[SLAC Controls Software Group [SLAC Controls Department] [SLAC Home Page]

Go to bottom of page



16.1 MODULE SPECIFICATIONS . . . . . . . . . . . . . 16-1

16.1.1 Module Width . . . . . . . . . . . . . . . . . 16-1

16.1.2 Number of Input Channels . . . . . . . . . . . 16-1

16.1.3 Input Levels . . . . . . . . . . . . . . . . . 16-1

16.1.4 Input . . . . . . . . . . . . . . . . . . . . 16-1

16.1.5 Latching . . . . . . . . . . . . . . . . . . . 16-2

16.1.6 Response Time: . . . . . . . . . . . . . . . . 16-2

16.1.7 CAMAC Codes, X and Q Responses . . . . . . . . 16-2

16.1.8 CAMAC Speed . . . . . . . . . . . . . . . . . 16-2

16.1.9 Power Required . . . . . . . . . . . . . . . . 16-3

16.1.10 Protection . . . . . . . . . . . . . . . . . . 16-3

16.1.11 Operating Temperature Range . . . . . . . . . 16-3

16.2 FRONT PANEL . . . . . . . . . . . . . . . . . . 16-3

16.2.1 Front Panel Indicators . . . . . . . . . . . . 16-3

16.2.2 Front Panel Connectors . . . . . . . . . . . . 16-3

16.3 DRAWING PACKAGE NUMBER . . . . . . . . . . . . . 16-4

16.4 RESPONSIBLE ENGINEER . . . . . . . . . . . . . . 16-4 CHAPTER 16 ISOLATED DIGITAL INPUT MODULE (IDIM) This unit is designed as a general purpose digital input module. Each input is opto-isolated and is designed to operate over a wide range of positive input voltages. The unit is nonlatching, each CAMAC Read of this unit presenting the data as seen at the inputs at the time of the Read command.

16.1 MODULE SPECIFICATIONS

16.1.1 Module Width Single.

16.1.2 Number of Input Channels 32, (numbered 0 through 31).

16.1.3 Input Levels o "0" = -30 through +1 volts, o "1" = +3 through +30 volts. o (Undefined from +1 volt to +3 volts.)

16.1.4 Input Optically isolated with current drawn not to exceed 10 milliAmps at 30 volts in. ______________________________ This chapter is excerpted from TN-83-01.


ISOLATED DIGITAL INPUT MODULE (IDIM) Page 16-2

16.1.5 Latching All inputs nonlatching. During a CAMAC read cycle the data is held.

16.1.6 Response Time: 100 microseconds maximum from input to Dataway.

16.1.7 CAMAC Codes, X and Q Responses

16.1.7.1 Read Functions - o F0 A0 reads J1 inputs, R1 = Channel 0 X=1, Q=1 if J1-C9 > 12 volts. o F0 A1 reads J2 inputs, R1 = Channel 16 X=1, Q=1 if J2-C9 > 12 volts.

16.1.7.2 Write Functions - None.

16.1.7.3 Command Functions - None.

16.1.7.4 Other X and Q Responses - X=Q=0 for all other codes and conditions.

16.1.7.5 C, Z, and I: - C, Z, and I have no effect on this module.

16.1.8 CAMAC Speed This module will respond to all CAMAC cycles as defined in IEEE Standard 583-1978.


ISOLATED DIGITAL INPUT MODULE (IDIM) Page 16-3

16.1.9 Power Required o +6 volts, 500 milliAmps typical, 700 milliAmps maximum; o +24 volts, 2-170 milliAmps, dependent upon J1&J2-C9 loading.

16.1.10 Protection o Inputs will withstand +/- 30 volts indefinitely, and +/- volts for one (1) second without damage. o The +6 and +24 volt lines are each protected with a fuse consisting of a single strand of #36 tinned copper wire. Fusing current is about 3.5 Amps.

16.1.11 Operating Temperature Range 10 to 65 degrees Celsius.

16.2 FRONT PANEL

16.2.1 Front Panel Indicators "N" and "X", red LED's, "Q" and "V", green LED's. ("V" lighted indicates both J1&J2-C9 > 12 volts.)

16.2.2 Front Panel Connectors 2 each, AMP P/N 204731-1. Pin assignments as follows: CHAN SIGNAL RETURN || OTHER SIGNALS # || CONNECTION / FUNCTION || 00 J1-A1 J1-A2 || 01 1-A3 A-A4 || J1-C9 +24 Volts out 02 1-A5 1-A6 || (see note) 03 1-A7 1-A8 || J1-C10 Ground 04 1-A9 1-A10 || 05 1-A11 1-A12 || J1-C11 N C 06 1-B1 1-B2 || 07 1-B3 1-B4 || J1-C12 Ground 08 1-B5 1-B6 ||


ISOLATED DIGITAL INPUT MODULE (IDIM) Page 16-4 09 1-B7 1-B8 || 10 1-B9 1-B10 || 11 1-B11 1-B12 || 12 1-C1 1-C2 || J2-C9 +24 Volts out 13 1-C3 1-C4 || (see note) 14 1-C5 1-C6 || J2-C10 Ground 15 J1-C7 J1-C8 || 16 J2-A1 J2-A2 || J2-C11 N C 17 1-A3 1-A4 || 18 1-A5 1-A6 || J2-C12 Ground 19 1-A7 1-A8 || 20 1-A9 1-A10 || 21 1-A11 1-A12 || 22 1-B1 1-B2 || NOTE: J1&J2-C9 are 23 1-B3 1-B4 || connected to the 24 1-B5 1-B6 || fused +24 volts 25 1-B7 1-B8 || thru independent 26 1-B9 1-B10 || 100 Ohm, 10 Watt 27 1-B11 1-B12 || resistor strings. 28 1-C1 1-C2 || 29 1-C3 1-C4 || 30 1-C5 1-C6 || 31 J2-C7 J2-C8 ||

16.3 DRAWING PACKAGE NUMBER 135-562 TN-83-01.

16.4 RESPONSIBLE ENGINEER John Kieffer


 
Go to top of page
Contact (until Aug. 15, 1996): Jeffrey Miller
Owner: Bob Sass

Converted from VAX Runoff output using doc2webset.pl