL02PH1Ack") { field(DESC, "BL02PH1 Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:BL02PH1AckType") { field(DESC, "BL02PH1 Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:BL02PH1ModeFilter") { field(DESC, "BL02PH1 Monitor Mode Filter") field(PINI, "YES") field(DOL, "3") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:BL02PH1Audio") { field(DESC, "BL02PH1 Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:BL02PH1AudioState") { field(DESC, "BL02PH1 Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:BL02PH1AudioRepeat") { field(DESC, "BL02PH1 Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:BL02PH1AudioDelay") { field(DESC, "BL02PH1 Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:BL02PH1Disable") { field(DESC, "BL02PH1 Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:BPMRMS") { field(DESC, "BPMRMS Monitor") field(PINI, "YES") field(VAL, "BPM RMS") } # Status message set by the monitoring application. record(stringout, "SPEARMON:BPMRMSStatusMsg") { field(DESC, "BPMRMS Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:BPMRMSCount") { field(DESC, "BPMRMS Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:BPMRMSCountDelay") { field(DESC, "BPMRMS Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:BPMRMSLatchDelay") { field(DESC, "BPMRMS Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:BPMRMSAck") { field(DESC, "BPMRMS Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:BPMRMSAckType") { field(DESC, "BPMRMS Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:BPMRMSModeFilter") { field(DESC, "BPMRMS Monitor Mode Filter") field(PINI, "YES") field(DOL, "3") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:BPMRMSAudio") { field(DESC, "BPMRMS Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:BPMRMSAudioState") { field(DESC, "BPMRMS Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:BPMRMSAudioRepeat") { field(DESC, "BPMRMS Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:BPMRMSAudioDelay") { field(DESC, "BPMRMS Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:BPMRMSDisable") { field(DESC, "BPMRMS Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:RF1") { field(DESC, "RF1 Monitor") field(PINI, "YES") field(VAL, "RF1") } # Status message set by the monitoring application. record(stringout, "SPEARMON:RF1StatusMsg") { field(DESC, "RF1 Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:RF1Count") { field(DESC, "RF1 Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:RF1CountDelay") { field(DESC, "RF1 Monitor Count Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:RF1LatchDelay") { field(DESC, "RF1 Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:RF1Ack") { field(DESC, "RF1 Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:RF1AckType") { field(DESC, "RF1 Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:RF1ModeFilter") { field(DESC, "RF1 Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:RF1Audio") { field(DESC, "RF1 Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:RF1AudioState") { field(DESC, "RF1 Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:RF1AudioRepeat") { field(DESC, "RF1 Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:RF1AudioDelay") { field(DESC, "RF1 Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:RF1Disable") { field(DESC, "RF1 Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:RF2") { field(DESC, "RF2 Monitor") field(PINI, "YES") field(VAL, "RF2") } # Status message set by the monitoring application. record(stringout, "SPEARMON:RF2StatusMsg") { field(DESC, "RF2 Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:RF2Count") { field(DESC, "RF2 Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:RF2CountDelay") { field(DESC, "RF2 Monitor Count Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:RF2LatchDelay") { field(DESC, "RF2 Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:RF2Ack") { field(DESC, "RF2 Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:RF2AckType") { field(DESC, "RF2 Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:RF2ModeFilter") { field(DESC, "RF2 Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:RF2Audio") { field(DESC, "RF2 Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:RF2AudioState") { field(DESC, "RF2 Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:RF2AudioRepeat") { field(DESC, "RF2 Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:RF2AudioDelay") { field(DESC, "RF2 Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:RF2Disable") { field(DESC, "RF2 Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:RF3") { field(DESC, "RF3 Monitor") field(PINI, "YES") field(VAL, "RF3") } # Status message set by the monitoring application. record(stringout, "SPEARMON:RF3StatusMsg") { field(DESC, "RF3 Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:RF3Count") { field(DESC, "RF3 Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:RF3CountDelay") { field(DESC, "RF3 Monitor Count Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:RF3LatchDelay") { field(DESC, "RF3 Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:RF3Ack") { field(DESC, "RF3 Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:RF3AckType") { field(DESC, "RF3 Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:RF3ModeFilter") { field(DESC, "RF3 Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:RF3Audio") { field(DESC, "RF3 Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:RF3AudioState") { field(DESC, "RF3 Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:RF3AudioRepeat") { field(DESC, "RF3 Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:RF3AudioDelay") { field(DESC, "RF3 Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:RF3Disable") { field(DESC, "RF3 Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:RF4") { field(DESC, "RF4 Monitor") field(PINI, "YES") field(VAL, "RF4") } # Status message set by the monitoring application. record(stringout, "SPEARMON:RF4StatusMsg") { field(DESC, "RF4 Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:RF4Count") { field(DESC, "RF4 Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:RF4CountDelay") { field(DESC, "RF4 Monitor Count Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:RF4LatchDelay") { field(DESC, "RF4 Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:RF4Ack") { field(DESC, "RF4 Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:RF4AckType") { field(DESC, "RF4 Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:RF4ModeFilter") { field(DESC, "RF4 Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:RF4Audio") { field(DESC, "RF4 Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:RF4AudioState") { field(DESC, "RF4 Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:RF4AudioRepeat") { field(DESC, "RF4 Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:RF4AudioDelay") { field(DESC, "RF4 Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:RF4Disable") { field(DESC, "RF4 Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:RF5") { field(DESC, "RF5 Monitor") field(PINI, "YES") field(VAL, "RF5") } # Status message set by the monitoring application. record(stringout, "SPEARMON:RF5StatusMsg") { field(DESC, "RF5 Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:RF5Count") { field(DESC, "RF5 Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:RF5CountDelay") { field(DESC, "RF5 Monitor Count Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:RF5LatchDelay") { field(DESC, "RF5 Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:RF5Ack") { field(DESC, "RF5 Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:RF5AckType") { field(DESC, "RF5 Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:RF5ModeFilter") { field(DESC, "RF5 Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:RF5Audio") { field(DESC, "RF5 Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:RF5AudioState") { field(DESC, "RF5 Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:RF5AudioRepeat") { field(DESC, "RF5 Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:RF5AudioDelay") { field(DESC, "RF5 Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:RF5Disable") { field(DESC, "RF5 Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:Press1") { field(DESC, "Press1 Monitor") field(PINI, "YES") field(VAL, "Vacuum Mon.") } # Status message set by the monitoring application. record(stringout, "SPEARMON:Press1StatusMsg") { field(DESC, "Press1 Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:Press1Count") { field(DESC, "Press1 Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:Press1CountDelay") { field(DESC, "Press1 Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:Press1LatchDelay") { field(DESC, "Press1 Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:Press1Ack") { field(DESC, "Press1 Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:Press1AckType") { field(DESC, "Press1 Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:Press1ModeFilter") { field(DESC, "Press1 Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:Press1Audio") { field(DESC, "Press1 Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:Press1AudioState") { field(DESC, "Press1 Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:Press1AudioRepeat") { field(DESC, "Press1 Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:Press1AudioDelay") { field(DESC, "Press1 Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:Press1Disable") { field(DESC, "Press1 Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:Press2") { field(DESC, "Press2 Monitor") field(PINI, "YES") field(VAL, "Press2") } # Status message set by the monitoring application. record(stringout, "SPEARMON:Press2StatusMsg") { field(DESC, "Press2 Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:Press2Count") { field(DESC, "Press2 Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:Press2CountDelay") { field(DESC, "Press2 Monitor Count Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:Press2LatchDelay") { field(DESC, "Press2 Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:Press2Ack") { field(DESC, "Press2 Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:Press2AckType") { field(DESC, "Press2 Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:Press2ModeFilter") { field(DESC, "Press2 Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:Press2Audio") { field(DESC, "Press2 Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:Press2AudioState") { field(DESC, "Press2 Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:Press2AudioRepeat") { field(DESC, "Press2 Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:Press2AudioDelay") { field(DESC, "Press2 Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:Press2Disable") { field(DESC, "Press2 Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:Beam1") { field(DESC, "Beam1 