SLAC Utilities Overview

 This document is written and maintained by Zoe VanHoover

Please contact Zoe to make comments or corrections.   

 

Contents:

  1. Electrical System
    1. Electrical Power Distribution

      1. Master Substation

      2. Distributed Substations

    2. Variable Voltage Substations (VVSs)

    3. Power Glitches

    4. Brown Out

    5. Site Power Meter

    6. Power Supplies

  2. Water Systems
    1. Cooling Towers

    2. Low Conductivity Water (LCW) Systems

    3. Heat Exchangers

    4. Demineralizers

    5. MAKO Still

    6. Deaerators

    7. Sand Filters

    8. Containment Sumps

    9. Hydrogen Recombiners

    10. PEP Water Systems

    11. Chilled Water Systems

      1. IR2 Chilled Water

      2. Refrigerated Baffle Chilled Water

  3. Compressed Air
  4. Cryogenics
    1. General Cryogenic System

      1. Controls and Diagnostics

      2. System Layout

      3. Helium Gas Storage Tanks

      4. Helium Compressors

      5. Refrigerators

    2. BaBar Cryogenic System

    3. P-Gun Cryogenic System

    4. E158 Hydrogen Target Cryogenic System

  5. Gas Systems
    1. Dry Nitrogen

    2. PLIC Gas

    3. Helium Gas

    4. Argon

    5. Hydrogen Gas

    6. BaBar Detector Gas Systems


 

  1. Electrical System
    1. Electrical Power Distribution

      1. Master Substation

      2.         The master substation is located just south of LINAC sector 30.  At the master substation, grid power is stepped down to 12KV before being transmitted and used on the SLAC site.  The master substation also contains switching equipment used to monitor and control the incoming grid power.  Underground transmission lines carry power from the master substation to each VVS, to each PEP region, and to other distributed substations.

         

      3. Distributed Substations

      4.         At the ends of the 12KV internal power distribution lines, the power must generally be stepped down again to power the devices in the area. The distributed transformers used to do this are located at distributed substations.

         

    2. Variable Voltage Substations (VVSs)

    3.         Each VVS steps down the 12KV power from the master substation to the 600V used by the modulators. Each VVS is located in an even numbered sector, and provides power to the modulators in both its own sector and the previous sector. The output voltage of most VVSs can be ramped up and down. Thus, when the VVS is turned on, the output voltage can be ramped up gradually, causing less of a shock to the VVS’s internal electronics, and to the modulators. The output voltage of the VVS is controlled by varying a second, lower voltage called the reference voltage. The reference voltage is moved from 90 to 120V, in order to move the VVS output voltage from 450V to 600V. Currently VV11 in sector 22 is the only VVS which does not have a variable output voltage. It is being tested to see if any unforeseen difficulties arise when a transformer with stable output voltage is used. It is still referred to as “VV11” in spite of its non-variable output voltage.

       

    4. Power Glitches

    5.         A power glitch can occur due to either on-site power distribution problems, or off-site problems with the power grid. A power glitch is a brief interruption of the power being provided to a large number of electrical devices on site. All electrical devices on site can be affected by some severe power glitches, while other power glitches can affect only a few devices. Generally many devices, including water pumps, air compressors, and power supplies trip off and must be reset following a power glitch. Power glitches can also cause disruption of computer network function. Micros often must be IPLed and/or power cycled, and sometimes network experts must be called to reboot the ALPHA servers, which run the control system.
              When recovering from a power dip, the operations staff must prioritize recovery tasks, and recover systems in a logical order. Immediately following a power dip, an electrician should diagnose the cause of the power dip, and ensure that power has been restored to all necessary buildings. Maintenance mechanics should also be contacted immediately following a power dip. They should first recover the site air compressors. Quick recovery of site air compressors will prevent the loss of the CID search complete status, and will allow actuation of vacuum valves and cryogenic system valves. When the site air compressor is recovered, the maintenance mechanic should begin to recover water pumps that have tripped. Cryotechnicians should be automatically notified of any cryogenic system failure, including those failures that immediately follow a power dip. However, operators should verify that cryotechs are aware of the power dip, and are responding. Meanwhile, operators should assess the status of the control system and, if necessary, contact appropriate experts to help recover the control system. When the control system has been recovered, operators can begin to recover failed CAMAC micros and crates, search any areas that have lost PPS search secured status, clear obstructions (vacuum valves, beam stoppers, and profile monitors) from the beam lines, and recover RF and magnet systems. System recovery is prioritized starting with CID systems, and progressing downstream, so that beams can be turned on in the injector area and can be brought progressively farther downstream as equipment is recovered.
       

