#================================== #---------------------------------- # res_temp.template: # # Records for single temperature. # For interlocked temps, use in # conjunction with # res_temp_lims.template # res_intlk_common.template # Largely ported from JLab # G. Lahti's software. PT100 RTD #---------------------------------- # Note--optional macro units can # be set to use DegC instead of K # To do so, set UNITS macro to non-zero # value #================================== #================================== # #================================== record(ai, "$(PREF,recursive)$(SIG,recursive)_OFF") { field(DESC, "Temperature offset") field(VAL, "0") field(EGU, "K") field(PINI, "YES") info(autosaveFields, "VAL") } # Integer readback for leep interface. # Intended for internal use only. record(longin, "$(PREF,recursive)$(SIG,recursive)_REG_V_") { field(DESC, "Raw $(SIG,recursive) RTD voltage") field(DTYP, "FEED Register Read") field(INP , "@name=$(NAME,undefined) reg=$(REG,recursive)_$(INDXB,recursive)") info(feed:info:input, "$(PREF,recursive)$(SIG,recursive)_REG_V_") } record(ai, "$(PREF,recursive)$(SIG,recursive)_V") { field(DESC, "$(SIG,recursive) RTD voltage") field(DTYP, "FEED Register Read") field(SCAN, "1 second") field(EGU, "V") field(ASLO, "5.3e-08") field(PREC, "4") field(LOLO, "0") field(LLSV, "MAJOR") field(HIHI, "0.416") field(HHSV, "MAJOR") field(INP , "@name=$(NAME,undefined) reg=$(REG,recursive)_$(INDXB,recursive)") info(feed:info:setting, "$(PREF,recursive)$(SIG,recursive)_V") field(FLNK, "$(PREF,recursive)$(SIG,recursive)_CALC") } record(sub,"$(PREF,recursive)$(SIG,recursive)_CALC") { field(DESC, "Calc $(SIG,recursive) temp") field(INAM, "INTres2tmpInit") field(SNAM, "INTres2tmpProc") field(SCAN, "1 second") # A: voltage readback field(INPA, "$(PREF,recursive)$(SIG,recursive)_V MSI") # B: excitation current readback field(INPB, "$(PREF,recursive)$(SIG,recursive)_I_RBV MSI") # C: optional temperature offset added to result in K field(INPC, "$(PREF,recursive)$(SIG,recursive)_OFF MSI") # D: 0 if desired units is K (default) # any other value for DegC field(INPD, "0") field(EGU, "K") field(HOPR, "0") field(LOPR, "0") field(HIHI, "0") field(LOLO, "0") field(HIGH, "0") field(LOW, "0") field(PREC, "3") field(LLSV, "NO_ALARM") field(LSV, "NO_ALARM") field(HSV, "NO_ALARM") field(HHSV, "NO_ALARM") field(HYST, "0") field(ADEL, "0") field(MDEL, "0") field(BRSV, "INVALID") field(FLNK, "$(PREF,recursive)$(SIG,recursive)") } record(ai, "$(PREF,recursive)$(SIG,recursive)") { field(DESC, "Interlock live reading") field(VAL, "0") field(INP, "$(PREF,recursive)$(SIG,recursive)_CALC MS") field(EGU, "K") field(PREC, "1") field(PINI, "YES") } # TODO: if excitation current should be fixed # set closed_loop/DOL and remove autosave record(ao, "$(PREF,recursive)$(SIG,recursive)_I") { field(DESC, "$(SIG,recursive) RTD excitation") field(DTYP, "FEED Register Write") field(EGU, "mA") field(ASLO, "7.62939453125e-05") field(PREC, "2") field(OMSL, "supervisory") field(VAL, "1.0") field(DRVL, "0") field(DRVH, "4.99") field(PINI, "YES") field(OUT , "@name=$(NAME,undefined) reg=ilock_dsp_excite_current_$(INDXA,recursive)_$(INDXB,recursive)") info(feed:info:setting, "$(PREF,recursive)$(SIG,recursive)_I") info(autosaveFields, "VAL") } record(ai, "$(PREF,recursive)$(SIG,recursive)_I_RBV") { field(DESC, "$(SIG,recursive) RTD excitation readback") field(DTYP, "FEED Register Read") field(SCAN, "1 second") field(EGU, "mA") field(ASLO, "7.62939453125e-05") field(PREC, "2") field(INP , "@name=$(NAME,undefined) reg=ilock_dsp_excite_current_$(INDXA,recursive)_$(INDXB,recursive)") info(feed:info:setting, "$(PREF,recursive)$(SIG,recursive)_I_RBV") } #================================== #---------------------------------- # res_temp_lims.template: # # Threshold records for single # temperature interlock. #---------------------------------- #================================== #================================== # #================================== # Init