Monitor") field(PINI, "YES") field(VAL, "CURMON") } # Status message set by the monitoring application. record(stringout, "SPEARMON:Beam1StatusMsg") { field(DESC, "Beam1 Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:Beam1Count") { field(DESC, "Beam1 Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:Beam1CountDelay") { field(DESC, "Beam1 Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:Beam1LatchDelay") { field(DESC, "Beam1 Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:Beam1Ack") { field(DESC, "Beam1 Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:Beam1AckType") { field(DESC, "Beam1 Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:Beam1ModeFilter") { field(DESC, "Beam1 Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:Beam1Audio") { field(DESC, "Beam1 Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:Beam1AudioState") { field(DESC, "Beam1 Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:Beam1AudioRepeat") { field(DESC, "Beam1 Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:Beam1AudioDelay") { field(DESC, "Beam1 Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:Beam1Disable") { field(DESC, "Beam1 Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:Beam3") { field(DESC, "Beam3 Monitor") field(PINI, "YES") field(VAL, "BL Intrlk") } # Status message set by the monitoring application. record(stringout, "SPEARMON:Beam3StatusMsg") { field(DESC, "Beam3 Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:Beam3Count") { field(DESC, "Beam3 Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:Beam3CountDelay") { field(DESC, "Beam3 Monitor Count Delay") field(PINI, "YES") field(DOL, "50") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:Beam3LatchDelay") { field(DESC, "Beam3 Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:Beam3Ack") { field(DESC, "Beam3 Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:Beam3AckType") { field(DESC, "Beam3 Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:Beam3ModeFilter") { field(DESC, "Beam3 Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:Beam3Audio") { field(DESC, "Beam3 Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:Beam3AudioState") { field(DESC, "Beam3 Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:Beam3AudioRepeat") { field(DESC, "Beam3 Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:Beam3AudioDelay") { field(DESC, "Beam3 Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:Beam3Disable") { field(DESC, "Beam3 Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:Beam4") { field(DESC, "Beam4 Monitor") field(PINI, "YES") field(VAL, "CURR Intrlk") } # Status message set by the monitoring application. record(stringout, "SPEARMON:Beam4StatusMsg") { field(DESC, "Beam4 Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:Beam4Count") { field(DESC, "Beam4 Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:Beam4CountDelay") { field(DESC, "Beam4 Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:Beam4LatchDelay") { field(DESC, "Beam4 Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:Beam4Ack") { field(DESC, "Beam4 Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:Beam4AckType") { field(DESC, "Beam4 Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:Beam4ModeFilter") { field(DESC, "Beam4 Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:Beam4Audio") { field(DESC, "Beam4 Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:Beam4AudioState") { field(DESC, "Beam4 Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:Beam4AudioRepeat") { field(DESC, "Beam4 Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:Beam4AudioDelay") { field(DESC, "Beam4 Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:Beam4Disable") { field(DESC, "Beam4 Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:Beam5") { field(DESC, "Beam5 Monitor") field(PINI, "YES") field(VAL, "Beam Integral") } # Status message set by the monitoring application. record(stringout, "SPEARMON:Beam5StatusMsg") { field(DESC, "Beam5 Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:Beam5Count") { field(DESC, "Beam5 Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:Beam5CountDelay") { field(DESC, "Beam5 Monitor Count Delay") field(PINI, "YES") field(DOL, "50") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:Beam5LatchDelay") { field(DESC, "Beam5 Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:Beam5Ack") { field(DESC, "Beam5 Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:Beam5AckType") { field(DESC, "Beam5 Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:Beam5ModeFilter") { field(DESC, "Beam5 Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:Beam5Audio") { field(DESC, "Beam5 Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:Beam5AudioState") { field(DESC, "Beam5 Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:Beam5AudioRepeat") { field(DESC, "Beam5 Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:Beam5AudioDelay") { field(DESC, "Beam5 Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:Beam5Disable") { field(DESC, "Beam5 Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:Temp1") { field(DESC, "Temp1 Monitor") field(PINI, "YES") field(VAL, "TC Intrlk") } # Status message set by the monitoring application. record(stringout, "SPEARMON:Temp1StatusMsg") { field(DESC, "Temp1 Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:Temp1Count") { field(DESC, "Temp1 Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:Temp1CountDelay") { field(DESC, "Temp1 Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:Temp1LatchDelay") { field(DESC, "Temp1 Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:Temp1Ack") { field(DESC, "Temp1 Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:Temp1AckType") { field(DESC, "Temp1 Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:Temp1ModeFilter") { field(DESC, "Temp1 Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:Temp1Audio") { field(DESC, "Temp1 Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:Temp1AudioState") { field(DESC, "Temp1 Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:Temp1AudioRepeat") { field(DESC, "Temp1 Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:Temp1AudioDelay") { field(DESC, "Temp1 Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:Temp1Disable") { field(DESC, "Temp1 Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:Temp2") { field(DESC, "Temp2 Monitor") field(PINI, "YES") field(VAL, "Room Monitor") } # Status message set by the monitoring application. record(stringout, "SPEARMON:Temp2StatusMsg") { field(DESC, "Temp2 Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:Temp2Count") { field(DESC, "Temp2 Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:Temp2CountDelay") { field(DESC, "Temp2 Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:Temp2LatchDelay") { field(DESC, "Temp2 Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:Temp2Ack") { field(DESC, "Temp2 Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:Temp2AckType") { field(DESC, "Temp2 Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:Temp2ModeFilter") { field(DESC, "Temp2 Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:Temp2Audio") { field(DESC, "Temp2 Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:Temp2AudioState") { field(DESC, "Temp2 Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:Temp2AudioRepeat") { field(DESC, "Temp2 Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:Temp2AudioDelay") { field(DESC, "Temp2 Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:Temp2Disable") { field(DESC, "Temp2 Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:Temp3") { field(DESC, "Temp3 Monitor") field(PINI, "YES") field(VAL, "Temp3") } # Status message set by the monitoring application. record(stringout, "SPEARMON:Temp3StatusMsg") { field(DESC, "Temp3 Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:Temp3Count") { field(DESC, "Temp3 Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:Temp3CountDelay") { field(DESC, "Temp3 Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:Temp3LatchDelay") { field(DESC, "Temp3 Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:Temp3Ack") { field(DESC, "Temp3 Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:Temp3AckType") { field(DESC, "Temp3 Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:Temp3ModeFilter") { field(DESC, "Temp3 Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:Temp3Audio") { field(DESC, "Temp3 Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:Temp3AudioState") { field(DESC, "Temp3 Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:Temp3AudioRepeat") { field(DESC, "Temp3 Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:Temp3AudioDelay") { field(DESC, "Temp3 Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:Temp3Disable") { field(DESC, "Temp3 Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:Temp4") { field(DESC, "Temp4 Monitor") field(PINI, "YES") field(VAL, "Temp4") } # Status message set by the monitoring application. record(stringout, "SPEARMON:Temp4StatusMsg") { field(DESC, "Temp4 Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:Temp4Count") { field(DESC, "Temp4 Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:Temp4CountDelay") { field(DESC, "Temp4 Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:Temp4LatchDelay") { field(DESC, "Temp4 Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:Temp4Ack") { field(DESC, "Temp4 Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:Temp4AckType") { field(DESC, "Temp4 Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:Temp4ModeFilter") { field(DESC, "Temp4 Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:Temp4Audio") { field(DESC, "Temp4 Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:Temp4AudioState") { field(DESC, "Temp4 Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:Temp4AudioRepeat") { field(DESC, "Temp4 Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:Temp4AudioDelay") { field(DESC, "Temp4 Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:Temp4Disable") { field(DESC, "Temp4 Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:Temp5") { field(DESC, "Temp5 Monitor") field(PINI, "YES") field(VAL, "Temp5") } # Status message set by the monitoring application. record(stringout, "SPEARMON:Temp5StatusMsg") { field(DESC, "Temp5 Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:Temp5Count") { field(DESC, "Temp5 Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:Temp5CountDelay") { field(DESC, "Temp5 Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:Temp5LatchDelay") { field(DESC, "Temp5 Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:Temp5Ack") { field(DESC, "Temp5 Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:Temp5AckType") { field(DESC, "Temp5 Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:Temp5ModeFilter") { field(DESC, "Temp5 Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:Temp5Audio") { field(DESC, "Temp5 Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:Temp5AudioState") { field(DESC, "Temp5 Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:Temp5AudioRepeat") { field(DESC, "Temp5 Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:Temp5AudioDelay") { field(DESC, "Temp5 Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:Temp5Disable") { field(DESC, "Temp5 Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:GUNFB") { field(DESC, "GUNFB Monitor") field(PINI, "YES") field(VAL, "Gun Feedback") } # Status message set by the monitoring application. record(stringout, "SPEARMON:GUNFBStatusMsg") { field(DESC, "GUNFB Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:GUNFBCount") { field(DESC, "GUNFB Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:GUNFBCountDelay") { field(DESC, "GUNFB Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:GUNFBLatchDelay") { field(DESC, "GUNFB Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:GUNFBAck") { field(DESC, "GUNFB Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:GUNFBAckType") { field(DESC, "GUNFB Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:GUNFBModeFilter") { field(DESC, "GUNFB Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:GUNFBAudio") { field(DESC, "GUNFB Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:GUNFBAudioState") { field(DESC, "GUNFB Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:GUNFBAudioRepeat") { field(DESC, "GUNFB Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:GUNFBAudioDelay") { field(DESC, "GUNFB Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:GUNFBDisable") { field(DESC, "GUNFB Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:LINFB") { field(DESC, "LINFB Monitor") field(PINI, "YES") field(VAL, "Linac Feedback") } # Status message set by the monitoring application. record(stringout, "SPEARMON:LINFBStatusMsg") { field(DESC, "LINFB Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:LINFBCount") { field(DESC, "LINFB Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:LINFBCountDelay") { field(DESC, "LINFB Monitor Count Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:LINFBLatchDelay") { field(DESC, "LINFB Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:LINFBAck") { field(DESC, "LINFB Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:LINFBAckType") { field(DESC, "LINFB Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:LINFBModeFilter") { field(DESC, "LINFB Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:LINFBAudio") { field(DESC, "LINFB Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:LINFBAudioState") { field(DESC, "LINFB Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:LINFBAudioRepeat") { field(DESC, "LINFB Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:LINFBAudioDelay") { field(DESC, "LINFB Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:LINFBDisable") { field(DESC, "LINFB Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:BOOFB") { field(DESC, "BOOFB Monitor") field(PINI, "YES") field(VAL, "Booster Feedback") } # Status message set by the monitoring application. record(stringout, "SPEARMON:BOOFBStatusMsg") { field(DESC, "BOOFB Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:BOOFBCount") { field(DESC, "BOOFB Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:BOOFBCountDelay") { field(DESC, "BOOFB Monitor Count Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:BOOFBLatchDelay") { field(DESC, "BOOFB Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:BOOFBAck") { field(DESC, "BOOFB Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:BOOFBAckType") { field(DESC, "BOOFB Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:BOOFBModeFilter") { field(DESC, "BOOFB Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:BOOFBAudio") { field(DESC, "BOOFB Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:BOOFBAudioState") { field(DESC, "BOOFB Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:BOOFBAudioRepeat") { field(DESC, "BOOFB Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:BOOFBAudioDelay") { field(DESC, "BOOFB Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:BOOFBDisable") { field(DESC, "BOOFB Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:BTSFB") { field(DESC, "BTSFB Monitor") field(PINI, "YES") field(VAL, "BTS Feedback") } # Status message set by the monitoring application. record(stringout, "SPEARMON:BTSFBStatusMsg") { field(DESC, "BTSFB Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:BTSFBCount") { field(DESC, "BTSFB Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:BTSFBCountDelay") { field(DESC, "BTSFB Monitor Count Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:BTSFBLatchDelay") { field(DESC, "BTSFB Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:BTSFBAck") { field(DESC, "BTSFB Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:BTSFBAckType") { field(DESC, "BTSFB Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:BTSFBModeFilter") { field(DESC, "BTSFB Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:BTSFBAudio") { field(DESC, "BTSFB Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:BTSFBAudioState") { field(DESC, "BTSFB Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:BTSFBAudioRepeat") { field(DESC, "BTSFB Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:BTSFBAudioDelay") { field(DESC, "BTSFB Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:BTSFBDisable") { field(DESC, "BTSFB Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:WCFB") { field(DESC, "WCFB Monitor") field(PINI, "YES") field(VAL, "White Circuit Feedback") } # Status message set by the monitoring application. record(stringout, "SPEARMON:WCFBStatusMsg") { field(DESC, "WCFB Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:WCFBCount") { field(DESC, "WCFB Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:WCFBCountDelay") { field(DESC, "WCFB Monitor Count Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:WCFBLatchDelay") { field(DESC, "WCFB Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:WCFBAck") { field(DESC, "WCFB Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:WCFBAckType") { field(DESC, "WCFB Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:WCFBModeFilter") { field(DESC, "WCFB Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:WCFBAudio") { field(DESC, "WCFB Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:WCFBAudioState") { field(DESC, "WCFB Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:WCFBAudioRepeat") { field(DESC, "WCFB Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:WCFBAudioDelay") { field(DESC, "WCFB Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:WCFBDisable") { field(DESC, "WCFB Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:CAMAC") { field(DESC, "CAMAC Monitor") field(PINI, "YES") field(VAL, "CAMAC Readout") } # Status message set by the monitoring application. record(stringout, "SPEARMON:CAMACStatusMsg") { field(DESC, "CAMAC Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:CAMACCount") { field(DESC, "CAMAC Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:CAMACCountDelay") { field(DESC, "CAMAC Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:CAMACLatchDelay") { field(DESC, "CAMAC Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:CAMACAck") { field(DESC, "CAMAC Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:CAMACAckType") { field(DESC, "CAMAC Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:CAMACModeFilter") { field(DESC, "CAMAC Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:CAMACAudio") { field(DESC, "CAMAC Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:CAMACAudioState") { field(DESC, "CAMAC Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:CAMACAudioRepeat") { field(DESC, "CAMAC Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:CAMACAudioDelay") { field(DESC, "CAMAC Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:CAMACDisable") { field(DESC, "CAMAC Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:SPEARHST") { field(DESC, "SPEARHST Monitor") field(PINI, "YES") field(VAL, "SPEAR History") } # Status message set by the monitoring application. record(stringout, "SPEARMON:SPEARHSTStatusMsg") { field(DESC, "SPEARHST Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:SPEARHSTCount") { field(DESC, "SPEARHST Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:SPEARHSTCountDelay") { field(DESC, "SPEARHST Monitor Count Delay") field(PINI, "YES") field(DOL, "20") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:SPEARHSTLatchDelay") { field(DESC, "SPEARHST Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:SPEARHSTAck") { field(DESC, "SPEARHST Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:SPEARHSTAckType") { field(DESC, "SPEARHST Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:SPEARHSTModeFilter") { field(DESC, "SPEARHST Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:SPEARHSTAudio") { field(DESC, "SPEARHST Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:SPEARHSTAudioState") { field(DESC, "SPEARHST Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:SPEARHSTAudioRepeat") { field(DESC, "SPEARHST Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:SPEARHSTAudioDelay") { field(DESC, "SPEARHST Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:SPEARHSTDisable") { field(DESC, "SPEARHST Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:ACM") { field(DESC, "ACM Monitor") field(PINI, "YES") field(VAL, "ACM Accounting") } # Status message set by the monitoring application. record(stringout, "SPEARMON:ACMStatusMsg") { field(DESC, "ACM Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:ACMCount") { field(DESC, "ACM Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:ACMCountDelay") { field(DESC, "ACM Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:ACMLatchDelay") { field(DESC, "ACM Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:ACMAck") { field(DESC, "ACM Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:ACMAckType") { field(DESC, "ACM Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:ACMModeFilter") { field(DESC, "ACM Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:ACMAudio") { field(DESC, "ACM Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:ACMAudioState") { field(DESC, "ACM Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:ACMAudioRepeat") { field(DESC, "ACM Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:ACMAudioDelay") { field(DESC, "ACM Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:ACMDisable") { field(DESC, "ACM Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:ConfCntl") { field(DESC, "ConfCntl Monitor") field(PINI, "YES") field(VAL, "Conf Mgmt") } # Status