From: Luchini, Kristi Sent: Friday, June 02, 2006 6:09 PM To: MacNair, Dave Cc: Lahey, Terri E. Subject: RE: EPSC RS-232 Adapter Hi Dave and Terri, I want to confirm the additional settings for the terminal server. Is this correct? 115200 Baud Rate 8 data bits 1 stop bit No parity No hardware flow control in No hardware flow control out - Thanks, Kristi -----Original Message----- From: MacNair, Dave Sent: Thursday, June 01, 2006 11:07 AM To: Harms, Michael JJ Cc: Luchini, Kristi Subject: EPSC RS-232 Adapter Mike I did have to reverse the RX/TX and RTS/CTS lines in the adapter. For future reference, the correct connections are as follows; Octopus RJ45 EPSC 9 Pin D EPSC 15 Pin D CTS PIN 1 PIN 6 RTS PIN 10 DSR PIN 2 NC NC RX PIN 3 PIN 2 TX PIN 9 COM PIN 4 PIN 5 GND PIN 5 COM PIN 5 PIN 5 GND PIN 5 TX PIN 6 PIN 3 RX PIN 1 DTR PIN 7 NC NC RTS PIN 8 PIN 7 CTS PIN 2 I have included the pinout of the 15 pin connector on the front of the controller in case we want to wire directly from the RJ45 receptacle to the 15 pin jack. Thank you for your help. David MacNair