    6. Brown Out

    7.         WAPA (Western Area Power Administration) acts as an electrical service coordinator, buying power for SLAC. WAPA communicates directly with the California ISO (Independent System Operator). In the event that WAPA is unable to buy sufficient power to meet SLAC’s electrical demand at a previously agreed upon price, WAPA will contact SLAC to initiate a brown out. WAPA specifies the time and duration of the brown out, as well as the site power level that we must stay below during the brown out. Generally notification of the brown out comes the morning of the brown out. The SLAC contract with WAPA allows WAPA to request an unlimited number of brown outs in the months of July and August, and a limited number of brown outs during the rest of the year. When WAPA requests a brown out, SLAC has the option of “buying out” of the brown out by purchasing power on the open market at higher than normal prices during the specified brown out period. The choice of curtailing power use or buying power at a higher price is made by the Accelerator Plans Office and the Accelerator Operations Group head.
              In addition to WAPA brown outs, SLAC is now participating in a separate brown out program with the California Power Authority (CPA). SLAC receives reduced electrical rates in exchange for participating in a voluntary curtailment program. Each month SLAC specifies an amount of power that can be curtailed. In the event of a CPA brown out, CPA will notify SLAC at 4:00 pm on the day before the brown out. SLAC may not buy out of these brown outs. The site power level that we must not exceed is calculated by averaging SLAC’s peak demand for the last ten days with the highest and lowest demand days thrown out, and then subtracting from that average the previously specified amount of power curtailment for that month.
              A revision of the MCC brownout procedure is underway at this time.

       

    8. Site Power Meter

    9.         The site power meter is located on the west wall of the control room and displays the total power being consumed on site at this time in Megawatts.

       

    10. Power Supplies

              Individual power supplies are used to power magnets, RF stations, and other equipment on the SLAC site.  Specific information on power supply systems for different types of magnets is beyond the scope of this discussion of utilities systems, and can be found in the (presently under development) Beam Transport section of this training manual.

       

  2. Water Systems

     

    1. Cooling Towers

    2.         There are three cooling towers for LINAC and damping ring water systems. One cooling tower complex near MCC provides cooling water for PEP, and for some research yard water systems. Another cooling tower (404) has recently been built in the research yard area to provide cooling for SPEAR and the Central Helium Facility.

       

      Tower # Location Description
      1200  Near SDR Cools water for DRxx, LI00, LI01, and LI02. (note: damping rings also have a separate low pressure water system for cooling power supplies)
      1201 Sector 9 Cools water for LI03-LI15
      1202 Sector 22 Cools water for LI16-LI30
      1701 Near MCC Cools water for research yard systems.
      1703 Near MCC 1703 tower is an add-on to 1701 tower, and is used to cool PEP water.
      1801 Near MCC 1801 pumps provide research yard LCW for BSY, ESA, ESB, ESC, FFTB, SPEAR, and SLC arcs. It uses a heat exchange mechanism with the 1701 cooling tower.
      404 Research Yard CT404 is a basin-less cooling tower used to provide cooling water to SPEAR and the Central Helium Facility (Bldg. 127). It is also slated to be used for LCLS cooling.


       

    3. Low Conductivity Water (LCW) Systems

    4.         In the LINAC, there are three separate LCW systems in addition to several independent rad-water systems. Rad-water systems are closed water systems providing water to cool devices designed to absorb a lot of beam power, and therefore are expected to become radioactive. Special radiological procedures are followed when doing maintenance work on rad-water systems to protect workers and prevent the spread of radioactive contamination.