message set by the monitoring application. record(stringout, "SPEARMON:ConfCntlStatusMsg") { field(DESC, "ConfCntl Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:ConfCntlCount") { field(DESC, "ConfCntl Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:ConfCntlCountDelay") { field(DESC, "ConfCntl Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:ConfCntlLatchDelay") { field(DESC, "ConfCntl Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:ConfCntlAck") { field(DESC, "ConfCntl Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:ConfCntlAckType") { field(DESC, "ConfCntl Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:ConfCntlModeFilter") { field(DESC, "ConfCntl Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:ConfCntlAudio") { field(DESC, "ConfCntl Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:ConfCntlAudioState") { field(DESC, "ConfCntl Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:ConfCntlAudioRepeat") { field(DESC, "ConfCntl Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:ConfCntlAudioDelay") { field(DESC, "ConfCntl Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:ConfCntlDisable") { field(DESC, "ConfCntl Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:Inject") { field(DESC, "Inject Monitor") field(PINI, "YES") field(VAL, "Automatic Injection") } # Status message set by the monitoring application. record(stringout, "SPEARMON:InjectStatusMsg") { field(DESC, "Inject Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:InjectCount") { field(DESC, "Inject Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:InjectCountDelay") { field(DESC, "Inject Monitor Count Delay") field(PINI, "YES") field(DOL, "20") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:InjectLatchDelay") { field(DESC, "Inject Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:InjectAck") { field(DESC, "Inject Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:InjectAckType") { field(DESC, "Inject Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:InjectModeFilter") { field(DESC, "Inject Monitor Mode Filter") field(PINI, "YES") field(DOL, "3") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:InjectAudio") { field(DESC, "Inject Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:InjectAudioState") { field(DESC, "Inject Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:InjectAudioRepeat") { field(DESC, "Inject Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:InjectAudioDelay") { field(DESC, "Inject Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:InjectDisable") { field(DESC, "Inject Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:BOO-RFPhase") { field(DESC, "BOO-RFPhase Monitor") field(PINI, "YES") field(VAL, "BOO RF Phase Stab") } # Status message set by the monitoring application. record(stringout, "SPEARMON:BOO-RFPhaseStatusMsg") { field(DESC, "BOO-RFPhase Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:BOO-RFPhaseCount") { field(DESC, "BOO-RFPhase Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:BOO-RFPhaseCountDelay") { field(DESC, "BOO-RFPhase Monitor Count Delay") field(PINI, "YES") field(DOL, "20") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:BOO-RFPhaseLatchDelay") { field(DESC, "BOO-RFPhase Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:BOO-RFPhaseAck") { field(DESC, "BOO-RFPhase Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:BOO-RFPhaseAckType") { field(DESC, "BOO-RFPhase Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:BOO-RFPhaseModeFilter") { field(DESC, "BOO-RFPhase Monitor Mode Filter") field(PINI, "YES") field(DOL, "3") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:BOO-RFPhaseAudio") { field(DESC, "BOO-RFPhase Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:BOO-RFPhaseAudioState") { field(DESC, "BOO-RFPhase Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:BOO-RFPhaseAudioRepeat") { field(DESC, "BOO-RFPhase Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:BOO-RFPhaseAudioDelay") { field(DESC, "BOO-RFPhase Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:BOO-RFPhaseDisable") { field(DESC, "BOO-RFPhase Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:IVUNIntrlk") { field(DESC, "IVUNIntrlk Monitor") field(PINI, "YES") field(VAL, "IVUN Intrlk") } # Status message set by the monitoring application. record(stringout, "SPEARMON:IVUNIntrlkStatusMsg") { field(DESC, "IVUNIntrlk Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:IVUNIntrlkCount") { field(DESC, "IVUNIntrlk Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:IVUNIntrlkCountDelay") { field(DESC, "IVUNIntrlk Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:IVUNIntrlkLatchDelay") { field(DESC, "IVUNIntrlk Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:IVUNIntrlkAck") { field(DESC, "IVUNIntrlk Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:IVUNIntrlkAckType") { field(DESC, "IVUNIntrlk Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:IVUNIntrlkModeFilter") { field(DESC, "IVUNIntrlk Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:IVUNIntrlkAudio") { field(DESC, "IVUNIntrlk Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:IVUNIntrlkAudioState") { field(DESC, "IVUNIntrlk Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:IVUNIntrlkAudioRepeat") { field(DESC, "IVUNIntrlk Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:IVUNIntrlkAudioDelay") { field(DESC, "IVUNIntrlk Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:IVUNIntrlkDisable") { field(DESC, "IVUNIntrlk Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:PicoHarp01") { field(DESC, "PicoHarp01 Monitor") field(PINI, "YES") field(VAL, "PicoHarp01") } # Status message set by the monitoring application. record(stringout, "SPEARMON:PicoHarp01StatusMsg") { field(DESC, "PicoHarp01 Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:PicoHarp01Count") { field(DESC, "PicoHarp01 Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:PicoHarp01CountDelay") { field(DESC, "PicoHarp01 Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:PicoHarp01LatchDelay") { field(DESC, "PicoHarp01 Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:PicoHarp01Ack") { field(DESC, "PicoHarp01 Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:PicoHarp01AckType") { field(DESC, "PicoHarp01 Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:PicoHarp01ModeFilter") { field(DESC, "PicoHarp01 Monitor Mode Filter") field(PINI, "YES") field(DOL, "3") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:PicoHarp01Audio") { field(DESC, "PicoHarp01 Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:PicoHarp01AudioState") { field(DESC, "PicoHarp01 Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:PicoHarp01AudioRepeat") { field(DESC, "PicoHarp01 Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:PicoHarp01AudioDelay") { field(DESC, "PicoHarp01 Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:PicoHarp01Disable") { field(DESC, "PicoHarp01 Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:InjSrv") { field(DESC, "InjSrv Monitor") field(PINI, "YES") field(VAL, "INJECTOR_SERVER") } # Status message set by the monitoring application. record(stringout, "SPEARMON:InjSrvStatusMsg") { field(DESC, "InjSrv Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:InjSrvCount") { field(DESC, "InjSrv Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:InjSrvCountDelay") { field(DESC, "InjSrv Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:InjSrvLatchDelay") { field(DESC, "InjSrv Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:InjSrvAck") { field(DESC, "InjSrv Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:InjSrvAckType") { field(DESC, "InjSrv Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:InjSrvModeFilter") { field(DESC, "InjSrv Monitor Mode Filter") field(PINI, "YES") field(DOL, "3") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:InjSrvAudio") { field(DESC, "InjSrv Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:InjSrvAudioState") { field(DESC, "InjSrv Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:InjSrvAudioRepeat") { field(DESC, "InjSrv Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:InjSrvAudioDelay") { field(DESC, "InjSrv Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:InjSrvDisable") { field(DESC, "InjSrv Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:MsgHnd1") { field(DESC, "MsgHnd1 Monitor") field(PINI, "YES") field(VAL, "MSG_HANDLER") } # Status message set by the monitoring application. record(stringout, "SPEARMON:MsgHnd1StatusMsg") { field(DESC, "MsgHnd1 Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:MsgHnd1Count") { field(DESC, "MsgHnd1 Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:MsgHnd1CountDelay") { field(DESC, "MsgHnd1 Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:MsgHnd1LatchDelay") { field(DESC, "MsgHnd1 Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:MsgHnd1Ack") { field(DESC, "MsgHnd1 Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:MsgHnd1AckType") { field(DESC, "MsgHnd1 Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:MsgHnd1ModeFilter") { field(DESC, "MsgHnd1 Monitor Mode Filter") field(PINI, "YES") field(DOL, "3") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:MsgHnd1Audio") { field(DESC, "MsgHnd1 Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:MsgHnd1AudioState") { field(DESC, "MsgHnd1 Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:MsgHnd1AudioRepeat") { field(DESC, "MsgHnd1 Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:MsgHnd1AudioDelay") { field(DESC, "MsgHnd1 Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:MsgHnd1Disable") { field(DESC, "MsgHnd1 Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:SprSrv") { field(DESC, "SprSrv Monitor") field(PINI, "YES") field(VAL, "SPEAR_SERVER") } # Status message set by the monitoring application. record(stringout, "SPEARMON:SprSrvStatusMsg") { field(DESC, "SprSrv Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:SprSrvCount") { field(DESC, "SprSrv Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:SprSrvCountDelay") { field(DESC, "SprSrv Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:SprSrvLatchDelay") { field(DESC, "SprSrv Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:SprSrvAck") { field(DESC, "SprSrv Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:SprSrvAckType") { field(DESC, "SprSrv Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:SprSrvModeFilter") { field(DESC, "SprSrv Monitor Mode Filter") field(PINI, "YES") field(DOL, "3") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:SprSrvAudio") { field(DESC, "SprSrv Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:SprSrvAudioState") { field(DESC, "SprSrv Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:SprSrvAudioRepeat") { field(DESC, "SprSrv Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:SprSrvAudioDelay") { field(DESC, "SprSrv Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:SprSrvDisable") { field(DESC, "SprSrv Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:AlrmSeq") { field(DESC, "AlrmSeq