PEP-II LLRF Tuner Inputs &Constants Panel
Overview
This panel contains the various constants necessary to define the operation
of the tuner loop, including phase offsets, gains, tuner polynomial
coefficients, deadband and forgetting factor.
This panel is accessed using the "Inp&Consts" button
about half down the Tuners panel in the
column associated with the cavity of interest.
Loading Angle Error Calculation
On the upper right of the panel, the equation for calculating the loading
angle error is listed:
Load Angle Error = Probe Phase - Forward Phase + Loading Angle
Offset
Since the phase length of the RF cables from the forward coupler and the
cavity probe are unknowns, an offset must be determined for each to null
both phases when the cavity is tuned to 476 MHz. Both offsets are
determined during tuner configuration which is part of
station configuration.
A loading angle offset is added to the phase difference to allow the
"Loading Angle Offset" loop (enabled on the
Feedback panel or
Tuners panel) or a fixed constant
offset to be added to the loading angle error calculation. Note that
if the station phase were changed, both the forward phase and the probe
phase would change but the difference would remain constant and the tuner
loop still operates properly.
- Ld Angle Err Limit (Deg) - Sets the magnitude
where the loading angle error value saturates.
A load angle error above 5 degrees will flash the field
yellow,
tuner loop status will be red and display
an error message. The load angle offset (discussed below) will freeze until the error goes below the limit. Nominal value = 0.5 degrees.
- Probe Phase Offset (Deg) - Amount of offset
added to the raw probe phase to form the probe phase. Determined
during tuner configuration.
Can range from -180 to +180 degrees.
- Frwd Phase Offset (Deg) - Amount of offset
added to the raw cavity forward phase to form the forward phase.
Determined during tuner configuration. Can range from -180
to +180 degrees.
Park Frequency Error Calculation
Below the loading angle error calculation is
the park frequency error calculation:
PARK Freq Error = (90/(4*476e3)) * Ql
* (Park Freq - Freq Offset)
This calculation is a linear approximation of the
phase slope through a resonator's 3 dB points. The difference between
the "Desired Park Frequency (kHz)" and the current "Freq Offset (kHz)"
along with the loaded Q allows the calculation of the "Freq Error (Deg)"
which is used to replace the normal loading angle error in the tuner movement
calculation (described below). Note that even if the Ql is not correct
the tuner will continue to move until the tuner polynomial reaches the
"Desired Park Frequency".
- Desired Park Frequency (kHz) - Offset in
kHz from 476 MHz where the cavity will move to in the PARK
state. For each station, half the cavities will be parked at +340
kHz and the other half parked at -340 kHz. This prevents parked cavities
from strongly driving low order coupled bunch modes.
- Loaded Cav Q (Ql) - Loaded cavity Q.
Does not need to be exact since the Park frequency
is in feedback using the tuner polynomials to report the present resonant
frequency. Nominal value = 7000.
Loading Angle Offset Calculation
Below the Park frequency error calculation is
the loading angle offset calculation:
Load Angle Offset = Fx_Offs+(F*(Prev_Offs-(K*(Strength-Setpoint))))
This loop creates a loading angle offset based on
the measured cavity strength (in percent) compared to the setpoint (also
in percent). Cavity strength is simply the fraction of the station
total gap voltage (in percent) produced by the one cavity. This is
an integrating loop which uses the previous value of the offset to calculate
the new value. When the beam current goes below the limit on the
Tuners panel, the RF IOC is unable to
connect to the BIC IOC for beam current status, or the calculation is turned
off on the Tuners panel, the stored
offset value is cleared and must regenerate as beam is injected.
A forgetting factor prevents runaway by pulling the offsets for all the
cavities toward zero. This loop allows running one or more cavities
at different voltages and has proven very useful.
- Fixed Offs (Deg) - Allows user to place
a constant phase offset into the tuner loop for a single cavity.
Intended to be used as a diagnostic but not currently used. Should
be set to zero.
- K (Deg/%) - Gain term for the loading angle
offset loop. Nominal value = 0.5.
- Forgetting Factor (F) - On each iteration
a small faction of the loading angle offset is "forgotten". This
prevents a potential (once observed) runaway condition where all tuners
get offset in the same direction. The addition of this term has solved
this issue. Nominal value = 0.9995.
