  <para>
   All labCA calls take a PV argument identifying the EPICS process
   variables the user wants to connect to. PVs are plain ASCII strings.
   labCA is capable of handling multiple PVs in a single call; they are
   simply passed as a column vector:
  </para>
  <programlisting role="example"><![CDATA[
pvs = [ 'PVa'; 'b'; 'anotherone' ]
  ]]></programlisting>
   <para>
   Because matlab doesn't allow the rows of a string vector to be of
   different size, the matlab wrapper expects a cell- array of strings:
   </para>
  <programlisting role="example"><![CDATA[
pvs = { 'PVa'; 'b'; 'anotherone' }
  ]]></programlisting>
   <para>
   All channel access activities for the PVs passed to a single labCA call
   are batched together and completion of the batch is awaited before
   returning from the labCA call. Consider the following example:
  </para>
  <note>
  <para>
          In matlab, the square brackets (``[]'') must be replaced by
          curly braces (``{}'').
  </para>
  </note>
  <programlisting role="example"><![CDATA[
       lcaPut( 'trigger', 1 )
data = lcaGet( ['sensor1' ; 'sens2'] );
  ]]></programlisting>
  <itemizedlist>
  <listitem>
     <para>
     It is guaranteed that writing the ``trigger'' completes (on the CA
     server) prior to reading the sensors.
     </para>
     <note>
     <para>
          If the remote sensors have finite processing time, the
          subsequent CA read may still get old data -- depending on the
          device support etc.; this is beyond the scope of channel access,
          however.
     </para>
     </note>
  </listitem>
  <listitem>
     <para>
     Reading the two sensors is done in ``parallel'' -- the exact order
     is unspecified. After the command sequence (successfully)
     completes, all the data are valid.
     </para>
  </listitem>
  </itemizedlist>
  </refsection>

  <refsection xml:id='lca_common_type_arg'>
  <title>Data Type Argument ('type')</title>
  <para>
  (optional argument) A string specifying the data type to be used for the
  channel access data transfer.
  </para>
  <note>
  <para>
  Unless the PVs are of native 'string' type or conversion to 'string'
  is enforced explicitly (type = <emphasis>'char'</emphasis>),
  labCA always converts the data to <emphasis>'double'</emphasis> locally.
  </para>
  </note> 
  <para>
  It can be desirable, however, to use a different data type for the transfer
  because by default CA transfers are limited to ~ 16kB.
  Legal values for type are
  </para>
  <itemizedlist>
  <listitem><para>  <emphasis>'byte'   </emphasis> </para></listitem>
  <listitem><para>  <emphasis>'short'  </emphasis> </para></listitem>
  <listitem><para>  <emphasis>'long'   </emphasis> </para></listitem>
  <listitem><para>  <emphasis>'float'  </emphasis> </para></listitem>
  <listitem><para>  <emphasis>'double' </emphasis> </para></listitem>
  <listitem><para>  <emphasis>'native' </emphasis> </para></listitem>
  <listitem><para>  <emphasis>'char'   </emphasis>(strings) </para></listitem>
  </itemizedlist>
  <para>
  There should rarely be a need for using anything other than
  <emphasis>'native'</emphasis>, the default, which directs CA to use
  the same type for transfer as the data are stored on the server.
  </para>
  <para>
  Occasionally, conversion to <emphasis>'char'</emphasis> can be useful:
  retrieve a number of PVs as strings, i.e. let the CA server convert them
  to strings (if the PVs are not native strings already) and transfer them.
  </para>
  <para>
  If multiple PVs are requested, either none or all must be of native
  DBF_STRING or DBF_ENUM type unless explicit conversion to
  <emphasis>'char'</emphasis> is enforced by specifying this argument.
  </para>
  <note>
  <para>
  While <emphasis>'native'</emphasis> might result in different types
  being used for different PVs, it is currently not possible to
  explicitly request different types for individual PVs (i.e.
  type can't be a vector).
  </para>
  </note>
  </refsection>

  <refsection xml:id='lca_common_timestamp_val'>
  <title>Timestamp Format</title>
  <para>
   Channel access timestamps are ``POSIX struct timespec'' compliant, i.e.
   they provide the number of nanoseconds expired since 00:00:00 UTC,
   January 1, 1970. labCA translates the timestamps into complex numbers
   with the seconds (tv_sec member) and nanoseconds (tv_nsec) in the real
   and imaginary parts, respectively. This makes it easy to extract the
   seconds while still maintaining full accuracy.
  </para>
  </refsection>

  <refsection xml:id='lca_common_nan_val'>
  <title>NaN Values</title>
  <para>
  Actually, all fields of an EPICS database record share a common
  severity, (which itself is a field/PV -- the .SEVR field).
  However, the INVALID status actually only applies to the .VAL
  field of a record -- other fields (e.g. .EGU) may still hold
  meaningful data. Consequently, INVALID PVs are returned as NaN
  only if they refer to a record's .VAL field.
  </para>
  </refsection>