#	IPMI module README 
#
#	Auth: Sonya Hoobler
#
#	Last updated: 16 May 2013
#
############################################################

To add MicroTCA IPMI support to your application:

1. Add to configure/RELEASE:

IPMICOMM_MODULE_VERSION=ipmiComm-R*-*-*
IPMICOMM=$(EPICS_MODULES)/ipmiComm/$(IPMICOMM_MODULE_VERSION)

2. Add to src/Makefile

IOCManager_DBD  += ipmiComm.dbd
IOCManager_LIBS += ipmiComm

3. Add to Db/Makefile

DB_INSTALLS += $(IPMICOMM)/db/shelf.db
DB_INSTALLS += $(IPMICOMM)/db/module.db
DB_INSTALLS += $(IPMICOMM)/db/sensor_temp.db
DB_INSTALLS += $(IPMICOMM)/db/sensor_fan.db
DB_INSTALLS += $(IPMICOMM)/db/sensor_hotswap_vt.db
DB_INSTALLS += $(IPMICOMM)/db/sensor_hotswap_nat.db
DB_INSTALLS += $(IPMICOMM)/db/sensor_voltage.db
DB_INSTALLS += $(IPMICOMM)/db/sensor_current.db

4. Add these lines to st.cmd for each MCH/shelf before iocInit. *Order is important*

Example for mch-b34-cd38:

drvAsynIPPortConfigure ("mch-b34-cd38","mch-b34-cd38:623 udp",0,0,0)
mchInit("mch-b34-cd38")
< st.mch-b34-cd38.cmd


NOTES ON THIS RELEASE
---------------------------

(below, 'ioc' refers to the managment ioc using ipmiComm to communicate 
 with a remote crate. at LCLS, this ioc is a soft ioc called IOCManager.)

-This release supports NAT and Vadatech MCHs

-During ioc boot, the ioc will discover which modules/sensors exist
 for each carrier defined in st.cmd. It will then build a script to 
 load EPICS records for what has been discovered. The script is saved
 to the ioc's data directory. The script is not in CVS. Any carriers
 that are offline during ioc boot will not have scripts created for them
 and thus, no PVs will be loaded for them.

-There is a EPICS PV $(crat):INIT for each crate. It is set to "Initialized"
 after all of the modules/sensors have been discovered. It is set to "Not
 initialized" if the software detects that the system has gone offline and 
 come back up in a different configuration. This is because sensor addresses 
 can change when new hardware is removed or reinstalled and we cannot be sure 
 we are correctly addressing the sensors when the system comes back up. Later,
 we will handle this better. Until then, if INIT = "Not initialized", the ioc 
 must be rebooted in order to re-discover the modules/sensors and resume 
 system monitoring.

-No alarm limits or severities have been implemented.