Monitor") field(PINI, "YES") field(VAL, "ALARMSEQ") } # Status message set by the monitoring application. record(stringout, "SPEARMON:AlrmSeqStatusMsg") { field(DESC, "AlrmSeq Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:AlrmSeqCount") { field(DESC, "AlrmSeq Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:AlrmSeqCountDelay") { field(DESC, "AlrmSeq Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:AlrmSeqLatchDelay") { field(DESC, "AlrmSeq Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:AlrmSeqAck") { field(DESC, "AlrmSeq Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:AlrmSeqAckType") { field(DESC, "AlrmSeq Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:AlrmSeqModeFilter") { field(DESC, "AlrmSeq Monitor Mode Filter") field(PINI, "YES") field(DOL, "3") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:AlrmSeqAudio") { field(DESC, "AlrmSeq Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:AlrmSeqAudioState") { field(DESC, "AlrmSeq Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:AlrmSeqAudioRepeat") { field(DESC, "AlrmSeq Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:AlrmSeqAudioDelay") { field(DESC, "AlrmSeq Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:AlrmSeqDisable") { field(DESC, "AlrmSeq Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:CalSrv") { field(DESC, "CalSrv Monitor") field(PINI, "YES") field(VAL, "CALSERVER") } # Status message set by the monitoring application. record(stringout, "SPEARMON:CalSrvStatusMsg") { field(DESC, "CalSrv Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:CalSrvCount") { field(DESC, "CalSrv Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:CalSrvCountDelay") { field(DESC, "CalSrv Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:CalSrvLatchDelay") { field(DESC, "CalSrv Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:CalSrvAck") { field(DESC, "CalSrv Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:CalSrvAckType") { field(DESC, "CalSrv Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:CalSrvModeFilter") { field(DESC, "CalSrv Monitor Mode Filter") field(PINI, "YES") field(DOL, "3") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:CalSrvAudio") { field(DESC, "CalSrv Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:CalSrvAudioState") { field(DESC, "CalSrv Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:CalSrvAudioRepeat") { field(DESC, "CalSrv Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:CalSrvAudioDelay") { field(DESC, "CalSrv Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:CalSrvDisable") { field(DESC, "CalSrv Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "LIN-RF-TUNER:Cell1PosnWatch") { field(DESC, "Cell1PosnWatch Monitor") field(PINI, "YES") field(VAL, "LIN Tuner pot") } # Status message set by the monitoring application. record(stringout, "LIN-RF-TUNER:Cell1PosnWatchStatusMsg") { field(DESC, "Cell1PosnWatch Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "LIN-RF-TUNER:Cell1PosnWatchCount") { field(DESC, "Cell1PosnWatch Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "LIN-RF-TUNER:Cell1PosnWatchCountDelay") { field(DESC, "Cell1PosnWatch Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "LIN-RF-TUNER:Cell1PosnWatchLatchDelay") { field(DESC, "Cell1PosnWatch Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "LIN-RF-TUNER:Cell1PosnWatchAck") { field(DESC, "Cell1PosnWatch Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "LIN-RF-TUNER:Cell1PosnWatchAckType") { field(DESC, "Cell1PosnWatch Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "LIN-RF-TUNER:Cell1PosnWatchModeFilter") { field(DESC, "Cell1PosnWatch Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "LIN-RF-TUNER:Cell1PosnWatchAudio") { field(DESC, "Cell1PosnWatch Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "LIN-RF-TUNER:Cell1PosnWatchAudioState") { field(DESC, "Cell1PosnWatch Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "LIN-RF-TUNER:Cell1PosnWatchAudioRepeat") { field(DESC, "Cell1PosnWatch Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "LIN-RF-TUNER:Cell1PosnWatchAudioDelay") { field(DESC, "Cell1PosnWatch Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "LIN-RF-TUNER:Cell1PosnWatchDisable") { field(DESC, "Cell1PosnWatch Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "BOO-RF-TUNER:Cell1PosnWatch") { field(DESC, "Cell1PosnWatch Monitor") field(PINI, "YES") field(VAL, "BOO Tuner1 pot") } # Status message set by the monitoring application. record(stringout, "BOO-RF-TUNER:Cell1PosnWatchStatusMsg") { field(DESC, "Cell1PosnWatch Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "BOO-RF-TUNER:Cell1PosnWatchCount") { field(DESC, "Cell1PosnWatch Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "BOO-RF-TUNER:Cell1PosnWatchCountDelay") { field(DESC, "Cell1PosnWatch Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "BOO-RF-TUNER:Cell1PosnWatchLatchDelay") { field(DESC, "Cell1PosnWatch Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "BOO-RF-TUNER:Cell1PosnWatchAck") { field(DESC, "Cell1PosnWatch Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "BOO-RF-TUNER:Cell1PosnWatchAckType") { field(DESC, "Cell1PosnWatch Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "BOO-RF-TUNER:Cell1PosnWatchModeFilter") { field(DESC, "Cell1PosnWatch Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "BOO-RF-TUNER:Cell1PosnWatchAudio") { field(DESC, "Cell1PosnWatch Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "BOO-RF-TUNER:Cell1PosnWatchAudioState") { field(DESC, "Cell1PosnWatch Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "BOO-RF-TUNER:Cell1PosnWatchAudioRepeat") { field(DESC, "Cell1PosnWatch Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "BOO-RF-TUNER:Cell1PosnWatchAudioDelay") { field(DESC, "Cell1PosnWatch Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "BOO-RF-TUNER:Cell1PosnWatchDisable") { field(DESC, "Cell1PosnWatch Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "BOO-RF-TUNER:Cell5PosnWatch") { field(DESC, "Cell5PosnWatch Monitor") field(PINI, "YES") field(VAL, "BOO Tuner5 pot") } # Status message set by the monitoring application. record(stringout, "BOO-RF-TUNER:Cell5PosnWatchStatusMsg") { field(DESC, "Cell5PosnWatch Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "BOO-RF-TUNER:Cell5PosnWatchCount") { field(DESC, "Cell5PosnWatch Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "BOO-RF-TUNER:Cell5PosnWatchCountDelay") { field(DESC, "Cell5PosnWatch Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "BOO-RF-TUNER:Cell5PosnWatchLatchDelay") { field(DESC, "Cell5PosnWatch Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "BOO-RF-TUNER:Cell5PosnWatchAck") { field(DESC, "Cell5PosnWatch Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "BOO-RF-TUNER:Cell5PosnWatchAckType") { field(DESC, "Cell5PosnWatch Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "BOO-RF-TUNER:Cell5PosnWatchModeFilter") { field(DESC, "Cell5PosnWatch Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "BOO-RF-TUNER:Cell5PosnWatchAudio") { field(DESC, "Cell5PosnWatch Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "BOO-RF-TUNER:Cell5PosnWatchAudioState") { field(DESC, "Cell5PosnWatch Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "BOO-RF-TUNER:Cell5PosnWatchAudioRepeat") { field(DESC, "Cell5PosnWatch Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "BOO-RF-TUNER:Cell5PosnWatchAudioDelay") { field(DESC, "Cell5PosnWatch Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "BOO-RF-TUNER:Cell5PosnWatchDisable") { field(DESC, "Cell5PosnWatch Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "LIN-RF-TUNER:Cell1MotorWatch") { field(DESC, "Cell1MotorWatch Monitor") field(PINI, "YES") field(VAL, "LIN Tuner1 motor") } # Status message set by the monitoring application. record(stringout, "LIN-RF-TUNER:Cell1MotorWatchStatusMsg") { field(DESC, "Cell1MotorWatch Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "LIN-RF-TUNER:Cell1MotorWatchCount") { field(DESC, "Cell1MotorWatch Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "LIN-RF-TUNER:Cell1MotorWatchCountDelay") { field(DESC, "Cell1MotorWatch Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "LIN-RF-TUNER:Cell1MotorWatchLatchDelay") { field(DESC, "Cell1MotorWatch Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "LIN-RF-TUNER:Cell1MotorWatchAck") { field(DESC, "Cell1MotorWatch Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "LIN-RF-TUNER:Cell1MotorWatchAckType") { field(DESC, "Cell1MotorWatch Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "LIN-RF-TUNER:Cell1MotorWatchModeFilter") { field(DESC, "Cell1MotorWatch Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "LIN-RF-TUNER:Cell1MotorWatchAudio") { field(DESC, "Cell1MotorWatch Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "LIN-RF-TUNER:Cell1MotorWatchAudioState") { field(DESC, "Cell1MotorWatch Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "LIN-RF-TUNER:Cell1MotorWatchAudioRepeat") { field(DESC, "Cell1MotorWatch Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "LIN-RF-TUNER:Cell1MotorWatchAudioDelay") { field(DESC, "Cell1MotorWatch Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "LIN-RF-TUNER:Cell1MotorWatchDisable") { field(DESC, "Cell1MotorWatch Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "BOO-RF-TUNER:Cell1MotorWatch") { field(DESC, "Cell1MotorWatch Monitor") field(PINI, "YES") field(VAL, "BOO Tuner1 motor") } # Status message set by the monitoring application. record(stringout, "BOO-RF-TUNER:Cell1MotorWatchStatusMsg") { field(DESC, "Cell1MotorWatch Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "BOO-RF-TUNER:Cell1MotorWatchCount") { field(DESC, "Cell1MotorWatch Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "BOO-RF-TUNER:Cell1MotorWatchCountDelay") { field(DESC, "Cell1MotorWatch Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "BOO-RF-TUNER:Cell1MotorWatchLatchDelay") { field(DESC, "Cell1MotorWatch Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "BOO-RF-TUNER:Cell1MotorWatchAck") { field(DESC, "Cell1MotorWatch Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "BOO-RF-TUNER:Cell1MotorWatchAckType") { field(DESC, "Cell1MotorWatch Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "BOO-RF-TUNER:Cell1MotorWatchModeFilter") { field(DESC, "Cell1MotorWatch Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "BOO-RF-TUNER:Cell1MotorWatchAudio") { field(DESC, "Cell1MotorWatch Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "BOO-RF-TUNER:Cell1MotorWatchAudioState") { field(DESC, "Cell1MotorWatch Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "BOO-RF-TUNER:Cell1MotorWatchAudioRepeat") { field(DESC, "Cell1MotorWatch Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "BOO-RF-TUNER:Cell1MotorWatchAudioDelay") { field(DESC, "Cell1MotorWatch Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "BOO-RF-TUNER:Cell1MotorWatchDisable") { field(DESC, "Cell1MotorWatch Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "BOO-RF-TUNER:Cell5MotorWatch") { field(DESC, "Cell5MotorWatch