       

      Non-radioactive LINAC Water Systems:

      System Name System Description
      Klystron Water 1 pump every three sectors: Sectors with pumps = 3N-1, where N is an integer.
      Devices Cooled: klystron focus magnets, klystron body, subbooster, QUAD magnet coils, magnet power supplies, I&C alcove equipment, and other upstairs devices.
      Temperature Stability: not very important.
      Note: Klystron water in most sectors is not classified as rad-water, but klystron water in sectors 5 and 29 is rad-water.
      Waveguide Water 1 pump per sector.
      Devices Cooled: Main Drive Line, Phase Reference Line, Sub-drive line, rectangular waveguides.
      Temperature Stability: important.
      Note: heat load for this system is low compared to other systems.
      Accelerator Water 1 pump per sector.
      Devices Cooled: Accelerator Structure (pipes along sides of disc loaded waveguide), SLED cavities (after water returns from accelerator structure)
      Temperature Stability: very important.
      Note: in order to help maintain a constant temperature, there are heaters hooked up in series with the heat exchanger for this system.

       

      Rad-water Systems:

      System Name System Description
      BAS-II Water Cools: BAS-II dump, some positron system items.
      Pump Location: blockhouse in sector 20
      Collimator Water Cools: Sector 30 collimators.
      Pump Location: cement enclosure near radioactive materials storage area (between MCC and sector 30).
      Slit 10-30 Water Cools: 10-30 Slits (A-line momentum collimator/ beam stopper).
      Pump Location: cement enclosure by MCC lower parking lot.
      Beam Dump East Water Cools : Beam dump at end of A-line.
      Pump Location: Inside BDE PPS area.
      A Beam Dump Water NO LONGER IN USE
      Pump Location: by AN4 entrance to ESA

       

    5. Heat Exchangers

    6.  

              Water flows from the cooled device toward the heat exchanger and comes to regulator 1. Regulator 1 monitors the temperature of the water going back out to the cooled device, and adjusts the amount of water going through the heat exchanger in order to regulate the temperature of the cooling water. The regulator sends some of the water through the heat exchanger, and allows the rest to bypass the heat exchanger. The water is then recombined after the heat exchanger, and pumped back out to the cooled device. On the opposite side of the heat exchanger, regulator 2 measures the temperature of the water going to the heat exchanger, and adjusts the amount of water going through the cooling tower vs. the amount of water bypassing the cooling tower, in order to maintain a constant temperature at the heat exchanger.

       

    7. Demineralizers

    8.         Demineralizers remove dissolved minerals from water by blowing the water in to a tank of ion exchange resin, which removes the ions from the water. The demineralizers reduce the electrical conductivity of the water.

       

    9. MAKO Still

    10.         The still cleans the water by evaporating the water and then recondensing it.

       

    11. Deaerators

    12.         Deaerators remove dissolved oxygen from the water.

       

    13. Sand Filters

    14.         Sand Filters are strainers that remove particulates from the water.

       

    15. Containment Sumps

    16.         Containment sumps are ditches around each of the pump pads, which will contain the water if a leak occurs anywhere on the pump pad.
       

    17. Hydrogen Recombiners

    18.         When the high power electron beam passes through water, it breaks the water molecules apart into hydrogen and oxygen gas. The recombiner turns the hydrogen and oxygen back into water. If the Hydrogen recombiner were to stop working, the build up of hydrogen gas in the water pipes could create an explosion hazard. For this reason, the hydrogen recombiner is interlocked to the MPS system, and actuates a warning on the MCC audible warning panel. Further information about this warning and the proper response can be found in the warning and alarm response procedures. There are hydrogen recombiner systems for the sector 30 collimator water system, the Slit 10-30 water system, and the beam dump east water system.

       

    19. PEP Water Systems

    20. System Name System Description
      RF water Cools PEP RF cavities.
      HCS water High conductivity water system cools RF loads.
      KLYS water Cools klystron focus magnet and collector.
      MAG water Cools magnets (also known as “aluminum” system because pipes are aluminum)
      VAC water Cools vacuum chambers (also known as “copper” system because pipes are copper)

       

    21. Chilled Water Systems

         

