#================================== #---------------------------------- # cavPhasePipIi.template: # # Cavity phase control for a single # cavity. Initial version based on # LCLS workflow. # # Conventions: # # Firmware phase setpoint is # PDES - phase offsets # # Phase offsets: # # PREF: 'gold' offset, used to # adjust raw PDES so that a PDES # of 0 corresponds to maximum # energy gain. Change of PREF # does not trigger a phase change. # User must then process PDES. # # PTOF: time-of-flight offset, used to # adjust raw PDES to compensate # for beam time-of-arrival changes, # presumed to be due to bunch # compressor path length changes. # Change of PTOF does trigger a # phase change # # POFF1: 'other' offset, placeholder # phase offset. # Change of POFF1 does trigger a # phase change # # POFFSUM = PREF + PTOF + POFF1 # It is subtracted from PDES # and added to the raw phase readback # # Note--observed sign flip and 90 # degree phase shift compensated # for in PDESCALC # # Macros: # # PREF - cavity name # NAME - chassis FEED name # BIT - RFS zone, 0 or 1 #---------------------------------- #================================== #================================== # On reconnect, push phase setpoint # to firmware #================================== record(longin, "$(PREF)PHASINIT1_") { field(DTYP, "FEED On Connect") field(INP , "@name=$(NAME)") field(SCAN, "I/O Intr") field(PHAS, "0") field(FLNK, "$(PREF)PHASINIT2_") } record(fanout, "$(PREF)PHASINIT2_") { field(LNK1, "$(PREF)PDES") } #================================== # On boot, process phase offsets # and settings in order #================================== record(fanout, "$(PREF)PHASINIT_") { field(PINI, "YES") field(LNK1, "$(PREF)PREF") field(LNK2, "$(PREF)PTOF") field(LNK3, "$(PREF)POFF1") # PTOF/POFF1 process PDES } #================================== # Set cavity phase # Based on new phase setting, # calculate new limits for PACTMEAN and push # Default alarm limits +/- .01 degree # based on LCLS2 SSA/LLRF PRD #================================== record(bo, "$(PREF)GOLD_PDES") { field(DESC, "Zero PDES and update PREF") field(ZNAM, "Gold PDES") field(ONAM, "Gold PDES") field(FLNK, "$(PREF)GOLD_PDES1_") field(PINI, "NO") } record(calcout, "$(PREF)GOLD_PDES1_") { field(DESC, "Internal step in PDES golding") field(CALC, "A-B") field(INPA, "$(PREF)PREF NPP") field(INPB, "$(PREF)PDES NPP") field(OOPT, "Every Time") field(OUT, "$(PREF)PREF PP") field(FLNK, "$(PREF)GOLD_PDES2_") field(ASG, "READONLY") } record(ao, "$(PREF)GOLD_PDES2_") { field(DESC, "Internal step in PDES golding") field(OMSL, "closed_loop") field(VAL, "0") field(DOL, "0") field(OUT, "$(PREF)PDES PP") field(ASG, "READONLY") } record(ao, "$(PREF)PREF") { field(DESC, "Gold phase offset") field(OMSL, "supervisory") field(VAL, "0") field(EGU, "degrees") info(autosaveFields, "VAL") } record(ao, "$(PREF)PTOF") { field(DESC, "Time-of-flight phase offset") field(OMSL, "supervisory") field(VAL, "0") field(EGU, "degrees") field(FLNK, "$(PREF)PDES") info(autosaveFields, "VAL") } record(ao, "$(PREF)POFF1") { field(DESC, "Phase offset other") field(OMSL, "supervisory") field(VAL, "0") field(EGU, "degrees") field(DRVL, "-180") field(DRVH, "180") field(LOPR, "-180") field(HOPR, "180") field(FLNK, "$(PREF)PDES") info(autosaveFields, "VAL") } # Dummy PV to allow python API to access actual PV record(longout, "$(PREF)PDESDMY") { field(DTYP, "FEED Register Write") field(OUT , "@name=$(NAME) reg=mbox_$(BIT)_PDES") info(feed:info:input, "$(PREF)PDES") info(feed:info:output, "$(PREF)PDES") } record(ao, "$(PREF)PDES") { field(DESC, "Phase setpoint") field(OMSL, "supervisory") field(VAL, "0") field(EGU, "degrees") field(LOLO, "-180") field(HIHI, "180") field(LLSV, "MINOR") field(HHSV, "MINOR") field(DRVL, "-180") field(DRVH, "180") field(LOPR, "-180") field(HOPR, "180") field(PREC, "1") field(FLNK, "$(PREF)POFFSUM") info(feed:info:setting, "$(PREF)PDES") info(autosaveFields, "VAL") } # PREF is not used until PDES # is processed, so at that time # also push POFFSUM TO