Monitor") field(PINI, "YES") field(VAL, "BOO Tuner5 motor") } # Status message set by the monitoring application. record(stringout, "BOO-RF-TUNER:Cell5MotorWatchStatusMsg") { field(DESC, "Cell5MotorWatch Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "BOO-RF-TUNER:Cell5MotorWatchCount") { field(DESC, "Cell5MotorWatch Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "BOO-RF-TUNER:Cell5MotorWatchCountDelay") { field(DESC, "Cell5MotorWatch Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "BOO-RF-TUNER:Cell5MotorWatchLatchDelay") { field(DESC, "Cell5MotorWatch Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "BOO-RF-TUNER:Cell5MotorWatchAck") { field(DESC, "Cell5MotorWatch Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "BOO-RF-TUNER:Cell5MotorWatchAckType") { field(DESC, "Cell5MotorWatch Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "BOO-RF-TUNER:Cell5MotorWatchModeFilter") { field(DESC, "Cell5MotorWatch Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "BOO-RF-TUNER:Cell5MotorWatchAudio") { field(DESC, "Cell5MotorWatch Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "BOO-RF-TUNER:Cell5MotorWatchAudioState") { field(DESC, "Cell5MotorWatch Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "BOO-RF-TUNER:Cell5MotorWatchAudioRepeat") { field(DESC, "Cell5MotorWatch Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "BOO-RF-TUNER:Cell5MotorWatchAudioDelay") { field(DESC, "Cell5MotorWatch Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "BOO-RF-TUNER:Cell5MotorWatchDisable") { field(DESC, "Cell5MotorWatch Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:BOORFCavFB") { field(DESC, "BOORFCavFB Monitor") field(PINI, "YES") field(VAL, "Booster RF Cav Feecback") } # Status message set by the monitoring application. record(stringout, "SPEARMON:BOORFCavFBStatusMsg") { field(DESC, "BOORFCavFB Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:BOORFCavFBCount") { field(DESC, "BOORFCavFB Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:BOORFCavFBCountDelay") { field(DESC, "BOORFCavFB Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:BOORFCavFBLatchDelay") { field(DESC, "BOORFCavFB Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:BOORFCavFBAck") { field(DESC, "BOORFCavFB Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:BOORFCavFBAckType") { field(DESC, "BOORFCavFB Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:BOORFCavFBModeFilter") { field(DESC, "BOORFCavFB Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:BOORFCavFBAudio") { field(DESC, "BOORFCavFB Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:BOORFCavFBAudioState") { field(DESC, "BOORFCavFB Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:BOORFCavFBAudioRepeat") { field(DESC, "BOORFCavFB Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:BOORFCavFBAudioDelay") { field(DESC, "BOORFCavFB Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:BOORFCavFBDisable") { field(DESC, "BOORFCavFB Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:LiberaAutoConfig") { field(DESC, "LiberaAutoConfig Monitor") field(PINI, "YES") field(VAL, "Libera BLM Auto Config") } # Status message set by the monitoring application. record(stringout, "SPEARMON:LiberaAutoConfigStatusMsg") { field(DESC, "LiberaAutoConfig Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:LiberaAutoConfigCount") { field(DESC, "LiberaAutoConfig Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:LiberaAutoConfigCountDelay") { field(DESC, "LiberaAutoConfig Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:LiberaAutoConfigLatchDelay") { field(DESC, "LiberaAutoConfig Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:LiberaAutoConfigAck") { field(DESC, "LiberaAutoConfig Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:LiberaAutoConfigAckType") { field(DESC, "LiberaAutoConfig Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:LiberaAutoConfigModeFilter") { field(DESC, "LiberaAutoConfig Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:LiberaAutoConfigAudio") { field(DESC, "LiberaAutoConfig Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:LiberaAutoConfigAudioState") { field(DESC, "LiberaAutoConfig Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:LiberaAutoConfigAudioRepeat") { field(DESC, "LiberaAutoConfig Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:LiberaAutoConfigAudioDelay") { field(DESC, "LiberaAutoConfig Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:LiberaAutoConfigDisable") { field(DESC, "LiberaAutoConfig Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } # Name of the monitoring application, set by the monitoring application. record(stringout, "SPEARMON:Curmon") { field(DESC, "Curmon Monitor") field(PINI, "YES") field(VAL, "CURMON IOC") } # Status message set by the monitoring application. record(stringout, "SPEARMON:CurmonStatusMsg") { field(DESC, "Curmon Monitor Status") field(PINI, "YES") field(VAL, "") } # Heart beat (counter), incremented by monitoring applicaton. # Program updates count on every cycle - when count is not incremented # in CountDelay seconds, then status is set to dead. # A CountDelay of 0 means program does not update Count. record(ao, "SPEARMON:CurmonCount") { field(DESC, "Curmon Monitor Count") field(PINI, "YES") field(DOL, "0") field(MDEL, "-1") } # If the alarm monitor does not see a change in Count after this delay, # it assumes the monitoring application is dead and # triggers an alarm. This alarm sets Status to 10. record(longout, "SPEARMON:CurmonCountDelay") { field(DESC, "Curmon Monitor Count Delay") field(PINI, "YES") field(DOL, "10") field(DRVH, "600") field(EGU, "Sec") field(MDEL, "-1") } # Changes in Status are accepted into Latch after this delay. # This parameter can filter short glitches. record(longout, "SPEARMON:CurmonLatchDelay") { field(DESC, "Curmon Latch Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Acknowledge button from operator. Acknowledges the current AlarmState. record(bo, "SPEARMON:CurmonAck") { field(DESC, "Curmon Monitor Ack State") field(PINI, "YES") field(ZNAM, "UnAcknowledge") field(ONAM, "Acknowledge") } # Type of acknowledgement. record(mbbo, "SPEARMON:CurmonAckType") { field(DESC, "Curmon Monitor Ack Type") field(PINI, "YES") field(DOL, "0") # Automatically acknowledge all alarms and return-to-normals field(ZRST, "Auto Ack") # Automatically acknowledge when return-to-normals (AlarmStatus going down) field(ONST, "Auto Ack RTN") # User must acknowledge any AlarmStatus change field(TWST, "Acknowledge") } # Filter alarms dependant on external conditions. # Initially, only the SPEAR status will be used. # This filter only filters alarms with a Status value of < 10. record(mbbo, "SPEARMON:CurmonModeFilter") { field(DESC, "Curmon Monitor Mode Filter") field(PINI, "YES") field(DOL, "0") # No Filter field(ZRST, "None") # Suppress alarm in DOWN mode field(ONST, "Down") # Suppress alarm in ACCPHY mode field(TWST, "AccPhy") # Suppress alarm in INJECT mode field(THST, "Inject") } # Audio alarm (on/off). Can be disabled by AudioState = 0. # OUT field defines wolf box channel. record(bo, "SPEARMON:CurmonAudio") { field(DESC, "Curmon Monitor Audio") field(DTYP, "Raw Soft Channel") field(OUT, "") field(DOL, "0") field(ZNAM, "No Alarm") field(ONAM, "Alarm") field(OSV, "MAJOR") field(PINI, "YES") } # Disable/Enable audio alarm. # (Should not be used by operator but for general configuration purpose only) record(bo, "SPEARMON:CurmonAudioState") { field(DESC, "Curmon Monitor Audio State") field(PINI, "YES") field(DOL, "1") field(ZNAM, "Off") field(ONAM, "On") } # Delay after which (unacknowledged) alarm will be retriggered # 0 = no repetitive alarms. record(longout, "SPEARMON:CurmonAudioRepeat") { field(DESC, "Curmon Audio Repeat") field(PINI, "YES") field(DOL, "0") field(DRVH, "300") field(EGU, "Sec") field(MDEL, "-1") } # Delay after which an alarm (Status > 1 ) sounds the audible alarm. record(longout, "SPEARMON:CurmonAudioDelay") { field(DESC, "Curmon Monitor Audio Delay") field(PINI, "YES") field(DOL, "0") field(DRVH, "120") field(EGU, "Sec") field(MDEL, "-1") } # Disable record for use by application. record(bo, "SPEARMON:CurmonDisable") { field(DESC, "Curmon Disable State") field(PINI, "YES") field(ZNAM, "Enabled") field(ONAM, "Disabled") } record(mbbo, "SPEARMON:Status") { field(DESC, " Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Latch") { field(DESC, " Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:AckedStatus") { field(DESC, " AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:AlarmStatus") { field(DESC, " AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:RFFBStatus") { field(DESC, "RFFB Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:RFFBLatch") { field(DESC, "RFFB Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:RFFBAckedStatus") { field(DESC, "RFFB AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:RFFBAlarmStatus") { field(DESC, "RFFB AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:SOFBStatus") { field(DESC, "SOFB Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:SOFBLatch") { field(DESC, "SOFB Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:SOFBAckedStatus") { field(DESC, "SOFB AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:SOFBAlarmStatus") { field(DESC, "SOFB AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:FDBKStatus") { field(DESC, "FDBK Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:FDBKLatch") { field(DESC, "FDBK Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:FDBKAckedStatus") { field(DESC, "FDBK AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:FDBKAlarmStatus") { field(DESC, "FDBK AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:BLDSStatus") { field(DESC, "BLDS Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "OFF") field(ONSV, "MINOR") field(TWST, "Warning") field(TWSV, "NO_ALARM") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:BLDSLatch") { field(DESC, "BLDS Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "OFF") field(ONSV, "MINOR") field(TWST, "Warning") field(TWSV, "NO_ALARM") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:BLDSAckedStatus") { field(DESC, "BLDS AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "OFF") field(ONSV, "MINOR") field(TWST, "Warning") field(TWSV, "NO_ALARM") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:BLDSAlarmStatus") { field(DESC, "BLDS AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "OFF") field(ONSV, "MINOR") field(TWST, "Warning") field(TWSV, "NO_ALARM") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:BL02PH1Status") { field(DESC, "BL02PH1 Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:BL02PH1Latch") { field(DESC, "BL02PH1 Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:BL02PH1AckedStatus") { field(DESC, "BL02PH1 AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:BL02PH1AlarmStatus") { field(DESC, "BL02PH1 AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:BPMRMSStatus") { field(DESC, "BPMRMS Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:BPMRMSLatch") { field(DESC, "BPMRMS Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:BPMRMSAckedStatus") { field(DESC, "BPMRMS AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:BPMRMSAlarmStatus") { field(DESC, "BPMRMS AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:RF1Status") { field(DESC, "RF1 Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:RF1Latch") { field(DESC, "RF1 Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:RF1AckedStatus") { field(DESC, "RF1 AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:RF1AlarmStatus") { field(DESC, "RF1 AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:RF2Status") { field(DESC, "RF2 Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:RF2Latch") { field(DESC, "RF2 Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:RF2AckedStatus") { field(DESC, "RF2 AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:RF2AlarmStatus") { field(DESC, "RF2 AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:RF3Status") { field(DESC, "RF3 Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:RF3Latch") { field(DESC, "RF3 Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:RF3AckedStatus") { field(DESC, "RF3 AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:RF3AlarmStatus") { field(DESC, "RF3 AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:RF4Status") { field(DESC, "RF4 Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:RF4Latch") { field(DESC, "RF4 Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:RF4AckedStatus") { field(DESC, "RF4 AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:RF4AlarmStatus") { field(DESC, "RF4 AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:RF5Status") { field(DESC, "RF5 Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:RF5Latch") { field(DESC, "RF5 Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:RF5AckedStatus") { field(DESC, "RF5 AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:RF5AlarmStatus") { field(DESC, "RF5 AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Press1Status") { field(DESC, "Press1 Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Press1Latch") { field(DESC, "Press1 Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Press1AckedStatus") { field(DESC, "Press1 AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Press1AlarmStatus") { field(DESC, "Press1 AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Press2Status") { field(DESC, "Press2 Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Press2Latch") { field(DESC, "Press2 Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Press2AckedStatus") { field(DESC, "Press2 AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Press2AlarmStatus") { field(DESC, "Press2 AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Beam1Status") { field(DESC, "Beam1 Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Beam1Latch") { field(DESC, "Beam1 Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Beam1AckedStatus") { field(DESC, "Beam1 AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Beam1AlarmStatus") { field(DESC, "Beam1 AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Beam3Status") { field(DESC, "Beam3 Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Beam3Latch") { field(DESC, "Beam3 Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Beam3AckedStatus") { field(DESC, "Beam3 AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Beam3AlarmStatus") { field(DESC, "Beam3 AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Beam4Status") { field(DESC, "Beam4 Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Beam4Latch") { field(DESC, "Beam4 Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Beam4AckedStatus") { field(DESC, "Beam4 AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Beam4AlarmStatus") { field(DESC, "Beam4 AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Beam5Status") { field(DESC, "Beam5 Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Beam5Latch") { field(DESC, "Beam5 Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Beam5AckedStatus") { field(DESC, "Beam5 AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Beam5AlarmStatus") { field(DESC, "Beam5 AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Temp1Status") { field(DESC, "Temp1 Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Temp1Latch") { field(DESC, "Temp1 Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Temp1AckedStatus") { field(DESC, "Temp1 AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Temp1AlarmStatus") { field(DESC, "Temp1 AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Temp2Status") { field(DESC, "Temp2 Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Temp2Latch") { field(DESC, "Temp2 Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Temp2AckedStatus") { field(DESC, "Temp2 AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Temp2AlarmStatus") { field(DESC, "Temp2 AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Temp3Status") { field(DESC, "Temp3 Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Temp3Latch") { field(DESC, "Temp3 Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Temp3AckedStatus") { field(DESC, "Temp3 AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Temp3AlarmStatus") { field(DESC, "Temp3 AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Temp4Status") { field(DESC, "Temp4 Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Temp4Latch") { field(DESC, "Temp4 Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Temp4AckedStatus") { field(DESC, "Temp4 AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Temp4AlarmStatus") { field(DESC, "Temp4 AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Temp5Status") { field(DESC, "Temp5 Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Temp5Latch") { field(DESC, "Temp5 Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Temp5AckedStatus") { field(DESC, "Temp5 AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:Temp5AlarmStatus") { field(DESC, "Temp5 AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:GUNFBStatus") { field(DESC, "GUNFB Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:GUNFBLatch") { field(DESC, "GUNFB Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:GUNFBAckedStatus") { field(DESC, "GUNFB AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:GUNFBAlarmStatus") { field(DESC, "GUNFB AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:LINFBStatus") { field(DESC, "LINFB Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:LINFBLatch") { field(DESC, "LINFB Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:LINFBAckedStatus") { field(DESC, "LINFB AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:LINFBAlarmStatus") { field(DESC, "LINFB AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:BOOFBStatus") { field(DESC, "BOOFB Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:BOOFBLatch") { field(DESC, "BOOFB Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:BOOFBAckedStatus") { field(DESC, "BOOFB AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:BOOFBAlarmStatus") { field(DESC, "BOOFB AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:BTSFBStatus") { field(DESC, "BTSFB Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:BTSFBLatch") { field(DESC, "BTSFB Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:BTSFBAckedStatus") { field(DESC, "BTSFB AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:BTSFBAlarmStatus") { field(DESC, "BTSFB AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:WCFBStatus") { field(DESC, "WCFB Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:WCFBLatch") { field(DESC, "WCFB Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:WCFBAckedStatus") { field(DESC, "WCFB AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:WCFBAlarmStatus") { field(DESC, "WCFB AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:CAMACStatus") { field(DESC, "CAMAC Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:CAMACLatch") { field(DESC, "CAMAC Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:CAMACAckedStatus") { field(DESC, "CAMAC AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:CAMACAlarmStatus") { field(DESC, "CAMAC AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:SPEARHSTStatus") { field(DESC, "SPEARHST Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:SPEARHSTLatch") { field(DESC, "SPEARHST Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:SPEARHSTAckedStatus") { field(DESC, "SPEARHST AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:SPEARHSTAlarmStatus") { field(DESC, "SPEARHST AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:ACMStatus") { field(DESC, "ACM Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:ACMLatch") { field(DESC, "ACM Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:ACMAckedStatus") { field(DESC, "ACM AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:ACMAlarmStatus") { field(DESC, "ACM AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:ConfCntlStatus") { field(DESC, "ConfCntl Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:ConfCntlLatch") { field(DESC, "ConfCntl Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:ConfCntlAckedStatus") { field(DESC, "ConfCntl AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:ConfCntlAlarmStatus") { field(DESC, "ConfCntl AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:InjectStatus") { field(DESC, "Inject Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "VAL") } record(mbbo, "SPEARMON:InjectLatch") { field(DESC, "Inject Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:InjectAckedStatus") { field(DESC, "Inject AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:InjectAlarmStatus") { field(DESC, "Inject AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:BOO-RFPhaseStatus") { field(DESC, "BOO-RFPhase Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:BOO-RFPhaseLatch") { field(DESC, "BOO-RFPhase Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:BOO-RFPhaseAckedStatus") { field(DESC, "BOO-RFPhase AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:BOO-RFPhaseAlarmStatus") { field(DESC, "BOO-RFPhase AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:IVUNIntrlkStatus") { field(DESC, "IVUNIntrlk Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:IVUNIntrlkLatch") { field(DESC, "IVUNIntrlk Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:IVUNIntrlkAckedStatus") { field(DESC, "IVUNIntrlk AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:IVUNIntrlkAlarmStatus") { field(DESC, "IVUNIntrlk AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:PicoHarp01Status") { field(DESC, "PicoHarp01 Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:PicoHarp01Latch") { field(DESC, "PicoHarp01 Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:PicoHarp01AckedStatus") { field(DESC, "PicoHarp01 AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:PicoHarp01AlarmStatus") { field(DESC, "PicoHarp01 AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:InjSrvStatus") { field(DESC, "InjSrv Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:InjSrvLatch") { field(DESC, "InjSrv Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:InjSrvAckedStatus") { field(DESC, "InjSrv AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:InjSrvAlarmStatus") { field(DESC, "InjSrv AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:MsgHnd1Status") { field(DESC, "MsgHnd1 Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:MsgHnd1Latch") { field(DESC, "MsgHnd1 Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:MsgHnd1AckedStatus") { field(DESC, "MsgHnd1 AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:MsgHnd1AlarmStatus") { field(DESC, "MsgHnd1 AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:SprSrvStatus") { field(DESC, "SprSrv Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:SprSrvLatch") { field(DESC, "SprSrv Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:SprSrvAckedStatus") { field(DESC, "SprSrv AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:SprSrvAlarmStatus") { field(DESC, "SprSrv AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:AlrmSeqStatus") { field(DESC, "AlrmSeq Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:AlrmSeqLatch") { field(DESC, "AlrmSeq Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:AlrmSeqAckedStatus") { field(DESC, "AlrmSeq AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:AlrmSeqAlarmStatus") { field(DESC, "AlrmSeq AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:CalSrvStatus") { field(DESC, "CalSrv Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:CalSrvLatch") { field(DESC, "CalSrv Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:CalSrvAckedStatus") { field(DESC, "CalSrv AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:CalSrvAlarmStatus") { field(DESC, "CalSrv AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "LIN-RF-TUNER:Cell1PosnWatchStatus") { field(DESC, "Cell1PosnWatch Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "LIN-RF-TUNER:Cell1PosnWatchLatch") { field(DESC, "Cell1PosnWatch Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "LIN-RF-TUNER:Cell1PosnWatchAckedStatus") { field(DESC, "Cell1PosnWatch AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "LIN-RF-TUNER:Cell1PosnWatchAlarmStatus") { field(DESC, "Cell1PosnWatch AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "BOO-RF-TUNER:Cell1PosnWatchStatus") { field(DESC, "Cell1PosnWatch Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "BOO-RF-TUNER:Cell1PosnWatchLatch") { field(DESC, "Cell1PosnWatch Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "BOO-RF-TUNER:Cell1PosnWatchAckedStatus") { field(DESC, "Cell1PosnWatch AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "BOO-RF-TUNER:Cell1PosnWatchAlarmStatus") { field(DESC, "Cell1PosnWatch AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "BOO-RF-TUNER:Cell5PosnWatchStatus") { field(DESC, "Cell5PosnWatch Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "BOO-RF-TUNER:Cell5PosnWatchLatch") { field(DESC, "Cell5PosnWatch Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "BOO-RF-TUNER:Cell5PosnWatchAckedStatus") { field(DESC, "Cell5PosnWatch AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "BOO-RF-TUNER:Cell5PosnWatchAlarmStatus") { field(DESC, "Cell5PosnWatch AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "LIN-RF-TUNER:Cell1MotorWatchStatus") { field(DESC, "Cell1MotorWatch Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "LIN-RF-TUNER:Cell1MotorWatchLatch") { field(DESC, "Cell1MotorWatch Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "LIN-RF-TUNER:Cell1MotorWatchAckedStatus") { field(DESC, "Cell1MotorWatch AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "LIN-RF-TUNER:Cell1MotorWatchAlarmStatus") { field(DESC, "Cell1MotorWatch AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "BOO-RF-TUNER:Cell1MotorWatchStatus") { field(DESC, "Cell1MotorWatch Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "BOO-RF-TUNER:Cell1MotorWatchLatch") { field(DESC, "Cell1MotorWatch Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "BOO-RF-TUNER:Cell1MotorWatchAckedStatus") { field(DESC, "Cell1MotorWatch AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "BOO-RF-TUNER:Cell1MotorWatchAlarmStatus") { field(DESC, "Cell1MotorWatch AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "BOO-RF-TUNER:Cell5MotorWatchStatus") { field(DESC, "Cell5MotorWatch Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "BOO-RF-TUNER:Cell5MotorWatchLatch") { field(DESC, "Cell5MotorWatch Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "BOO-RF-TUNER:Cell5MotorWatchAckedStatus") { field(DESC, "Cell5MotorWatch AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "BOO-RF-TUNER:Cell5MotorWatchAlarmStatus") { field(DESC, "Cell5MotorWatch AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:BOORFCavFBStatus") { field(DESC, "BOORFCavFB Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:BOORFCavFBLatch") { field(DESC, "BOORFCavFB Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:BOORFCavFBAckedStatus") { field(DESC, "BOORFCavFB AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:BOORFCavFBAlarmStatus") { field(DESC, "BOORFCavFB AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:LiberaAutoConfigStatus") { field(DESC, "LiberaAutoConfig Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:LiberaAutoConfigLatch") { field(DESC, "LiberaAutoConfig Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:LiberaAutoConfigAckedStatus") { field(DESC, "LiberaAutoConfig AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:LiberaAutoConfigAlarmStatus") { field(DESC, "LiberaAutoConfig AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:CurmonStatus") { field(DESC, "Curmon Status") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:CurmonLatch") { field(DESC, "Curmon Latch") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:CurmonAckedStatus") { field(DESC, "Curmon AckedStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } record(mbbo, "SPEARMON:CurmonAlarmStatus") { field(DESC, "Curmon AlarmStatus") field(PINI, "YES") field(DOL, "0") field(ZRST, "OK") field(ONST, "Informational") field(ONSV, "NO_ALARM") field(TWST, "Warning") field(TWSV, "MINOR") field(THST, "Alarm") field(THSV, "MAJOR") field(FRST, "Critical") field(FRSV, "MAJOR") field(FVST, "Invalid") field(FVSV, "INVALID") field(TEST, "Dead") field(TESV, "INVALID") info(autosaveFields, "") } # checks an incrementor PV to see if it's incrementing. # the incrementors are updated by ioc processes. # this will be 0 if old = current (i.e. not incrementing) # ======================================================= # A has current, B has previous record(calcout, "SPEARMON:BOORFCavFB:SCAN") { field(CALC, "A=B?0:A+1") field(SCAN, "1 second") field(INPA, "SPEARMON:BOORFCavFB:SCAN.VAL") field(INPB, "SPEARMON:BOORFCavFBCountDelay") field(OUT, "SPEARMON:BOORFCavFB:ALHBCURR.VAL PP") field(DOPT, "Use CALC") field(OOPT, "Transition To Zero") field(PINI, "YES") } record(ai, "SPEARMON:BOORFCavFB:ALHBCURR") { field(INP, "SPEARMON:BOORFCavFBCount NPP MS") field(SCAN, "Passive") field(FLNK, "SPEARMON:BOORFCavFB:ALHBCHK") } # scondam: 20-Sept-2018: # If the Heartbeat "Count" PV status is INVALID, ioc may be Dead. # Or if "Count" just not updating, ioc may be too slow or Dead. # else ioc is alive and heartbeat updating, everything OK. record(calcout, "SPEARMON:BOORFCavFB:ALHBCHK") { field(CALC, "(C>2)?10:(A=B)?10:0") field(INPA, "SPEARMON:BOORFCavFB:ALHBCURR NPP MS") field(INPB, "SPEARMON:BOORFCavFB:ALHBPREV.VAL NPP MS") field(INPC, "SPEARMON:BOORFCavFB:ALHBCURR.SEVR") field(OUT, "SPEARMON:BOORFCavFBAlarmStatus.VAL PP") field(OOPT, "On Change") field(FLNK, "SPEARMON:BOORFCavFB:ALHBERR") field(PINI, "YES") } # MS will cause this to be invalid if the HBCHK is record(mbbi, "SPEARMON:BOORFCavFB:ALHBERR") { field(DESC, "Booster RF Cav Feecback monitoring") field(INP, "SPEARMON:BOORFCavFB:ALHBCHK.VAL NPP MS") field(ZRSV, "NO_ALARM") field(FRSV, "MAJOR") field(TESV, "INVALID") field(ZRST, "RUNNING") field(FRST, "NOT_RUNNING") field(TEST, "Dead") field(FLNK, "SPEARMON:BOORFCavFB:ALHBPREV") } record(ai, "SPEARMON:BOORFCavFB:ALHBPREV") { field(INP, "SPEARMON:BOORFCavFB:ALHBCURR NPP NMS") } # checks an incrementor PV to see if it's incrementing. # the incrementors are updated by ioc processes. # this will be 0 if old = current (i.e. not incrementing) # ======================================================= # A has current, B has previous record(calcout, "SPEARMON:PicoHarp01:SCAN") { field(CALC, "A=B?0:A+1") field(SCAN, "1 second") field(INPA, "SPEARMON:PicoHarp01:SCAN.VAL") field(INPB, "SPEARMON:PicoHarp01CountDelay") field(OUT, "SPEARMON:PicoHarp01:ALHBCURR.VAL PP") field(DOPT, "Use CALC") field(OOPT, "Transition To Zero") field(PINI, "YES") } record(ai, "SPEARMON:PicoHarp01:ALHBCURR") { field(INP, "SPEARMON:PicoHarp01Count NPP MS") field(SCAN, "Passive") field(FLNK, "SPEARMON:PicoHarp01:ALHBCHK") } # scondam: 20-Sept-2018: # If the Heartbeat "Count" PV status is INVALID, ioc may be Dead. # Or if "Count" just not updating, ioc may be too slow or Dead. # else ioc is alive and heartbeat updating, everything OK. record(calcout, "SPEARMON:PicoHarp01:ALHBCHK") { field(CALC, "(C>2)?10:(A=B)?10:0") field(INPA, "SPEARMON:PicoHarp01:ALHBCURR NPP MS") field(INPB, "SPEARMON:PicoHarp01:ALHBPREV.VAL NPP MS") field(INPC, "SPEARMON:PicoHarp01:ALHBCURR.SEVR") field(OUT, "SPEARMON:PicoHarp01AlarmStatus.VAL PP") field(OOPT, "On Change") field(FLNK, "SPEARMON:PicoHarp01:ALHBERR") field(PINI, "YES") } # MS will cause this to be invalid if the HBCHK is record(mbbi, "SPEARMON:PicoHarp01:ALHBERR") { field(DESC, "PicoHarp Monitor monitoring") field(INP, "SPEARMON:PicoHarp01:ALHBCHK.VAL NPP MS") field(ZRSV, "NO_ALARM") field(FRSV, "MAJOR") field(TESV, "INVALID") field(ZRST, "RUNNING") field(FRST, "NOT_RUNNING") field(TEST, "Dead") field(FLNK, "SPEARMON:PicoHarp01:ALHBPREV") } record(ai, "SPEARMON:PicoHarp01:ALHBPREV") { field(INP, "SPEARMON:PicoHarp01:ALHBCURR NPP NMS") }