- Max Offs (Deg) - Limits the maximum loading
angle offset the loop can produce. Should not need to be greater
than 10 degrees but is presently set higher.
Nominal value = 75 degrees.
- Setpoint (%) - Setpoint for the loading
angle offset loop. Determines the percent of the total station gap
voltage a single cavity will contribute (once the "Min Beam Curr" limit
has been reached). For example in a 4-cavity station, each cavity
will normally be set to 25%. If one cavity is prone to RF breakdown
its set point can be reduced to 22% and the remaining three raised to
26%. Important note: The sum of
all the station cavity set points must equal 100%.
- Deadband (%) - Prevents calculation of
new loading angle offset if the strength error is below this value.
Prevents constant tuner motion and decreases mechanical wear. Nominal
value = 0.05.
Delta Position Calculation
Near the bottom right of the panel is the tuner
motor delta position calculation:
Delta Position = Loop Gain * Conv * Error
Based on the error term (which can be either the
"Load Angle Error" or the "PARK Freq Error"), the tuner position movement
in mm is calculated.
- Error Deadband (Deg) - No tuner movement
will be requested if the magnitude of the error is smaller than the "Deadband"
value. This is designed to prevent unnecessary tuner movements to
reduce mechanical wear. Nominal value = 0.25 degrees.
- Max Delta Posn (mm) - Maximum tuner movement
allowed for each loop iteration. Prevents rapid tuner movements.
Nominal value = 1.00 mm.
- Conv (mm/Deg) - Scale factor which converts
tuner loop phase error to desired movement in mm. This factor is
determined during tuner configuration.
Nominal range = 0.020 to 0.030.
- Loop Gain - Loop gain term which allows
changing gain without affecting the measured "Conv" term. Since tuner
movement is completed before the next loop iteration, this term should not
exceed unity. We have always run with unity tuner loop gain.
Nominal value = 1.00.
Frequency Offset (Tuner Polynomial) Calculation
On the left of the panel is the frequency offset calculation:
Freq Offset (kHz) = polynomial(Tuner
Posn - ON Home Posn) + (t1*(Cav Volt**2)) where
polynomial(x) = p0 + p1*(x) + p2*(x**2)
+ p3*(x**3)
The polynomial coefficients are generated using the "make_polynomials.m"
Matlab script which is called by the "Make Polys" button in the invasive
list on the MoreMATLAB EPICS panel. Remember to turn off the direct and
comb RF feedback loops before generating the polynomial coefficients.
A properly generated polynomial should be accurate to 10 kHz.
The philosophy that the polynomial is based on the TUNE/ON
home position allows reusing the old polynomial coefficients even after
changing a tuner assembly or position potentiometer, as long as
tuner configuration is done to relocate
the "TUNE/ON Home" position. Since the invention
of the "Fast Turnon" option, we have realized that the "TUNE/ON Home" position
is set when the cavities are at a medium range gap voltage and is not optimum
for banging the station on to full gap voltage. If one adjusts the
"TUNE/ON Home" position, then the polynomial is no longer valid. The
proper solution would be to either change tuner configuration
to set the "TUNE/ON Home" position at a very low gap voltage or
rewrite the polynomial related EPICS and Matlab code to base the polynomial
on actual position (not relative to "TUNE/ON Home"). I prefer the
first option.
The t1*(Cav Volt**2) term is a simple attempt to correct
for cavity heating effects since thermal power is proportional to the voltage
squared.
- p0 - Constant term
for the tuner polynomial. Nominal range = 10 to 20.
- p1 - First order
term for the tuner polynomial. Nominal range = 20 to 30.
- p2 - Second order
term for the tuner polynomial. Nominal range = 0.4 to 0.6.
- p3 - Third order
term for the tuner polynomial. Nominal range = -0.01 to +0.01.
- t1 - Thermal term
for the frequency offset calculation. Nominal value = -.00010.
- Smoothing Factor (S) - Filters the calculated
"Freq Offset (kHz)" value. Nominal value = 0.5. Smoothing equation:
new value = (1-S)*(input data)+S*(previous value)