PACTMEAN calc record(calcout, "$(PREF)POFFSUM") { field(DESC, "Push offsets to phase readback") field(CALC, "A+B+C") field(INPA, "$(PREF)PREF") field(INPB, "$(PREF)PTOF") field(INPC, "$(PREF)POFF1") field(OOPT, "Every Time") # Use CA link to reduce lockset field(OUT, "$(PREF)CAV:ZRANGLE CA") field(FLNK, "$(PREF)PDESCALC") } record(calc, "$(PREF)PDESCALC") { field(DESC, "Calc internal PDES") field(CALC, "B*(A-C-D)") field(INPA, "$(PREF)PDES") # Compensate for observed sign flip field(INPB, "-1") # Compensate for observed 90 degree offset field(INPC, "90") field(INPD, "$(PREF)POFFSUM") field(PREC, "1") field(EGU, "degrees") field(FLNK, "$(PREF)PDES_") } # Firmware handles phase wrapping record(ao, "$(PREF)PDES_") { field(DESC, "Internal PDES, do not use") field(DTYP, "FEED Register Write") field(OMSL, "closed_loop") field(DOL, "$(PREF)PDESCALC MS") field(VAL, "0") field(LOPR, "-180") field(HOPR, "180") field(EGU, "degrees") field(PREC, "1") # ASLO = 360/2^18 field(ASLO, "0.001373291") field(OUT , "@name=$(NAME) reg=shell_$(BIT)_dsp_fdbk_core_mp_proc_setmp_1 wait=false") } record(longin, "$(PREF)REGPDES_RBV") { field(DESC, "Phase setpoint raw readback") field(DTYP, "FEED Register Read") field(SCAN, "1 second") field(INP , "@name=$(NAME) reg=shell_$(BIT)_dsp_fdbk_core_mp_proc_setmp_1") field(TSE , "-2") field(FLNK, "$(PREF)PDES_RBV") info(feed:info:input, "$(PREF)REGPDES_RBV") } record(calc, "$(PREF)PDES_RBV") { field(DESC, "Phase setpoint readback") field(CALC, "$(PDESRBVCALC=(C*D*A)+B)") field(INPA, "$(PREF)REGPDES_RBV") # Compensate for observed 90 degree offset field(INPB, "$(PDESRBVINPB=90)") # Compensate for observed sign flip field(INPC, "$(PDESRBVINPC=-1)") field(INPD, "$(PREF)PDES_.ASLO") field(INPE, "$(PDESRBVINPE=)") field(INPF, "$(PDESRBVINPF=)") field(PREC, "1") } record(calcout, "$(PREF)PACTMEANACALC") { field(DESC, "Calc PACTMEAN alarm values") field(CALC, "A+B") field(OCAL, "A-B") # Use CA link to reduce lockset field(INPA, "$(PREF)PDES CP") field(INPB, "$(PREF)PACTMEANATHRESH NPP") field(OOPT, "Every Time") field(DOPT, "Use OCAL") field(PREC, "3") field(FLNK, "$(PREF)PACTMEANWCALC") } record(ai, "$(PREF)PACTMEANATHRESH") { field(DESC, "PACTMEAN alarm threshold") field(VAL, ".01") field(PREC, "3") field(EGU, "degrees") field(PINI, "YES") field(FLNK, "$(PREF)PACTMEANACALC") info(autosaveFields, "VAL") } record(calcout, "$(PREF)PACTMEANWCALC") { field(DESC, "Calc PACTMEAN warning values") field(CALC, "A+B") field(OCAL, "A-B") field(INPA, "$(PREF)PACTMEANACALC.A") field(INPB, "$(PREF)PACTMEANWTHRESH NPP") field(OOPT, "Every Time") field(DOPT, "Use OCAL") field(PREC, "3") field(FLNK, "$(PREF)PACTMEANASEQ") } record(ai, "$(PREF)PACTMEANWTHRESH") { field(DESC, "PACTMEAN warning threshold") field(VAL, ".005") field(PREC, "3") field(EGU, "degrees") field(PINI, "YES") field(FLNK, "$(PREF)PACTMEANACALC") info(autosaveFields, "VAL") } # Use CA link to reduce lockset record(seq, "$(PREF)PACTMEANASEQ") { field(DESC, "Push new lims to PACTMEAN") field(SELM, "All") field(DOL1, "$(PREF)PACTMEANACALC") field(LNK1, "$(PREF)PACTMEAN.HIHI CA") field(DOL2, "$(PREF)PACTMEANACALC.OVAL") field(LNK2, "$(PREF)PACTMEAN.LOLO CA") field(DOL3, "$(PREF)PACTMEANWCALC") field(LNK3, "$(PREF)PACTMEAN.HIGH CA") field(DOL4, "$(PREF)PACTMEANWCALC.OVAL") field(LNK4, "$(PREF)PACTMEAN.LOW CA") } #================================== # Phase readback #================================== record(ai, "$(PREF)PACTMEAN") { field(DESC, "Cavity phase readback") field(INP, "$(PREF)CAV:PMEAN MS CP") field(EGU, "degrees") field(LOPR, "-200") field(HOPR, "200") field(PREC, "1") field(LLSV, "MAJOR") field(LSV, "MINOR") field(HSV, "MINOR") field(HHSV, "MAJOR") field(TSEL, "$(PREF)CAV:PMEAN.TIME CA") field(FLNK, "$(PREF)PACTMEANRAW") } record(calc, "$(PREF)PACTMEANRAW") { field(DESC, "Cavity phase readback") field(CALC, "A-B") field(INPA, "$(PREF)PACTMEAN MSI") field(INPB, "$(PREF)POFFSUM") field(LOPR, "-200") field(HOPR, "200") field(PREC, "1") field(EGU, "degrees") field(TSEL, "$(PREF)CAV:PMEAN.TIME CA") }