      1. IR2 Chilled Water

      2.         The IR2 “Icewagon” chiller is used to cool the Q1 and B1 permanent magnets located very near the IP, as well as several components of the BaBar detector, including the Silicone Vertex Detector. Because the pin diodes used to protect the vertex detector against radiation damage are also highly sensitive to temperature changes, the earliest observed symptom of an IR2 chiller failure is generally a beam independent gradual rise in the radiation level readback from all of the vertex detector pin diodes. Temperature stability for IR magnets is critical to maintaining consistent magnetic fields at the IP, and thus maintaining high luminosity beam optics. Magnet temperature readback for the IR2 cooled magnets can be found trough the following SCP path: INDEX g ANALOG INDEX g PEP RING ANALOG g TEMPS g BEAM LINE NEAR IR g IR2 MAGNET TEMPS. If the IR2 chiller fails, the temperatures of these magnets will begin to rise, however temperature equilibrium will not be reached for several hours. Similarly, when cooling is restored, it may take several hours for the magnet temperatures to stabilize at their normal running temperatures.
                There are interlocks intended to prevent beam operation in the event of an IR2 chiller failure. Each of the magnet temperatures that can be found through the SCP path above can trigger a beam abort through the SDS action system if it exceeds the database trip point. If water flow in the IR2 chiller system is interrupted, flow switches trip and trigger the beam abort system through the PR02 Chilled LCW BATS chanel. Also, the QD1R and QD1L TRIM magnets trip off when chiller flow is interrupted.

         

      3. Refrigerated Baffle Chilled Water

      4.         The refrigerated baffle (see vacuum system description) is cooled with a chiller system. In order to achieve typical temperatures of -20 F without freezing, the chiller cools a brine solution. The chillers for the refrigerated baffle are located in the klystron gallery at the end of sector 30. There are two chiller units, but only one is used at a time. In the event of a chiller failure, HVAC techs can switch to the backup chiller. This chiller system has historically run quite reliably, only occasionally needing to be reset after power dips. Analog read back for the refrigerated baffle temperatures can be found through the following SCP path: INDEX g ANALOG INDEX g LINAC ANALOG STATUS g ACC MISC. The analog channels ASTS LI30 DPS_TEM1 and DPS_TEM2 give read back of temperatures at the two ends of the refrigerated baffle.

         

  3. Compressed Air
  4.         The site compressed air system has three air compressors located in building 23. There are two 200 horsepower compressors and one 60 horsepower compressor. In order to maintain adequate site air pressure, any two out of those three compressors must be running. The air pressure at building 23 is maintained at 110 to 128 psi. However, the air pressure drops as the compressed air is distributed around the SLAC site, so that the actual air pressure at a device actuated by compressed air is always lower than the pressure maintained at building 23.
            Compressed air is used to actuate many systems critical to beam operation. The concrete shielding blocks at CID and the positron vault are moved with compressed air, and may open and cause a PPS fault if the site air pressure is too low. Many vacuum valves are site air actuated, and will fall in and not be able to be pulled out without adequate site air pressure. Cryogenic systems depend on site air to actuate valves within the cryogenic system. Site air is also used to actuate the water system valves which regulate the flow of water through heat exchangers and cooling towers.
            There are several diagnostics that operators can use to monitor the site air system. There is SCP analog read back of the air pressure in LI00 available through the CID analog panel on the “CID MISC” display. There are also air compressor alarms and faults reported through the DCS (Distributed Control System), and used primarily by instrument techs. In the event that the control system is down and operators need to know the status of the site compressed air system, there is also an analog pressure gauge located outside the northwest corner of building 5. It shows the compressed air pressure at the location of that gauge, and normally runs at about 115psi. An image showing the location of this gauge is shown below.

     

     

     

  5. Cryogenics

     

    1. General Cryogenic System

         

      1. Controls and Diagnostics

      2.        SLAC cryogenic systems do not provide readback to any SCP, EPICS, or hardware control panels in MCC. There are local controls operated by the on duty cryotech at the Central Helium Facility, at IR 2 for BaBar systems, and at CID for P-Gun systems. There is an automatic paging system to alert offsite cryogenic system experts of possible problems, and web-based diagnostics to allow remote troubleshooting. These diagnostics are designed to be used by cryotechnicians and cryotech supervisors who need to monitor and investigate trouble with cryogenic systems from off site, but can also be useful for MCC operators. Links to these displays can be found through the EFD (Experimental Facilities Department) web page, or here:


        BaBar Cryogenic Systems

        Research Yard Refrigerator Facility

        (Note: These links may not work during periods when the cryogenic systems are not operating.)