settings for single temp interlock # Processed by external database; # for LCLS-II: intlkCavCommon.template record(fanout, "$(PREF,recursive)$(SIG,recursive)_INIT1_") { field(DESC, "Init settings") field(SELM, "All") field(LNK1, "$(PREF,recursive)$(SIG,recursive)_I") field(LNK2, "$(PREF,recursive)$(SIG,recursive)_BYP") field(LNK3, "$(PREF,recursive)$(SIG,recursive)_LLIM_V") field(LNK4, "$(PREF,recursive)$(SIG,recursive)_HLIM_V") } record(ao, "$(PREF,recursive)$(SIG,recursive)_LLIM_V") { field(DESC, "$(SIG,recursive) RTD lower thres") field(DTYP, "FEED Register Write") field(EGU, "V") field(ASLO, "5.3e-08") field(PREC, "4") field(DRVL, "0") field(DRVH, "0.416") field(PINI, "YES") field(OUT , "@name=$(NAME,undefined) reg=$(LIMREG,recursive)_lo_limit_$(INDXB,recursive)") info(feed:info:setting, "$(PREF,recursive)$(SIG,recursive)_LLIM_V") info(autosaveFields, "VAL") } record(ai, "$(PREF,recursive)$(SIG,recursive)_LLIM_V_RBV") { field(DESC, "$(SIG,recursive) RTD lower lim") field(DTYP, "FEED Register Read") field(SCAN, "1 second") field(EGU, "V") field(ASLO, "5.3e-08") field(PREC, "4") field(INP , "@name=$(NAME,undefined) reg=$(LIMREG,recursive)_lo_limit_$(INDXB,recursive)") info(feed:info:setting, "$(PREF,recursive)$(SIG,recursive)_LLIM_V_RBV") } record(ao, "$(PREF,recursive)$(SIG,recursive)_HLIM_V") { field(DESC, "$(SIG,recursive) RTD upper thres") field(DTYP, "FEED Register Write") field(EGU, "V") field(ASLO, "5.3e-08") field(PREC, "4") field(DRVL, "0") field(DRVH, "0.416") field(PINI, "YES") field(OUT , "@name=$(NAME,undefined) reg=$(LIMREG,recursive)_limit_$(INDXB,recursive)") info(feed:info:setting, "$(PREF,recursive)$(SIG,recursive)_HLIM_V") info(autosaveFields, "VAL") } record(ai, "$(PREF,recursive)$(SIG,recursive)_HLIM_V_RBV") { field(DESC, "$(SIG,recursive) RTD upper lim") field(DTYP, "FEED Register Read") field(SCAN, "1 second") field(EGU, "V") field(ASLO, "5.3e-08") field(PREC, "4") field(INP , "@name=$(NAME,undefined) reg=$(LIMREG,recursive)_limit_$(INDXB,recursive)") info(feed:info:setting, "$(PREF,recursive)$(SIG,recursive)_HLIM_V_RBV") } #================================== #---------------------------------- # res_intlk_common.template: # # Resonance/interlock chassis. # Records used by each interlock. # Instantiate one per signal. #---------------------------------- #================================== #================================== # #================================== record(bo, "$(PREF,recursive)$(SIG,recursive)_BYP") { field(DESC, "Interlock bypass") field(ZNAM, "Not Bypassed") field(ONAM, "Bypassed") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") field(VAL, "0") field(PINI, "YES") field(OUT, "$(CHAS,recursive)$(FLT,recursive)_BYP.B$(BYPBIT,recursive) PP") info(autosaveFields,"VAL") } record(bi, "$(PREF,recursive)$(SIG,recursive)_BYP_RBV") { field(DESC, "Interlock bypass status") field(SCAN, "1 second") field(ZNAM, "Not Bypassed") field(ONAM, "Bypassed") field(ZSV, "NO_ALARM") field(OSV, "MINOR") field(INP, "$(CHAS,recursive)$(FLT,recursive)_BYP_RBV.B$(BYPBIT,recursive) MS") } record(bi, "$(PREF,recursive)$(SIG,recursive)_FLT") { field(DESC, "Interlock status") field(SCAN, "1 second") field(ZNAM, "Ok") field(ONAM, "Fault") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") field(INP, "$(CHAS,recursive)$(FLT,recursive)_FLT.B$(FLTBIT,recursive) MS") } record(bi, "$(PREF,recursive)$(SIG,recursive)_LTCH") { field(DESC, "Interlock latched status") field(SCAN, "1 second") field(ZNAM, "Ok") field(ONAM, "Fault") field(ZSV, "NO_ALARM") field(OSV, "MAJOR") field(INP, "$(CHAS,recursive)$(FLT,recursive)_FLT.B$(LTCHBIT,recursive) MS") } # Performed initial testing. Uncomment until # more thorough testing and integrate with upper level # controls #record(bo, "$(PREF,recursive)$(SIG,recursive)_RESET") { # field(DESC, "Interlock reset") # field(ONAM, "Reset") # field(PINI, "NO") # field(OUT, "$(CHAS,recursive)$(FLT,recursive)_RESET.B$(RESETBIT,recursive) PP") #}