                Although cryogenic systems are listed in this manual as “utilities” because of their function providing cooling to several accelerator and detector components, it is important to note that many components of the cryogenic systems are dependent on other site utilities including electrical systems, compressed air systems, and cooling water systems.

         

      3. System Layout

      4.         The following schematic diagram shows the general layout of the SLAC cryogenic system.

         

  1. Helium Gas Storage Tanks

  2.         There are two large helium gas storage tanks located in the research yard. They store helium at low pressure (up to 240psi) and ambient temperature. The helium compressors compress helium from these tanks. In addition to these low pressure helium storage tanks, there are high pressure (2500psi), ambient temperature helium gas tube trailers that can provide additional gas to cryogenic helium system when it is needed.

     

  3. Helium Compressors

  4.         Three helium compressors are housed in building 127 in the research yard. All of these compressors operate by mixing the helium with oil and using a large mechanical screw to compress the helium and oil mixture. The three compressors are all manufactured by the Sullair Corporation, and are referred to as Sullair #1, Sullair #2, and Sullair #3. Sullair #1 and Sullair #2 are 300kW compressors, each capable of producing 50g/s of 16 Bar compressed helium. Sullair #3 is a 600kW unit, capable of producing 100g/s of 16 Bar compressed helium gas. The compressed helium is then pumped to a refrigerator through a high pressure, ambient temperature gas line. The compressors can be used interchangeably to provide compressed helium to either the BaBar refrigerator or the research yard refrigerator.
            Each compressor has an oil removal system which separates the compressed helium from the compressor oil and filters the oil before returning the oil to the compressor for reuse. It is important that the oil be completely removed from the compressed helium. If residual oil or other contaminants remain in the helium as it is cooled in the refrigerator, the oil or other contaminants will freeze and block pipes.
            The helium compressors depend on cooling water from CT404 to cool the compressor oil. They also depend on electrical power to run their motors. In the event of a power glitch interrupting power to the compressors, it is important to get the compressors back up as soon as possible in order to get the compressor and refrigerator system back to equilibrium, and thus minimize the interruption of the supply of liquid helium to cryogenically cooled devices. If cooling water from CT404 is unavailable, there are two portable cooling towers located in the research yard that can be used to temporarily provide cooling water to the research yard compressors. These backup cooling towers should be turned on as soon as possible after a CT404 failure.

     

  5. Refrigerators

  6.         The cryogenic refrigerators use a series of gas expansion turbines and heat exchangers to cool and liquefy the compressed helium that is supplied by the research yard compressors. When equilibrium running conditions have been reached within the refrigerators, the refrigerators divert 40% of the incoming compressed helium through turbines. These turbines lower the temperature of the helium by decreasing its pressure. The cooled lower pressure helium then passes through heat exchangers that cool the remaining 60% of the incoming high pressure helium.
            The refrigerators also contain a series of heat exchangers that cool the incoming high pressure helium using low pressure cold helium gas returning from the cold end of the refrigerator. After being fully cooled by gas expansion, cold low pressure helium passes through these heat exchangers on its way back to the central compressor facility. These heat exchangers contribute additional cooling of the high pressure gas line, adding to the cooling that is done by the heat exchangers in the turbine line. Thus, the helium that was cooled by both the turbine line heat exchangers and the cold gas return line heat exchangers is at a lower temperature than the helium that was only cooled by the turbine line heat exchangers. As the cooling process progresses, the temperature of the output helium gradually becomes lower, until the temperature is low enough to liquefy helium. The cryogenic helium system is a closed system, meaning that all of the helium used in the refrigerator and the experimental facility is recovered, passes back through the refrigerator return line heat exchangers to provide additional cooling to incoming gas, and is then returned to the research yard compressor facility through a low pressure, ambient temperature gas line.
            After the high pressure helium has been cooled by all of the heat exchangers, it is ready to be liquefied. In order to produce liquid helium, the high pressure cold helium is sent through a Joule Thompson expansion valve (JT valve). The gas undergoes enough additional cooling as it expands through the valve to cause it to liquefy. Further liquefication occurs as the helium line subsequently passes through a bath of previously liquefied helium that is stored in the refrigerator’s internal dewar. The newly liquefied helium is then piped into an external storage dewar.
            Helium refrigerators depend on site air and cooling water. Compressed site air is used to operate the pneumatic valves that regulate the flow of helium through the refrigerator system. A backup compressed air system can temporarily be used in the event of a site compressed air system failure. It uses compressed air from tube trailer storage tanks to actuate valves when the site compressed air system is down. A small amount of cooling water is used to cool the refrigerator turbines. Water from cooling tower 1701 is used to cool the turbines. Backup chillers are in place to be used for this purpose if CT1701 is down.

     

  1. BaBar Cryogenic System

  2.         The BaBar cryogenic refrigerator and 4000 L liquid helium storage tank are located in building 624, adjacent to the IR2 hall. A high pressure helium line is run from the research yard helium compressor building to the IR2 refrigerator system, and a low pressure helium return line runs back to the compressors from IR2. Both of these lines are at ambient temperature. The BaBar refrigerator can receive a helium flow rate of up to 150 g/s at 16 Bar. However, the BaBar system normally operates with an input helium flow rate of 60 to 70 g/s, and can operate with a helium flow rate as low as 50 g/s. This allows the system to run using only one of the two lower power Sullair compressors, leaving the other compressor available as a backup.

     

  3. P-Gun Cryogenic System

  4.         The polarized gun cathode is cooled by a continuous flow of gaseous nitrogen running through cooling lines that are in thermal contact with the bracket that holds the cathode in place. The nitrogen gas lines run in a closed loop from the gun housing in CID to a heat exchanger in the klystron gallery at sector 0. The nitrogen gas temperature at the inlet to the cathode is normally 6 degrees C, and the outlet temperature is normally 9 degrees C. In the heat exchanger, the gaseous nitrogen lines run through a bath of liquid nitrogen. The gaseous nitrogen continuously flows through the closed loop and is repeatedly cooled and heated as it passes through the heat exchanger and the p-gun housing. The liquid nitrogen for the heat exchanger is supplied from a liquid nitrogen dewar outside of sector 0. That stationary dewar is refilled as necessary from a towable dewar by cryotech personnel.
            Alarms from the p-gun cryogenic system are sent directly to the on-call cryotech. SCP readback of temperatures in this system can also be found on the CID analogs panel, on the button labeled “POL GUN cooling”.
            The p-gun cathode will begin to degrade if it is allowed to heat up, even if it is not actively in use for beam production at the time of the heating. In order to maintain the p-gun as a usable spare gun during periods when the t-gun is being used for beam production, the p-gun cathode must be kept cold. Gun system experts estimate that the cathode will begin to degrade if the p-gun cryogenic system is down for more than two hours.

     

  5. E158 Hydrogen Target Cryogenic System

            The research yard cryogenic system can be set up to fit the needs of experimenters. Most recently it has been used to supply liquid helium to cool the hydrogen for the E158 liquid hydrogen target. It had previously been used for the SLD detector. The research yard refrigerator can receive an input helium flow of up to 100g/s at 16Bar. This provides more than 1 KW of cooling at 4.2 K.

  1. Gas Systems

     

    1. Dry Nitrogen

    2.         There are several large liquid nitrogen tanks on the SLAC site. These tanks provide both liquid nitrogen and dry nitrogen gas to areas such as SSRL, the SLC collider hall, the polarized electron source, the BaBar detector, central lab, and the research yard cryogenic system. These tanks are periodically filled by an outside vendor. Smaller liquid nitrogen dewars are used to provide liquid nitrogen to users at ES&H, and the gun test lab. Small dewars are also used for the cooling of the LINAC main drive line. The small dewars are refilled by cryogenics staff from the liquid nitrogen supply in the larger storage tanks.

       

    3. PLIC Gas

    4.         PLIC gas is a 95% nitrogen, 5% argon gas mixture. Instrument tech personnel monitor PLIC gas bottle pressure, and swap in new gas bottles when necessary.

       

    5. Helium Gas

    6.         There is a site wide helium gas distribution system used to distribute pure 300K He gas throughout the site. The gas is supplied by high pressure helium tube trailers that are filled offsite by a outside vendor. These tube trailers are located in the research yard. This site wide helium gas distribution system is maintained by the cryogenics group, but is independent of the cryogenic helium system discussed in the cryogenics section of this document. Connections between this helium system and the cryogenic helium system are possible, but are generally avoided in order to prevent contamination of the hydrogen used for the cryogenic system.

       

    7. Argon

    8.         There is a large reservoir of liquid argon in the SLD Liquid Argon Calorimeter. This argon is maintained at temperature by a continuous flow of liquid nitrogen from a large storage tank next to the collider hall. This liquid nitrogen tank is refilled by an outside vendor.

       

    9. Hydrogen Gas

    10.         Presently hydrogen gas is only used at SLAC for the brazing ovens located at Heavy Fab and the klystron lab.  The hydrogen for these ovens is stored in nearby tanks.  The tanks are filled by an outside vendor.  There is also a high pressure hydrogen tube trailer, and a low pressure hydrogen storage tank located near the ESA counting house.  These tanks were used for the E158 liquid hydrogen target.  These tanks do still contain hydrogen, but the hydrogen is not presently being used.

       

    11. BaBar Detector Gas Systems

    12.         The BaBar detector consists of several layers of detector equipment.  Each layer is designed to detect different properties of the particles (and decay products of particles) produced during PEPII collisions.  Because each layer is uniquely designed for its detection purpose, each layer has different gas system requirements. The table below shows the gasses associated with each detector layer:

       

      Detector Layer Gasses Used
      Detector Magnet Gas: Cryogenically cooled liquid helium

      Purpose: Cools the superconducting solenoid magnet.

      Notes: See the cryogenics section of this document for details on the cryogenic system that provides this liquid helium.

      Vertex Detector The vertex detector is composed of layers silicone-strip detectors.  No gas is required for this layer of the detector.
      Drift Chamber Gas: A mixture of 80% helium and 20% isobutane, also, nitrogen flushes the drift chamber endplates.

      Purpose: Charged particles are tracked as they pass through a chamber containing an array of sense wires and an ionizable gas mizture.  The gas is ionized by the charged particles passing through the chamber, and electrons liberated in the ionization events are drawn to the nearest positively charged sense wire.  

      Notes: The helium-isobutane mix is flammable.  Nitrogen flushes the drift chamber endplates to remove any helium-isobutane mix that may have escaped the drift chamber volume.  These gasses create an oxygen deficiency hazard within the tunnel through the DIRC.  This small tunnel into the detector is, therefore, a permit required confined space.

      Detector of Internally Reflected Cherenkov Light (DIRC) Gas: Dry nitrogen

      Purpose: The DIRC uses quartz bars to internally reflect Cherenkov light to a set of PMTs.  The PMTs cover an interior wall of a water filled standoff box, opposite the windows to the internally reflecting quartz bars. A constant dry nitrogen purge keeps the airspace around the quartz bars dry. There are also moisture sensors in the DIRC barboxes (which contain the quartz bars), sampling the nitrogen in order to quickly detect any presence of water near the DIRC crystals.  These moisture sensors are interlocked to dump the DIRC standoff box water in the event of a possible water leak from the standoff box into a DIRC barbox.

      Electromagnetic Calorimitier (EMC) Gas: Dry Nitrogen

      Notes: The EMC uses hygroscopic cesium iodide crystals which would be damaged if they came into contact with water.  A dry nitrogen purge prevents this damage.

      Instrumented Flux Return (IFR) Resistive Plate Chambers (RPCs) gas: A mix of 61.2% argon, 34.4% freon and 4.4% isobutane.

      Limited Streamer Tubes (LSTs) gas: A mix of argon, CO2 and isobutane.

      Purpose:  Particles coming through the IFR cause ionization of the gas mixture, and this ionization allows sparking between the plates of the RPCs.

      Notes: These gasses are flammable, but not explosive in the mixtures used.

              All BaBar detector gas statuses (except for the BaBar magnet cryogenic gas system) are monitored and controlled by the BaBar control room staff, not the MCC operations staff.  MCC operators should, however, be aware of the presence of these other specialized gas systems for the BaBar detector. The support infrastructure used to mix and store the BaBar detector gasses is housed in the BaBar "Gas Shack" (bldg 636), which is located near the IR2 pump pad, above the IR2 hall.